Sending end from A = 0.98∠3°, B = 110∠75°
Short answer
Using V_S = A V_R + B I_R per phase, V_R = 76.21 kV, I_R = 218.7∠−36.87° A. Sending-end line voltage is 165.19 kV, power angle 11.35°. Sending-end powers: P_S = 62.49 MW, Q_S = 33.38 Mvar. Line losses: 22.49 MW, 3.38 Mvar.
A 3-phase 132 kV, 50 Hz overhead line delivers 50 MVA at pf 0.8 lagging at its receiving end. The constants of the line are A = 0.98∠3° and B = 110∠75° Ω per phase. Find (i) sending end voltage and power angle (ii) sending end active and reactive power (iii) line losses.
Given: 132 kV, 50 MVA at 0.8 p.f. lagging at the receiving end; , per phase. Symmetrical line assumed, so .
MW, Mvar.
(i) Sending-end voltage and power angle
Power angle .
(ii) Sending-end active and reactive power
Using the sending-end power equations with line values (, , ):
(Check: the receiving-end form of the same equations gives back MW and Mvar.)
(iii) Line losses
Answer: (i) kV (line), ; (ii) MW, Mvar; (iii) losses MW and Mvar.
Note: the active loss is large because the 3° angle of implies a resistive (lossy) shunt branch: from , S. The series resistance alone () would account for only about 4.1 MW.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sending end from A = 0.98∠0.3°, B = 110∠75° · Power System Analysis I, chapter 6 · asked 2×
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- Sending end active power from ABCD, 132/130.5 kV · Power System Analysis I, chapter 6
- Static compensation to hold sending end at 140 kV · Power System Analysis I, chapter 6
- Sending and receiving power, 140∠10° and 132 kV · Power System Analysis I, chapter 6
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Fault at load end of overhead line · Power System Analysis II, chapter 3