- 2083 Baishakh (new course) · 7 marks
L-L fault through Zf with two motors
Short answer
On 25 MVA base, positive/negative Thevenin impedance at the motor bus is Z1 = Z2 = j0.1597 pu. With Zf = j0.1 pu, Ia1 = -j2.384 pu, and L-L fault current is √3 × 2.384 = 4.13 pu = 5418 A.
For the power system network shown below, if Line to Line fault occurs at point 'F' then find the fault current, take fault impedance Zf = 0.1 p.u. For Generator: X1 = X2 = 20%, X0 = 5%; For Both Motor: X1 = X2 = 25%, X0 = 10%; For Both Transformer: X1 = X2 = X0 = 10%. The neutral reactance of generator G1 and motor M2 are in p.u. [Figure: G1 25 MVA, 11 kV, Y grounded through Xn = 0.1 - T1 30 MVA, 10.8/121 kV, Δ/Y grounded - line X1 = X2 = 100 Ω, X0 = 250 Ω - T2 30 MVA, 121/10.8 kV, Y grounded/Δ - motor bus with M1 (15 MVA, 10 kV, Y ungrounded) and M2 (7.5 MVA, 10 kV, Y grounded through Xn = 0.036); fault F at the motor bus]
Assumptions: base 25 MVA, 11 kV in the generator circuit; pre-fault voltage at F is 1 pu with no load current; pu. An L-L fault involves only positive and negative sequence networks, so the neutral reactances and zero-sequence data are not needed.
Base voltages
Per-unit reactances (25 MVA)
| Element | Calculation | (pu) |
|---|---|---|
| G1 | given | 0.20 |
| T1, T2 | 0.0803 each | |
| Line | 0.1646 | |
| M1 | 0.3444 | |
| M2 | 0.6887 |
Positive (and negative) sequence network at F
Eg-j0.2-T1 j0.0803-line j0.1646-T2 j0.0803-(F)
|
+-------------+
| |
j0.3444 j0.6887
Em1 Em2
L-L fault through
Base current at the motor bus (11 kV):
Answer: L-L fault current at F ≈ 4.13 pu ≈ 5.42 kA.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- L-G fault at bus 1 through Zf · Power System Analysis II, chapter 5
- L-L fault at point q with two motors · Power System Analysis II, chapter 5
- L-G fault through Zf: currents and voltages · Power System Analysis II, chapter 5
- Fault through impedance at bus 2 · Power System Analysis II, chapter 3
- Fault at generator terminal feeding motor · Power System Analysis II, chapter 3
- Fault at both ends of a 50 Ω line · Power System Analysis II, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Impedance diagram: 25 MVA generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×