- 2072 Kartik · 10 marks
DLG fault at bus 2, fault MVA
Short answer
For a DLG fault at bus 2, sequence networks connect in parallel. Thevenin impedances: Z1 = Z2 = j0.1583 pu, Z0 = j0.0824 pu. Fault current If = 3I0 = j9.287 pu = 3886 A (ground); short-circuit MVA = 928.7 MVA.
For the given power system network, draw sequence networks for DLG fault at bus no 2 and determine the fault current, short circuit MVA. G1: 100 MVA, 15.75 kV, X1 = X2 = 0.15 pu, X0 = 0.05 pu; G2: 100 MVA, 15.75 kV, X1 = X2 = 0.2 pu, X0 = 0.1 pu; T1 = T2: 100 MVA, 15.75/138 kV, X1 = X2 = X0 = 0.1 pu; Line: X1 = X2 = 25 Ω, X0 = 70 Ω. [Figure: G1 (Y grounded) - bus 1 - T1 (Δ/Y grounded) - bus 2 - line - bus 3 - T2 (Y grounded/Δ) - bus 4 - G2 (Y grounded)]
Base: 100 MVA; 15.75 kV (generators), 138 kV (line). Pre-fault voltage 1 pu, no load, bolted fault ().
Sequence networks
Positive (emfs , ):
E1-j0.15-(1)-j0.1-(2)-j0.1313-(3)-j0.1-(4)-j0.2-E2
|
F
Negative: same reactances (), no emfs.
Zero:
- T1 is Δ (bus 1 side)/Yg (bus 2 side): bus 2 to reference through ; G1 isolated.
- T2 is Yg (bus 3 side)/Δ (bus 4 side): bus 3 to reference through ; G2 isolated.
ref-j0.1-(2)-j0.3676-(3)-j0.1-ref
|
F (G1 j0.05, G2 j0.1 isolated by deltas)
Thevenin impedances at bus 2
DLG fault (b, c to ground): networks in parallel
Phase currents:
Fault (ground) current:
(Each faulted line carries A.)
Short-circuit MVA
Answer: pu kA; short-circuit level ≈ 929 MVA.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- LLG fault sequence currents at bus 3 · Power System Analysis II, chapter 5
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- L-G fault at bus 1 through Zf · Power System Analysis II, chapter 5
- DLG fault sequence network connection · Power System Analysis II, chapter 5 · asked 3×
- Equivalent Z0, Z1, Z2 at bus 3 · Power System Analysis II, chapter 5
- Impedance diagram, 100 MVA 132 kV base, with load · Power System Analysis I, chapter 3
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Fault level: two 25 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Power by two generators, 1.05∠5° and 1.05∠20° pu · Power System Analysis I, chapter 3 · asked 2×