Design data: 1000 kVA 66/11 kV transformer
Short answer
Core d=324.4 mm, cruciform (a=275.8, b=171.9 mm); window 267.4×735.2 mm; yoke depth 275.8 mm height 285.0 mm; frame H=1305.2 mm, W=1459.3 mm, depth 275.8 mm.
The design parameters for a 1000 kVA, 50 Hz, 66/11 kV, 3-phase, delta/delta, core type, oil immersed natural cooled power transformer are given below. Constant for output voltage per turn = 0.6; Maximum flux density in the core = 1.45 Wb/m²; Current density in conductor = 2.75 A/mm²; Core type = cruciform two stepped; Window space factor = 0.13; Stacking factor = 0.9; Ratio of window height to width = 2.75; Take hot rolled steel and area of yoke is 20% greater than gross area of core; Width of LV winding = 40 mm; Width of HV winding = 50 mm; Width of duct between HV and LV winding = 20 mm; Resistivity of copper = 0.021 Ω-mm²/m. [The list of quantities to calculate is not shown in the scanned paper.]
The list of quantities is missing from the paper, so the usual set is worked out: core, window and yoke; overall frame; per unit resistance and reactance; regulation at 0.8 pf lagging. Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. Assumed: core-to-LV clearance 10 mm, end clearance 50 mm (66 kV), -mm²/m.
Core and window
Voltage per turn, ( in kVA, total for 3 phases):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Yoke
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
Overall dimensions of frame
+-----------------------------+ ---
| top yoke | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H
| | | | | | |
+-----+-----+-----+-----+-----+ |
| bottom yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
|<--- D --->|<--- D --->|
Turns and conductors (delta/delta)
Phase voltages: LV (delta) V; HV (delta) V.
Phase currents: A; A.
Winding dimensions
Radial build (assumed clearance between core and LV = 10 mm):
| Item | Inside dia (mm) | Outside dia (mm) |
|---|---|---|
| LV winding | 344.4 | 424.4 |
| HV winding | 464.4 | 564.4 |
Radial depths: mm (LV), mm (HV), duct mm. Axial length mm.
Mean lengths of turn:
Check: HV outside diameter 564 mm vs = 592 mm. Adjacent HV coils have about 27 mm clearance, so the coils fit.
Per unit resistance
Resistance referred to HV, with (copper at about 75 °C):
Per unit leakage reactance
Leakage reactance (per unit), with per limb and axial winding length mm:
Regulation at 0.8 pf lagging
Answer: = 324 mm; window 267 × 735 mm; frame 1305 × 1459 × 276 mm; = 0.0086, = 0.0411; regulation ≈ 3.15%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 250 m head plant, 66 kV double circuit · Power Plant Design, chapter 4 · asked 13×
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- Design: 280 m head plant, 66 kV · Power Plant Design, chapter 4 · asked 12×
- Delta capacitor per phase for 50 kW motor · Basic Electrical Engineering, chapter 8