- 2074 Bhadra · 6 marks
Static compensation to hold sending end at 140 kV
Short answer
A capacitive compensator of approximately 35 MVAr must be installed at the receiving end to reduce the sending end voltage to 140 kV for the same load.
A 3-phase 132 kV overhead line delivers 50 MVA at 132 kV and 0.8 pf lagging. The constants of the line are A = 0.983∠3°, B = 110∠75° Ω per phase. Determine the capacity of the static compensation equipment at the receiving end to reduce the sending end voltage to 140 kV for the same load condition.
Data: , , , , = 132 kV, load 50 MVA at 0.8 lag = 40 MW + j30 MVAr. With line kV, powers are three-phase.
Without compensation, kV, which is too high. We need kV with the same 40 MW load.
Receiving-end power-circle equations
Find from = 40 MW
Reactive power the line delivers
So the line can deliver no lagging VAr; it actually needs 5.05 MVAr from the receiving end.
Compensator rating
Load requires 30 MVAr lagging. The compensator must supply:
Answer: Static (capacitive) compensator of about 35 MVAr at the receiving end.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sending end from A = 0.98∠3°, B = 110∠75° · Power System Analysis I, chapter 6 · asked 2×
- Sending end from A = 0.98∠0.3°, B = 110∠75° · Power System Analysis I, chapter 6 · asked 2×
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Sending end active power from ABCD, 132/130.5 kV · Power System Analysis I, chapter 6
- Sending and receiving power, 140∠10° and 132 kV · Power System Analysis I, chapter 6
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×