500 kVA delta/star transformer efficiency
Short answer
Full-load copper loss 4488 W (from phase currents), iron loss 3050 W. At 0.8 pf: η full load=98.15%, η half load=97.96%.
A 500-KVA, 3-Ø, 50 Hz transformer has a voltage ratio (line voltage) of 33/11 kV and is delta/star connected. The resistances per phase are: High voltage 35 Ω, low voltage 0.876 Ω and the iron loss is 3050 W. Calculate the value of efficiency at full-load and one-half of full-load respectively at 0.8 p.f.
The copper loss is found from the phase currents of the delta (HV) and star (LV) windings. The resistances are given per phase, so the loss is 3 × I_ph² × R. The load is taken at 0.8 pf lagging.
Rated phase currents
- HV (delta): phase voltage = 33 kV, so I_ph1 = 500 000 / (3 × 33 000) = 5.051 A
- LV (star): I_ph2 = I_L = 500 000 / (√3 × 11 000) = 26.24 A
Full-load copper loss
- HV: 3 × (5.051)² × 35 = 2678.3 W
- LV: 3 × (26.24)² × 0.876 = 1809.9 W
- P_cu(fl) = 4488.2 W
- Iron loss P_i = 3050 W
Full load at 0.8 pf
Output = 500 000 x 0.8 = 400 000 W
Losses = 3050 + 4488.2 = 7538.2 W
η = 400 000 / 407 538.2 = 0.9815
η(full load) = 98.15 %
Half load at 0.8 pf
P_cu = (1/2)² × 4488.2 = 1122.1 W
Output = 200 000 W
Losses = 3050 + 1122.1 = 4172.1 W
η = 200 000 / 204 172.1 = 0.9796
η(half load) = 97.96 %
| Load | Output (kW) | Cu loss (W) | Iron loss (W) | η (%) |
|---|---|---|---|---|
| Full | 400 | 4488.2 | 3050 | 98.15 |
| Half | 200 | 1122.1 | 3050 | 97.96 |
Answer: 98.15 % at full load and 97.96 % at half load.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- CT ratio for 33/6.6 kV star/delta (400/5) · Switchgear and Protection, chapter 7
- CT ratio for 33/6.6 kV star/delta (300:5) · Switchgear and Protection, chapter 7
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×