Short answer
On 90 MVA base: X_G=0.25, X_T1=0.0446, X_line=0.4269, X_T2=0.0310, X_M1=0.2231, X_M2=0.2789 pu. Base voltages: 11 kV, 145.2 kV, 12.70 kV.
A 90 MVA, 11 kV 3-phase generator has a reactance of 25%. The generator supplies two motors through transformers and transmission line shown in figure below. The transformer T1 is a 3-phase, 100 MVA, 10/132 kV, 6% reactance. The transformer T2 is composed of three single phase units each rated at 30 MVA, 66/10 kV with 5% reactance. The connection of T1 and T2 are shown in figure. The motors are rated at 50 MVA and 40 MVA, both 10 kV and 20% reactance. Taking the generator rating as base, draw the per unit reactance diagram. The reactance of the line is 100 Ω. [Figure: G1 → T1 (Δ on generator side, Y grounded on line side) → Line → T2 (Y grounded on line side, Δ on motor side) → bus feeding M1 (Y, grounded) and M2 (Δ).]
Base: 90 MVA and 11 kV in the generator circuit (generator rating). Base voltages in other zones follow the line-to-line turns ratios.
Base voltages
- Generator zone: kV
- Line zone (T1 is 10/132 kV): kV
- T2: three single-phase 66/10 kV units connected Y (line side) – Δ (motor side), so line-to-line ratio is kV. Motor zone:
Per-unit reactances (on 90 MVA)
| Element | X (pu, 90 MVA base) |
|---|---|
| Generator | 0.2500 |
| T1 | 0.0446 |
| Line (100 Ω) | 0.4269 |
| T2 | 0.0310 |
| Motor M1 | 0.2231 |
| Motor M2 | 0.2789 |
Reactance diagram
j0.0446 j0.4269 j0.0310
+---/\/\/-----/\/\/-----/\/\/---+--------+
| T1 line T2 | |
j0.25 j0.2231 j0.2789
| | |
(Eg) (Em1) (Em2)
| | |
+-------------------------------+--------+
reference bus
Answer: On 90 MVA base: , , , , , pu; base voltages 11 kV, 145.2 kV and 12.70 kV.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Impedance diagram: 25 MVA generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 100 MVA base, two parallel paths · Power System Analysis I, chapter 3
- Per unit values: 100 MVA generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: two generators, two motors, j50 Ω line · Power System Analysis I, chapter 3
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- L-L fault through Zf with two motors · Power System Analysis II, chapter 5
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- IDMT relays across 132/11 kV transformer (3500 A) · Switchgear and Protection, chapter 7