SLG fault on bus with three alternators
Short answer
Using 10 MVA, 6.6 kV base, parallel reactances: (i) all neutrals solidly grounded, X0=0.015 pu, If=29.27 pu = 25.6 kA; (ii) one neutral through 0.3 Ω (3Rn=0.2066 pu), others isolated, Z0=0.2066+j0.045, If=12.22 pu = 10.7 kA.
Three 6.6 kV, 3-phase, 10 MVA alternators are connected to a common bus. Each alternator has a positive sequence reactance of 0.15 pu. The negative and zero sequence reactances are 75% and 30% of positive sequence reactance. A single line-to-ground fault occurs on the bus. Find the fault current for the following cases: (i) All the alternator neutrals are solidly grounded. (ii) One alternator neutral is grounded through 0.3 ohm resistance and the other two neutrals are isolated.
Base: 10 MVA, 6.6 kV (rating of each alternator).
Each alternator: , , pu. Pre-fault voltage 1 pu, no load.
The positive and negative networks always have all three machines in parallel:
(i) All neutrals solidly grounded
All three zero-sequence reactances are in parallel:
(ii) One neutral grounded through 0.3 Ω, others isolated
Only the grounded machine provides a zero-sequence path; its neutral resistance appears as :
Results
| Case | Fault current |
|---|---|
| (i) All neutrals solidly grounded | 29.27 pu = 25.6 kA |
| (ii) One neutral through 0.3 Ω | 12.22 pu = 10.7 kA |
Grounding only one machine through a resistance cuts the earth-fault current to about 42 % and is why generator neutrals on a common bus are normally grounded through impedance, with only one neutral grounded.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- L-L fault line voltages, 25 MVA alternator · Power System Analysis II, chapter 5 · asked 2×
- Sequence reactances from fault currents · Power System Analysis II, chapter 5
- DLG fault at bus 2, fault MVA · Power System Analysis II, chapter 5
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3