Fault current: two 50 MVA generators, feeder reactor
Short answer
On 50 MVA, 11 kV base with negligible feeder reactance, parallel reactance is 0.01875 pu. Fault current = 1/0.01875 = 53.33 pu = 139.96 kA (G1: 52.49 kA, G2: 87.48 kA), fault power 2666.7 MVA. To reduce by 40% (to 1600 MVA), add series reactor of 0.0303 Ω (0.0125 pu).
Two generators each of capacities 50 MVA, 11 kV having their sub transient reactance of 5% and 3% respectively operating in parallel and supplying to a common load through a feeder. If a 3 phase to ground fault occurs on the outgoing feeder, calculate the fault current supplied by each generator and fault power on the outgoing feeder. Also calculate the value of reactor to be connected in series with the outgoing feeder to reduce the fault level by 40 %.
The feeder reactance is not given, so it is taken as negligible: the fault is close to the bus. Fault MVA .
Base: 50 MVA, 11 kV; ; .
G1 50MVA,5% G2 50MVA,3%
| |
====+=====+=======+==== 11 kV bus
| outgoing feeder
F
Fault current and fault power
Current from each generator
Current divides inversely as the reactances:
Reactor for 40 % reduction
New fault MVA MVA.
Answer: kA (G1: 52.49 kA, G2: 87.48 kA), fault power = 2666.7 MVA; series reactor = 0.0125 pu ≈ 0.0303 Ω (fault level becomes 1600 MVA).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault level: two 40 MVA generators, 2 Ω feeder · Power Plant Equipment, chapter 4 · asked 5×
- Feeder reactor: 40 and 30 MVA, 50% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Feeder reactor: 40 and 30 MVA, 40% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4
- Fault current: two 50 MW generators, reactor inductance · Power Plant Equipment, chapter 4
- Fault level: two 50 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 100 MVA base, two parallel paths · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3