- 2071 Chaitra · 8 marks
Fault at receiving end of 132 kV lines
Short answer
Assuming 200 km lines (40 Ω each), on100 MVA base X_th =0.255 pu. Fault level =392 MVA, fault current =1.71 kA at132 kV. At11 kV, G1 supplies12.55 kA, G2 supplies8.02 kA.
Figure below shows power system fed by two generators. The rating and reactances of the equipments are shown. A 3-phase balanced short circuit fault occurs at the receiving end bus of 132 kV. Find (a) Fault level and fault current at receiving end (b) Fault current supplied by generators G1 and G2. Note that reactance of machines are based on their own rating. [Figure: G1 100 MVA, 11 kV, 15% - T1 100 MVA, 11/132 kV, X = 8%; G2 50 MVA, 11 kV, 10% - T2 50 MVA, 11/132 kV, X = 8%; both transformers feed the 132 kV bus; Line-1 and Line-2, each X = 0.2 Ω/km/phase, in parallel to the receiving end bus F (line length not given)]
Fault level at a bus is (pu), where is the total reactance from the source EMFs (1 pu) to the fault.
Assumption: the line length is not given in the question, so a length of 200 km is assumed. Each line then has . G2 is 50 MVA, 11 kV, 10%; T2 is 50 MVA, 11/132 kV, 8%.
Step 1: Per unit values on 100 MVA base
Base: 100 MVA, 11 kV (generators), 132 kV (lines). .
| Element | Calculation | X (pu) |
|---|---|---|
| G1 | 0.15 (own base = 100 MVA) | 0.15 |
| T1 | 0.08 | 0.08 |
| G2 | 0.20 | |
| T2 | 0.16 | |
| Each line | 0.2296 |
Step 2: Reactance diagram and reduction
G1 0.15 T1 0.08
(~)--------||---+ Line-1 0.2296
|-- 132 kV bus ====+=========+--- F
(~)--------||---+ Line-2 0.2296
G2 0.20 T2 0.16
(a) Fault level and fault current at the receiving end
(b) Currents supplied by G1 and G2
The fault current divides between the two generator branches inversely as their reactances:
Base current on the 11 kV side: A.
Answer (200 km lines): fault level ≈ 392 MVA, fault current ≈ 1.71 kA at 132 kV; G1 supplies ≈ 12.55 kA and G2 ≈ 8.02 kA at 11 kV. For any other line length km, only pu changes in Step 2.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Fault level at end of two 200 km lines · Power System Analysis II, chapter 3 · asked 2×
- Fault at far end of 33 kV line · Power System Analysis II, chapter 3
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- HV bus fault and limiting reactor · Power System Analysis II, chapter 3
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Receiving end power, 140.2∠18.2° kV and 132 kV · Power System Analysis I, chapter 6
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×