SLG fault at bus 3, currents and voltages
Short answer
Bus 3 lies between two delta windings, so Z0 is infinite. Consequently, SLG fault current is zero. Phase voltages: Va=0, Vb=1.732∠-150° pu (115 kV line-to-ground), Vc=1.732∠150° pu (115 kV).
In a power system network shown in figure below, single line to ground (SLG) fault occurs at bus 3. i. Draw the positive, negative and zero sequence networks; ii. Determine phase currents in per units and amperes; iii. Phase voltages in per units and kilovolts. Specifications of the equipments are as under: G1: 100 MVA, 13.8 kV, X1 = X2 = 15% and X0 = 5%; G2: 100 MVA, 13.8 kV, X1 = X2 = 15% and X0 = 5%; G3: 100 MVA, 13.8 kV, X1 = X2 = 15% and X0 = 5%; T1: 100 MVA, 13.8/115 kV, X1 = X2 = X0 = 20%; T2: 100 MVA, 115/13.8 kV, X1 = X2 = X0 = 18%; Line: 100 MVA, 115 kV, X1 = X2 = 30% and X0 = 90%. [Figure: G1 (Y, ungrounded) and G2 (Y grounded) at bus 1 - T1 (Y grounded through j0.01 pu on bus 1 side / Δ) - bus 2 - line - bus 3 - T2 (Δ / Y grounded through 0.02 pu on bus 4 side) - bus 4 - G3 (Y grounded through j0.03 pu)]
Base: 100 MVA; 13.8 kV (generator buses 1 and 4), 115 kV (buses 2 and 3). Pre-fault voltage 1 pu, no load. From the figure: T1 is Yg (through j0.01) on the bus 1 side and Δ on the bus 2 side; T2 is Δ on the bus 3 side and Yg (through 0.02) on the bus 4 side; G1 is ungrounded, G2 solidly grounded, G3 grounded through j0.03.
(i) Sequence networks
Positive (emfs at G1, G2, G3):
G1 j0.15 \
(1)-j0.2-(2)-j0.3-(3)-j0.18-(4)-j0.15-G3
G2 j0.15 / |
F
Negative: same reactances, no emfs.
Zero:
G2: ref-j0.05-(1) G1: open (ungrounded)
T1: (1)-[3(j0.01)+j0.2]-ref ; Δ side (2): open
line: (2)-j0.9-(3) -> floating, no ground path
T2: Δ side (3): open ; (4)-[0.06+j0.18]-ref
G3: (4)-[j0.05+3(j0.03)]-ref
-> bus 3 has NO connection to the reference
Because bus 3 sits between the Δ windings of T1 and T2, the zero-sequence impedance seen from bus 3 is infinite: .
Thevenin values: pu.
(ii) Phase currents
No fault current flows: the 115 kV section between the two deltas is an ungrounded system (only a small capacitive current would flow in practice).
(iii) Phase voltages at bus 3
With no current, , , and the condition forces pu (the whole neutral shifts):
Base phase voltage at bus 3 kV:
- kV
- kV
Results
| Quantity | pu | Actual |
|---|---|---|
| 0 | 0 A | |
| 0 | 0 kV | |
| 1.732∠−150° | 115 kV | |
| 1.732∠150° | 115 kV |
The healthy phases rise to full line voltage, showing why ungrounded sections need insulation for line voltage to ground.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- SLG fault: sequence networks in series · Power System Analysis II, chapter 5 · asked 5×
- SLG fault on bus with three alternators · Power System Analysis II, chapter 5
- L-G fault through Zf: currents and voltages · Power System Analysis II, chapter 5
- LLG fault sequence currents at bus 3 · Power System Analysis II, chapter 5
- DLG fault sequence network connection · Power System Analysis II, chapter 5 · asked 3×
- L-G fault of unloaded generator: equal currents · Power System Analysis II, chapter 5
- Delta load line currents and power, ABC sequence · Basic Electrical Engineering, chapter 8
- Delta load phase currents, power, line currents · Basic Electrical Engineering, chapter 8
- Healthy-phase overvoltage in SLG fault; effective grounding · High Voltage Engineering, chapter 3
- Temporary overvoltage for SLG fault at line middle · High Voltage Engineering, chapter 3