Skip to main content

Impedance diagram, 100 MVA 132 kV base, with load

Short answer

Using 100 MVA base and 132 kV in the transmission line, base impedances are derived from transformer ratios. Results: G1 j0.571, T1 j0.186, main line 0.2296+j0.9183, each parallel section 0.1148+j0.4591, load 2.1778+j1.6333, T2 j0.372, G2 j1.116.

Prepare an impedance diagram of the system shown in the figure below and show all impedances in per unit on a 100 MVA, 132 kV base in the transmission line circuit. [Figure: G1 (50 MVA, 13.8 kV, X = 0.15 p.u.) → T1 (80 MVA, Y-Y, 12.2/161 kV, Xt = 0.1 p.u.) → HV bus; from this bus a line of 40 + j160 Ω goes to the HV side of T2, and a parallel path of two sections 20 + j80 Ω and 20 + j80 Ω also joins the two buses, with a load of 50 MVA, cos φ = 0.8 lag, V = 154 kV tapped at the junction of the two sections; T2 (40 MVA, Y-Y, 161/13.8 kV, Xt2 = 0.1 p.u.) → G2 (20 MVA, 13.8 kV, X = 0.15 p.u.).]

Base values

  • Sb=100S_b = 100 MVA, and Vb=132V_b = 132 kV in the transmission circuit, so Zb=1322/100=174.24 ΩZ_b = 132^2/100 = 174.24\ \Omega.
  • G1 side, through T1 (12.2/161 kV): Vb=132×12.2161=10.0025V_b = 132\times\dfrac{12.2}{161} = 10.0025 kV.
  • G2 side, through T2 (161/13.8 kV): Vb=132×13.8161=11.3143V_b = 132\times\dfrac{13.8}{161} = 11.3143 kV.

Per-unit impedances

Use Znew=ZoldSbSrated(VratedVb)2Z_{new} = Z_{old}\dfrac{S_b}{S_{rated}}\left(\dfrac{V_{rated}}{V_b}\right)^2.

G1:0.15×10050(13.810.0025)2=j0.5710T1:0.1×10080(161132)2=j0.1860T2:0.1×10040(161132)2=j0.3719G2:0.15×10020(13.811.3143)2=j1.1157\begin{aligned} G_1&: 0.15\times\frac{100}{50}\left(\frac{13.8}{10.0025}\right)^2 = j0.5710\\ T_1&: 0.1\times\frac{100}{80}\left(\frac{161}{132}\right)^2 = j0.1860\\ T_2&: 0.1\times\frac{100}{40}\left(\frac{161}{132}\right)^2 = j0.3719\\ G_2&: 0.15\times\frac{100}{20}\left(\frac{13.8}{11.3143}\right)^2 = j1.1157 \end{aligned}

Lines:

Z40+j160=40+j160174.24=0.2296+j0.9183Z20+j80=20+j80174.24=0.1148+j0.4591 (each section)\begin{aligned} Z_{40+j160} &= \frac{40 + j160}{174.24} = 0.2296 + j0.9183\\ Z_{20+j80} &= \frac{20 + j80}{174.24} = 0.1148 + j0.4591\ \text{(each section)} \end{aligned}

Load (50 MVA, 0.8 lagging, 154 kV): V=154/132=1.1667V = 154/132 = 1.1667 p.u. and S=0.5S = 0.5 p.u.

ZL=∣V∣2S∗=1.166720.5∠36.87∘=2.7222∠36.87∘=2.1778+j1.6333 p.u.Z_L = \frac{|V|^2}{S^*} = \frac{1.1667^2}{0.5}\angle36.87^\circ = 2.7222\angle36.87^\circ = 2.1778 + j1.6333\ \text{p.u.}

Impedance diagram

 j0.571  j0.186      0.2296+j0.9183      j0.3719  j1.1157
+-/\/\----/\/\--+-------/\/\/\/\-------+--/\/\----/\/\--+
|               |                      |               |
(E1)            +-0.1148+j0.4591-+-0.1148+j0.4591-+   (E2)
|                                |                     |
|                        2.1778+j1.6333 (load)         |
|                                |                     |
+---------------- reference -----+---------------------+
Elementp.u. (100 MVA, 132 kV line base)
G1j0.5710
T1j0.1860
Line (40 + j160 Ω)0.2296 + j0.9183
Each section (20 + j80 Ω)0.1148 + j0.4591
Load2.1778 + j1.6333
T2j0.3719
G2j1.1157