For a DLG fault at bus 2, sequence networks connect in parallel. Thevenin impedances: Z1 = Z2 = j0.1583 pu, Z0 = j0.0824 pu. Fault current If = 3I0 = j9.287 pu = 3886 A (ground); short-circuit MVA = 928.7 MVA.

For the given power system network, draw sequence networks for DLG fault at bus no 2 and determine the fault current, short circuit MVA. G1: 100 MVA, 15.75 kV, X1 = X2 = 0.15 pu, X0 = 0.05 pu; G2: 100 MVA, 15.75 kV, X1 = X2 = 0.2 pu, X0 = 0.1 pu; T1 = T2: 100 MVA, 15.75/138 kV, X1 = X2 = X0 = 0.1 pu; Line: X1 = X2 = 25 Ω, X0 = 70 Ω. [Figure: G1 (Y grounded) - bus 1 - T1 (Δ/Y grounded) - bus 2 - line - bus 3 - T2 (Y grounded/Δ) - bus 4 - G2 (Y grounded)]

Base: 100 MVA; 15.75 kV (generators), 138 kV (line). Pre-fault voltage 1 pu, no load, bolted fault (Zf=0Z_f = 0).

Zbase,line=1382100=190.44 Ω,X1,line=25190.44=0.1313,X0,line=70190.44=0.3676 puZ_{base,line} = \frac{138^2}{100} = 190.44\ \Omega, \quad X_{1,line} = \frac{25}{190.44} = 0.1313, \quad X_{0,line} = \frac{70}{190.44} = 0.3676\ \text{pu}

Sequence networks

Positive (emfs E1E_1, E2E_2):

 E1-j0.15-(1)-j0.1-(2)-j0.1313-(3)-j0.1-(4)-j0.2-E2
                   |
                   F

Negative: same reactances (X2=X1X_2 = X_1), no emfs.

Zero:

  • T1 is Δ (bus 1 side)/Yg (bus 2 side): bus 2 to reference through j0.1j0.1; G1 isolated.
  • T2 is Yg (bus 3 side)/Δ (bus 4 side): bus 3 to reference through j0.1j0.1; G2 isolated.
 ref-j0.1-(2)-j0.3676-(3)-j0.1-ref
           |
           F      (G1 j0.05, G2 j0.1 isolated by deltas)

Thevenin impedances at bus 2

Z1=Z2=j0.25 ∥ j(0.1313+0.1+0.2)=j0.25 ∥ j0.4313=j0.1583 puZ0=j0.1 ∥ j(0.3676+0.1)=j0.1 ∥ j0.4676=j0.0824 pu\begin{aligned} Z_1 = Z_2 &= j0.25\ \|\ j(0.1313 + 0.1 + 0.2) = j0.25\ \|\ j0.4313 = j0.1583\ \text{pu} \\ Z_0 &= j0.1\ \|\ j(0.3676 + 0.1) = j0.1\ \|\ j0.4676 = j0.0824\ \text{pu} \end{aligned}

DLG fault (b, c to ground): networks in parallel

Z2∥Z0=0.1583×0.08240.2406=j0.0542Ia1=1j(0.1583+0.0542)=−j4.707 puIa2=−Ia1Z0Z2+Z0=j1.612 puIa0=−Ia1Z2Z2+Z0=j3.096 pu\begin{aligned} Z_2\|Z_0 &= \frac{0.1583 \times 0.0824}{0.2406} = j0.0542 \\ I_{a1} &= \frac{1}{j(0.1583 + 0.0542)} = -j4.707\ \text{pu} \\ I_{a2} &= -I_{a1}\frac{Z_0}{Z_2+Z_0} = j1.612\ \text{pu} \\ I_{a0} &= -I_{a1}\frac{Z_2}{Z_2+Z_0} = j3.096\ \text{pu} \end{aligned}

Phase currents:

Ib=7.177∠139.68∘ pu,Ic=7.177∠40.32∘ puI_b = 7.177\angle{139.68^\circ}\ \text{pu}, \quad I_c = 7.177\angle{40.32^\circ}\ \text{pu}

Fault (ground) current:

If=3Ia0=j9.287 puI_f = 3I_{a0} = j9.287\ \text{pu} Ibase=100×1063×138×103=418.4 A⇒If=9.287×418.4=3886 AI_{base} = \frac{100\times10^6}{\sqrt3\times138\times10^3} = 418.4\ \text{A} \Rightarrow I_f = 9.287 \times 418.4 = 3886\ \text{A}

(Each faulted line carries 7.177×418.4=30037.177 \times 418.4 = 3003 A.)

Short-circuit MVA

SC MVA=∣If∣pu×Vf×MVAbase=9.287×1×100=928.7 MVA\text{SC MVA} = |I_f|_{pu} \times V_f \times \text{MVA}_{base} = 9.287 \times 1 \times 100 = 928.7\ \text{MVA}

Answer: If≈9.29I_f \approx 9.29 pu =3.89= 3.89 kA; short-circuit level ≈ 929 MVA.