- 2070 Chaitra · 10 marks
L-G fault through Zf: currents and voltages
Short answer
Positive sequence has a-b-c rotation and generator source; negative has a-c-b; zero has no rotation, all phasors in phase. For an L-G fault through Zf on phase a with solidly grounded neutral, the three sequence networks connect in series with 3Zf. Sequence currents: I0=I1=I2=Ea/(Z1+Z2+Z0+3Zf). Fault current If=3Ea/(Z1+Z2+Z0+3Zf). Faulted phase voltage Va=ZfIf; healthy phase voltages Vb=I1[(a^2-a)Z2+(a^2-1)Z0+3a^2Zf], Vc=I1[(a-a^2)Z2+(a-1)Z0+3aZf].
What is the difference between symmetrical components of positive, negative and zero phase sequence? A 3-phase synchronous generator with its neutral solidly grounded and operating at no load develops an L-G fault in one of the phase have fault impedance Zf. Derive expressions for the fault currents and the line to ground voltage at the location of the fault at all the phases.
Difference between positive, negative and zero sequence components
| Feature | Positive sequence | Negative sequence | Zero sequence |
|---|---|---|---|
| Magnitudes | Equal | Equal | Equal |
| Phase displacement | 120° | 120° | 0° (all in phase) |
| Phase order | a-b-c (same as system) | a-c-b (reverse) | No rotation |
| Relation to phase a | , | , | |
| Source in generator | Yes (EMF) | No | No |
| Return path needed | No | No | Neutral/ground () |
| Effect | Useful power, torque | Reverse torque, rotor heating | Ground currents, interference |
L-G fault through on phase a (solidly grounded, no load)
Generator equations: , , (solid grounding: ).
Boundary conditions (fault on phase a through )
a o----------+
b o--- (Ib=0)
c o--- (Ic=0)
| Ia = If
Zf
|
ground
Sequence currents
So the same current flows in all three sequence networks, which means they are in series.
Voltage condition
Substituting the network equations:
Fault current
For a bolted fault (): . The currents in the healthy phases are .
Interconnection of sequence networks
F1 --(Ea)--[Z1]-- N1 == F2 --[Z2]-- N2 == F0 --[Z0]-- N0
| |
+------------------------[ 3Zf ]------------------------+
common current Ia1 = Ia2 = Ia0
The three networks are connected in series with : is joined to (the "==" links), is joined to , and returns to through . The common current flows through all of them. Both conditions ( and ) are satisfied only by this series connection.
Line-to-ground voltages at the fault
Let .
Phase a:
Phase b:
Replacing :
Phase c: similarly, with :
For a bolted fault (): and
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault currents of isolated-neutral 380 V generator · Power System Analysis II, chapter 5
- Sequence components of load phase voltages · Power System Analysis II, chapter 4
- L-G fault at bus 1 through Zf · Power System Analysis II, chapter 5
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- Line currents with isolated and grounded neutral · Power System Analysis II, chapter 4
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Advantages of solidly grounded generators · Power Plant Design, chapter 4
- Delta load (15+j20) phase and line currents · Basic Electrical Engineering, chapter 8