L-G fault through Zf: currents and voltages

Short answer

Positive sequence has a-b-c rotation and generator source; negative has a-c-b; zero has no rotation, all phasors in phase. For an L-G fault through Zf on phase a with solidly grounded neutral, the three sequence networks connect in series with 3Zf. Sequence currents: I0=I1=I2=Ea/(Z1+Z2+Z0+3Zf). Fault current If=3Ea/(Z1+Z2+Z0+3Zf). Faulted phase voltage Va=ZfIf; healthy phase voltages Vb=I1[(a^2-a)Z2+(a^2-1)Z0+3a^2Zf], Vc=I1[(a-a^2)Z2+(a-1)Z0+3aZf].

What is the difference between symmetrical components of positive, negative and zero phase sequence? A 3-phase synchronous generator with its neutral solidly grounded and operating at no load develops an L-G fault in one of the phase have fault impedance Zf. Derive expressions for the fault currents and the line to ground voltage at the location of the fault at all the phases.

Difference between positive, negative and zero sequence components

FeaturePositive sequenceNegative sequenceZero sequence
MagnitudesEqualEqualEqual
Phase displacement120°120°0° (all in phase)
Phase ordera-b-c (same as system)a-c-b (reverse)No rotation
Relation to phase aVb1=a2Va1V_{b1} = a^2V_{a1}, Vc1=aVa1V_{c1} = aV_{a1}Vb2=aVa2V_{b2} = aV_{a2}, Vc2=a2Va2V_{c2} = a^2V_{a2}Vb0=Vc0=Va0V_{b0} = V_{c0} = V_{a0}
Source in generatorYes (EMF)NoNo
Return path neededNoNoNeutral/ground (In=3I0I_n = 3I_0)
EffectUseful power, torqueReverse torque, rotor heatingGround currents, interference

L-G fault through ZfZ_f on phase a (solidly grounded, no load)

Generator equations: Va1=Ea−Z1Ia1V_{a1} = E_a - Z_1I_{a1}, Va2=−Z2Ia2V_{a2} = -Z_2I_{a2}, Va0=−Z0Ia0V_{a0} = -Z_0I_{a0} (solid grounding: Z0=Zg0Z_0 = Z_{g0}).

Boundary conditions (fault on phase a through ZfZ_f)

  a o----------+
  b o---  (Ib=0)
  c o---  (Ic=0)
               |  Ia = If
              Zf
               |
            ground
Ib=0,Ic=0,Va=ZfIaI_b = 0, \qquad I_c = 0, \qquad V_a = Z_fI_a

Sequence currents

[Ia0Ia1Ia2]=13[1111aa21a2a][Ia00]⇒Ia0=Ia1=Ia2=Ia3\begin{bmatrix} I_{a0}\\I_{a1}\\I_{a2} \end{bmatrix} = \frac13\begin{bmatrix} 1&1&1\\1&a&a^2\\1&a^2&a \end{bmatrix}\begin{bmatrix} I_a\\0\\0 \end{bmatrix} \quad\Rightarrow\quad I_{a0} = I_{a1} = I_{a2} = \frac{I_a}{3}

So the same current flows in all three sequence networks, which means they are in series.

Voltage condition

Va=Va0+Va1+Va2=ZfIa=3ZfIa1V_a = V_{a0} + V_{a1} + V_{a2} = Z_fI_a = 3Z_fI_{a1}

Substituting the network equations:

−Z0Ia1+Ea−Z1Ia1−Z2Ia1=3ZfIa1-Z_0I_{a1} + E_a - Z_1I_{a1} - Z_2I_{a1} = 3Z_fI_{a1} Ia1=Ia2=Ia0=EaZ1+Z2+Z0+3ZfI_{a1} = I_{a2} = I_{a0} = \frac{E_a}{Z_1 + Z_2 + Z_0 + 3Z_f}

Fault current

If=Ia=3Ia1=3EaZ1+Z2+Z0+3ZfI_f = I_a = 3I_{a1} = \frac{3E_a}{Z_1 + Z_2 + Z_0 + 3Z_f}

For a bolted fault (Zf=0Z_f = 0): If=3EaZ1+Z2+Z0I_f = \dfrac{3E_a}{Z_1+Z_2+Z_0}. The currents in the healthy phases are Ib=Ic=0I_b = I_c = 0.

Interconnection of sequence networks

   F1 --(Ea)--[Z1]-- N1 == F2 --[Z2]-- N2 == F0 --[Z0]-- N0
   |                                                       |
   +------------------------[ 3Zf ]------------------------+
              common current  Ia1 = Ia2 = Ia0

The three networks are connected in series with 3Zf3Z_f: N1N_1 is joined to F2F_2 (the "==" links), N2N_2 is joined to F0F_0, and N0N_0 returns to F1F_1 through 3Zf3Z_f. The common current Ia1I_{a1} flows through all of them. Both conditions (Ia0=Ia1=Ia2I_{a0} = I_{a1} = I_{a2} and Va0+Va1+Va2=3ZfIa1V_{a0}+V_{a1}+V_{a2} = 3Z_fI_{a1}) are satisfied only by this series connection.

Line-to-ground voltages at the fault

Let I1=Ia1=Ia2=Ia0=EaZ1+Z2+Z0+3ZfI_1 = I_{a1} = I_{a2} = I_{a0} = \dfrac{E_a}{Z_1+Z_2+Z_0+3Z_f}.

Phase a:

Va=ZfIa=3ZfI1=3ZfEaZ1+Z2+Z0+3ZfV_a = Z_fI_a = 3Z_fI_1 = \frac{3Z_fE_a}{Z_1 + Z_2 + Z_0 + 3Z_f}

Phase b:

Vb=Va0+a2Va1+aVa2=−Z0I1+a2(Ea−Z1I1)−aZ2I1\begin{aligned} V_b &= V_{a0} + a^2V_{a1} + aV_{a2} \\ &= -Z_0I_1 + a^2(E_a - Z_1I_1) - aZ_2I_1 \end{aligned}

Replacing a2Ea=a2I1(Z1+Z2+Z0+3Zf)a^2E_a = a^2I_1(Z_1 + Z_2 + Z_0 + 3Z_f):

Vb=I1[(a2−a)Z2+(a2−1)Z0+3a2Zf]V_b = I_1\left[(a^2 - a)Z_2 + (a^2 - 1)Z_0 + 3a^2Z_f\right]

Phase c: similarly, with aEa=aI1(Z1+Z2+Z0+3Zf)aE_a = aI_1(Z_1+Z_2+Z_0+3Z_f):

Vc=I1[(a−a2)Z2+(a−1)Z0+3aZf]V_c = I_1\left[(a - a^2)Z_2 + (a - 1)Z_0 + 3aZ_f\right]

For a bolted fault (Zf=0Z_f = 0): Va=0V_a = 0 and

Vb=Ea[(a2−a)Z2+(a2−1)Z0]Z1+Z2+Z0,Vc=Ea[(a−a2)Z2+(a−1)Z0]Z1+Z2+Z0V_b = \frac{E_a\left[(a^2 - a)Z_2 + (a^2 - 1)Z_0\right]}{Z_1 + Z_2 + Z_0}, \quad V_c = \frac{E_a\left[(a - a^2)Z_2 + (a - 1)Z_0\right]}{Z_1 + Z_2 + Z_0}