- Asked 4/22
- 2075 Chaitra · 16 marks
Design: 125 kVA 6600/400 V three phase transformer
Short answer
Core diameter 173.1 mm, window width 187.9 mm, height 469.7 mm, yoke depth 147.2 mm, height 152.1 mm. Overall frame 773.9 × 869.2 × 147.2 mm. Leakage reactance computed from winding dimensions and turns (value not completed in excerpt).
Design a 125 kVA, 50 Hz, 6600/400 V, 3-phase, Δ/Y, core type oil immersed natural cooled distribution transformer. (Assume suitable data if necessary) Maximum flux density in core = 1.35 Wb/m², core type = cruciform; Current density = 2.75 A/mm²; Window space factor = 0.4; Hw/Ww = 2.5; Take hot rolled steel sheet and area of yoke = 1.2 × area of core; Axial depth of L.V. = 268 mm; Axial depth of H.V. = 276 mm; Radial depth of L.V. = 14 mm; Radial depth of H.V. = 18 mm; Width of insulation between L.V. and H.V. = 11 mm; Outside diameter of L.V. = 293 mm, Inside diameter of L.V. = 255 mm; Inside diameter of H.V. = 314 mm, Outside diameter of H.V. = 351 mm. Calculate: i) Dimension of core, window and yoke ii) Overall dimension of frame iii) Leakage reactance of transformer iv) Draw overall dimension of frame
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. = 0.45 assumed (3-phase distribution transformer), -mm²/m. Winding data are given: LV 255/293 mm (inside/outside diameter), HV 314/351 mm, radial depths = 14 mm, = 18 mm, gap = 11 mm. Axial length taken as the mean of 268 and 276 mm, = 272 mm.
i) Dimensions of core, window and yoke
Voltage per turn, ( in kVA, total for 3 phases):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Check with the given windings: = 173 mm fits inside the LV (255 mm), but the HV outside diameter 351 mm > = 283 mm and the coil height 276 mm > = 274 mm. So the window is enlarged to suit the given coils (10 mm between adjacent HV coils), and its height is increased to keep the given ratio :
Yoke:
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
ii) Overall dimensions of frame
iii) Leakage reactance
Phase voltages: LV (star) V; HV (delta) V.
Phase currents: A; A.
Radial depths: mm (LV), mm (HV), duct mm.
Mean lengths of turn:
Leakage reactance (per unit), with per limb and axial winding length mm:
iv) Overall dimensions of frame (sketch)
+-----------------------------+ ---
| yoke, Hy = 152 mm | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H = 774 mm
| |188 | | | | |
+-----+-----+-----+-----+-----+ |
| yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
W = 869 mm, D = 361 mm (limb centres)
Depth of core and yoke = 147 mm
Window height Hw = 470 mm
Answer: = 173 mm; window 188 × 470 mm; yoke 152 × 147 mm; frame 774 × 869 × 147 mm; leakage reactance ≈ 51.7 Ω/phase referred to HV (4.95%).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Design: 150 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 125 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 150 kVA 11000/420 V distribution transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
- Air gap flux density in core with three windings · Electrical Machines I, chapter 1
- 25 kVA ideal transformer currents, flux · Basic Electrical and Electronics Engineering, chapter 2
- Three-phase full converter at 50% of maximum output · Power Electronics, chapter 3
- Flux density in circular iron core · Electrical Machines, chapter 1