A reactance diagram uses only p.u. reactances, neglecting resistance and shunt branches, for fault/studies. With 100 MVA, 13.8 kV gen base: G j0.2, all transformers j0.2, line1 j0.1033, line2 j0.4017, motor j0.2256, load 1.2667+j0.95.

What is the significance of reactance diagram? The single line diagram of a three phase power system is shown in the figure. Draw a reactance diagram considering a base of 100 MVA and 13.8 kV on generator side. G: 90 MVA, 13.8 kV, Xg = 18%; T1 = 50 MVA, 13.8/220 kV, XT1 = 10%; T2 = 50 MVA, 220/11 kV, XT2 = 10%; T3 = 50 MVA, 13.8/132 kV, XT3 = 10%; T4 = 50 MVA, 132/11 kV, XT4 = 10%; M: 80 MVA, 10.45 kV, Xm = 20%; Load: 57 MVA, 0.8 pf lagging at 10.45 kV; Xline1 = 50 Ω, Xline2 = 70 Ω. [Figure: generator G at bus 1 feeds two parallel paths to bus 4: T1 (bus 1–2) → Line-1 at 220 kV (bus 2–3) → T2 (bus 3–4); and T3 (bus 1–5) → Line-2 at 132 kV (bus 5–6) → T4 (bus 6–4). Motor M and the load are connected at bus 4.]

Significance of the reactance diagram

A reactance diagram is the per-phase equivalent circuit of the system, drawn from the single line diagram, in which:

  • resistances, magnetising branches and line charging are neglected
  • all values are in p.u. on a common base

It is used for short-circuit (fault) calculations and stability studies, where the reactances dominate. It gives a simple network that can be reduced quickly.

Base values

  • Sb=100S_b = 100 MVA, and Vb=13.8V_b = 13.8 kV at the generator (bus 1).
SectionBase kVZbZ_b (Ω)
Bus 1 (generator)13.8–
Line 1 (via T1 13.8/220)2202202/100=484220^2/100 = 484
Line 2 (via T3 13.8/132)1321322/100=174.24132^2/100 = 174.24
Bus 4 (via T2 220/11 or T4 132/11)11–

Both paths give 11 kV at bus 4, so the bases are consistent.

Per-unit values

XG=0.18×10090=0.2XT1=XT2=XT3=XT4=0.1×10050=0.2XL1=50484=0.1033XL2=70174.24=0.4017XM=0.2×10080×(10.4511)2=0.2256\begin{aligned} X_G &= 0.18\times\frac{100}{90} = 0.2\\ X_{T1} = X_{T2} = X_{T3} = X_{T4} &= 0.1\times\frac{100}{50} = 0.2\\ X_{L1} &= \frac{50}{484} = 0.1033\\ X_{L2} &= \frac{70}{174.24} = 0.4017\\ X_M &= 0.2\times\frac{100}{80}\times\left(\frac{10.45}{11}\right)^2 = 0.2256 \end{aligned}

Load: S=57/100=0.57S = 57/100 = 0.57 p.u. at a power factor of 0.8 lagging, and V=10.45/11=0.95V = 10.45/11 = 0.95 p.u. As a series impedance:

ZL=∣V∣2S∗=0.9520.57∠36.87∘=1.5833∠36.87∘=1.2667+j0.95 p.u.Z_L = \frac{|V|^2}{S^*} = \frac{0.95^2}{0.57}\angle36.87^\circ = 1.5833\angle36.87^\circ = 1.2667 + j0.95\ \text{p.u.}

Reactance diagram

               T1     L1      T2
          +--j0.2--j0.1033--j0.2--+
  j0.2    |                       |
 +-/\/\---+ bus1            bus4  +---+------+
 |        |                       |   |      |
(Eg)      +--j0.2--j0.4017--j0.2--+ j0.2256 1.2667
 |             T3     L2      T4     |   +j0.95
 |                                  (Em)  |
 +------------- reference -----------+----+
Elementp.u.
Gj0.2
T1, T2, T3, T4j0.2 each
Line 1j0.1033
Line 2j0.4017
Motorj0.2256
Load1.2667 + j0.95