- 2080 Chaitra · 8 marks
Reactance diagram: 100 MVA base, two parallel paths
Short answer
A reactance diagram uses only p.u. reactances, neglecting resistance and shunt branches, for fault/studies. With 100 MVA, 13.8 kV gen base: G j0.2, all transformers j0.2, line1 j0.1033, line2 j0.4017, motor j0.2256, load 1.2667+j0.95.
What is the significance of reactance diagram? The single line diagram of a three phase power system is shown in the figure. Draw a reactance diagram considering a base of 100 MVA and 13.8 kV on generator side. G: 90 MVA, 13.8 kV, Xg = 18%; T1 = 50 MVA, 13.8/220 kV, XT1 = 10%; T2 = 50 MVA, 220/11 kV, XT2 = 10%; T3 = 50 MVA, 13.8/132 kV, XT3 = 10%; T4 = 50 MVA, 132/11 kV, XT4 = 10%; M: 80 MVA, 10.45 kV, Xm = 20%; Load: 57 MVA, 0.8 pf lagging at 10.45 kV; Xline1 = 50 Ω, Xline2 = 70 Ω. [Figure: generator G at bus 1 feeds two parallel paths to bus 4: T1 (bus 1–2) → Line-1 at 220 kV (bus 2–3) → T2 (bus 3–4); and T3 (bus 1–5) → Line-2 at 132 kV (bus 5–6) → T4 (bus 6–4). Motor M and the load are connected at bus 4.]
Significance of the reactance diagram
A reactance diagram is the per-phase equivalent circuit of the system, drawn from the single line diagram, in which:
- resistances, magnetising branches and line charging are neglected
- all values are in p.u. on a common base
It is used for short-circuit (fault) calculations and stability studies, where the reactances dominate. It gives a simple network that can be reduced quickly.
Base values
- MVA, and kV at the generator (bus 1).
| Section | Base kV | (Ω) |
|---|---|---|
| Bus 1 (generator) | 13.8 | – |
| Line 1 (via T1 13.8/220) | 220 | |
| Line 2 (via T3 13.8/132) | 132 | |
| Bus 4 (via T2 220/11 or T4 132/11) | 11 | – |
Both paths give 11 kV at bus 4, so the bases are consistent.
Per-unit values
Load: p.u. at a power factor of 0.8 lagging, and p.u. As a series impedance:
Reactance diagram
T1 L1 T2
+--j0.2--j0.1033--j0.2--+
j0.2 | |
+-/\/\---+ bus1 bus4 +---+------+
| | | | |
(Eg) +--j0.2--j0.4017--j0.2--+ j0.2256 1.2667
| T3 L2 T4 | +j0.95
| (Em) |
+------------- reference -----------+----+
| Element | p.u. |
|---|---|
| G | j0.2 |
| T1, T2, T3, T4 | j0.2 each |
| Line 1 | j0.1033 |
| Line 2 | j0.4017 |
| Motor | j0.2256 |
| Load | 1.2667 + j0.95 |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Three-phase single-way controlled rectifier, α = 90° · Power Electronics, chapter 3 · asked 4×
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3