Currents and efficiency of 132/11 kV transformer at 5 MW

Short answer

Secondary line current is 328.0 A and phase current is 189.4 A (delta); primary line current is 27.34 A (star). Copper loss is 24.57 kW plus iron loss 20 kW gives efficiency 99.12%.

A 132/11 kV, star/delta, 3-phase, 50 Hz transformer has balanced star connected three-phase 5 MW at 0.8 pf lagging per phase. The primary winding has a resistance and leakage reactance of 10 Ω and 30 Ω per phase respectively and the secondary winding has a resistance and leakage reactance of 0.02 Ω and 0.06 Ω per phase respectively. Given that the iron loss of transformer is 20 kW. Calculate secondary phase and line currents, primary line current and efficiency of transformer.

Reading of the data: the load is 5 MW in total (balanced, three-phase) at 0.8 pf lag, supplied at 11 kV line voltage from the delta secondary; the 132 kV primary is star-connected. Winding R and X are per phase. Copper loss is found from winding currents; the voltage drop is neglected when finding currents.

Secondary currents (delta, 11 kV)

IL2=P3VLcos⁡ϕ=5×1063×11000×0.8=328.04 AIph2=IL23=328.043=189.39 A\begin{aligned} I_{L2} &= \frac{P}{\sqrt3 V_L\cos\phi} = \frac{5\times10^6}{\sqrt3\times11000\times0.8} = 328.04\ \text{A} \\ I_{ph2} &= \frac{I_{L2}}{\sqrt3} = \frac{328.04}{\sqrt3} = 189.39\ \text{A} \end{aligned}

Primary current (star, 132 kV)

Phase voltages: primary 132/3=76.21132/\sqrt3 = 76.21 kV, secondary 11 kV, so the turns ratio per phase is 76.21/11=6.92876.21/11 = 6.928.

IL1=Iph1=189.396.928=27.34 AI_{L1} = I_{ph1} = \frac{189.39}{6.928} = 27.34\ \text{A}

Check: 5×106/(3×132000×0.8)=27.345\times10^6/(\sqrt3\times132000\times0.8) = 27.34 A.

Losses

Pcu1=3Iph12R1=3×27.342×10=22419 WPcu2=3Iph22R2=3×189.392×0.02=2152 WPcu=22419+2152=24571 WPloss=24571+20000=44571 W\begin{aligned} P_{cu1} &= 3 I_{ph1}^2 R_1 = 3\times27.34^2\times10 = 22419\ \text{W} \\ P_{cu2} &= 3 I_{ph2}^2 R_2 = 3\times189.39^2\times0.02 = 2152\ \text{W} \\ P_{cu} &= 22419 + 2152 = 24571\ \text{W} \\ P_{loss} &= 24571 + 20000 = 44571\ \text{W} \end{aligned}

(The leakage reactances cause voltage drop but no loss, so they do not enter the efficiency.)

Efficiency

η=50005000+44.571×100=99.12%\eta = \frac{5000}{5000 + 44.571}\times100 = 99.12\%

Answer: secondary phase current = 189.4 A, secondary line current = 328.0 A, primary line current = 27.34 A, efficiency = 99.12%.