Design: 500 kVA 66/11 kV power transformer
Short answer
Cruciform core d=260 mm, stampings 221×138 mm; window 853 mm high × 310 mm wide; yoke depth 221 mm, height 228 mm; overall frame 1309×1360×221 mm. Per unit resistance drop 0.010, leakage reactance drop 0.065, voltage regulation at 0.8 pf lagging 0.0472 (4.72%).
For a 500 kVA, 3-phase, 50 Hz, 66/11 kV, delta/star, core type, oil immersed natural cooled power transformer the design data are: Maximum flux density in the core = 1.6 Wb/m²; Constant for output voltage per turn = 0.6; Core type = cruciform; Current density in the conductor = 2.5 A/mm²; Window space factor = 0.22; Stacking factor = 0.9; Ratio of window height to width = 2.75. Width of duct between LV and core, LV winding, HV winding and duct between HV and LV are 10 mm, 50 mm, 60 mm, 20 mm respectively. Assuming all other required parameters, calculate: (i) Overall dimension of core (ii) Overall dimension of frame (iii) Per unit resistance and leakage reactance drop (iv) Per unit voltage regulation
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. Assumed: yoke area 1.2 × core area (hot-rolled steel), end clearance 50 mm (66 kV), -mm²/m, regulation at 0.8 pf lagging (pf not given).
(i) Overall dimensions of core
Voltage per turn, ( in kVA, total for 3 phases):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Winding build (LV next to core):
Radial build (given clearance between core and LV = 10 mm):
| Item | Inside dia (mm) | Outside dia (mm) |
|---|---|---|
| LV winding | 279.7 | 379.7 |
| HV winding | 419.7 | 539.7 |
Radial depths: mm (LV), mm (HV), duct mm. Axial length of coil, from the output-equation window height: mm.
Mean lengths of turn:
Check: the HV outside diameter is 539.7 mm but from the output equation is only 441.0 mm, so the coils of adjacent limbs would overlap. The window is widened so that there is 30 mm clearance between adjacent HV coils (66 kV), and its height is increased to keep the given ratio . The coil height stays at = 398.4 mm.
Yoke:
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
(ii) Overall dimensions of frame
+-----------------------------+ ---
| top yoke | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H
| | | | | | |
+-----+-----+-----+-----+-----+ |
| bottom yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
|<--- D --->|<--- D --->|
(iii) Per unit resistance and leakage reactance drop
Phase voltages: LV (star) V; HV (delta) V.
Phase currents: A; A.
Resistance referred to HV, with (copper at about 75 °C):
Leakage reactance (per unit), with per limb and axial winding length mm:
(iv) Per unit voltage regulation (0.8 pf lagging)
Answer: = 260 mm; window 310 × 853 mm (after widening); frame 1309 × 1360 × 221 mm; = 0.0099, = 0.0668; regulation ≈ 4.80%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 150 kVA 11000/420 V distribution transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 125 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 150 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 4×
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2