- 2080 Chaitra · 4+6 marks
Receiving and sending end powers from ABCD, 132/134 kV
Short answer
From ABCD parameters and voltages, using power-circle equations: receiving power 59.29 MW, −21.07 MVAr, pf 0.942 leading; sending power 68.59 MW, −27.65 MVAr, pf 0.927 leading; loss 9.30 MW; regulation 0.52 % (no-load voltage 134.69 kV).
A 50 Hz, three-phase overhead line has the following parameters: A = 0.98∠0.8°; B = 45∠74° Ω; VSL = 132∠10° kV, VRL = 134∠0° kV. Determine the receiving end active and reactive power, power factor and line losses. Also find out the sending end active and reactive power, power factor and voltage regulation of the line.
Use the power-circle equations (taking ). Let , , leading by . With line voltages in kV, powers come out directly in three-phase MW/MVAr.
Data: , , , , kV, kV, .
Useful terms:
Angles: , , .
Receiving end
is negative, so reactive power flows from the receiving end into the line: the receiving-end pf is 0.942 leading. This is expected because .
Sending end
Line losses
The negative reactive difference means the line, on net, generates about 6.59 MVAr (its charging exceeds its absorption).
Voltage regulation
No-load receiving voltage kV.
Answer: = 59.29 MW, = −21.07 MVAr, pf 0.942 lead; = 68.59 MW, = −27.65 MVAr, pf 0.927 lead; loss 9.30 MW; regulation 0.52 %.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sending end active power from ABCD, 132/130.5 kV · Power System Analysis I, chapter 6
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
- 150 mile, 60 Hz line: ABCD and sending end · Power System Analysis I, chapter 5
- Sending and receiving power, 140∠10° and 132 kV · Power System Analysis I, chapter 6
- Sending end from A = 0.98∠3°, B = 110∠75° · Power System Analysis I, chapter 6 · asked 2×
- Sending end from A = 0.98∠0.3°, B = 110∠75° · Power System Analysis I, chapter 6 · asked 2×
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Shunt reactors for 750 kV line ABCD · High Voltage Engineering, chapter 3