SLG fault on bus with three alternators

Short answer

Using 10 MVA, 6.6 kV base, parallel reactances: (i) all neutrals solidly grounded, X0=0.015 pu, If=29.27 pu = 25.6 kA; (ii) one neutral through 0.3 Ω (3Rn=0.2066 pu), others isolated, Z0=0.2066+j0.045, If=12.22 pu = 10.7 kA.

Three 6.6 kV, 3-phase, 10 MVA alternators are connected to a common bus. Each alternator has a positive sequence reactance of 0.15 pu. The negative and zero sequence reactances are 75% and 30% of positive sequence reactance. A single line-to-ground fault occurs on the bus. Find the fault current for the following cases: (i) All the alternator neutrals are solidly grounded. (ii) One alternator neutral is grounded through 0.3 ohm resistance and the other two neutrals are isolated.

Base: 10 MVA, 6.6 kV (rating of each alternator).

Ibase=10×1063×6.6×103=874.8 A,Zbase=6.6210=4.356 ΩI_{base} = \frac{10\times10^6}{\sqrt3 \times 6.6\times10^3} = 874.8\ \text{A}, \quad Z_{base} = \frac{6.6^2}{10} = 4.356\ \Omega

Each alternator: X1=0.15X_1 = 0.15, X2=0.75×0.15=0.1125X_2 = 0.75 \times 0.15 = 0.1125, X0=0.30×0.15=0.045X_0 = 0.30 \times 0.15 = 0.045 pu. Pre-fault voltage 1 pu, no load.

The positive and negative networks always have all three machines in parallel:

X1=0.153=0.05 pu,X2=0.11253=0.0375 puX_1 = \frac{0.15}{3} = 0.05\ \text{pu}, \quad X_2 = \frac{0.1125}{3} = 0.0375\ \text{pu}

(i) All neutrals solidly grounded

All three zero-sequence reactances are in parallel:

X0=0.0453=0.015 puIf=3Ej(X1+X2+X0)=3j(0.05+0.0375+0.015)=3j0.1025=−j29.27 pu∣If∣=29.27×874.8=25 603 A≈25.6 kA\begin{aligned} X_0 &= \frac{0.045}{3} = 0.015\ \text{pu} \\ I_f &= \frac{3E}{j(X_1+X_2+X_0)} = \frac{3}{j(0.05+0.0375+0.015)} = \frac{3}{j0.1025} = -j29.27\ \text{pu} \\ |I_f| &= 29.27 \times 874.8 = 25\,603\ \text{A} \approx 25.6\ \text{kA} \end{aligned}

(ii) One neutral grounded through 0.3 Ω, others isolated

Only the grounded machine provides a zero-sequence path; its neutral resistance appears as 3Rn3R_n:

Rn=0.34.356=0.06887 pu,3Rn=0.2066 puZ0=3Rn+jX0=0.2066+j0.045 puZ1+Z2+Z0=0.2066+j(0.05+0.0375+0.045)=0.2066+j0.1325If=30.2066+j0.1325=12.22∠−32.67∘ pu∣If∣=12.22×874.8=10 692 A≈10.7 kA\begin{aligned} R_n &= \frac{0.3}{4.356} = 0.06887\ \text{pu}, \quad 3R_n = 0.2066\ \text{pu} \\ Z_0 &= 3R_n + jX_0 = 0.2066 + j0.045\ \text{pu} \\ Z_1+Z_2+Z_0 &= 0.2066 + j(0.05 + 0.0375 + 0.045) = 0.2066 + j0.1325 \\ I_f &= \frac{3}{0.2066 + j0.1325} = 12.22\angle{-32.67^\circ}\ \text{pu} \\ |I_f| &= 12.22 \times 874.8 = 10\,692\ \text{A} \approx 10.7\ \text{kA} \end{aligned}

Results

CaseFault current
(i) All neutrals solidly grounded29.27 pu = 25.6 kA
(ii) One neutral through 0.3 Ω12.22 pu = 10.7 kA

Grounding only one machine through a resistance cuts the earth-fault current to about 42 % and is why generator neutrals on a common bus are normally grounded through impedance, with only one neutral grounded.