Currents and efficiency of 132/11 kV transformer at 4 MW
Short answer
Use S = P/pf = 5 MVA. Secondary line current = 5 MVA/(sqrt3 times 11 kV) = 262.43 A, phase current = 151.52 A. Primary line current = 21.87 A; total copper loss 15.73 kW, iron loss 20 kW, efficiency = 4000/(4035.73) = 99.11%.
A 132 kV/11 kV Star/Delta, 3-phase transformer has balanced star connected 3-phase load of 4 MW at p.f of 0.8 lagging per phase. The primary winding has resistance and leakage reactance of 10 Ω and 30 Ω respectively. The secondary winding has resistance and leakage reactance of 0.02 Ω and 0.06 Ω respectively. Given that the iron loss of transformer is 20 kW. Calculate: i) Secondary phase and line currents ii) Primary line current iii) Efficiency of transformer
Primary is star (line current = phase current), secondary is delta (phase voltage = line voltage = 11 kV, line current = × phase current). Winding resistances are taken as per-phase values.
Load apparent power:
(i) Secondary line and phase currents
(ii) Primary line current
Neglecting no-load current, input VA = output VA:
Check through the turns ratio: V, , A.
(iii) Efficiency
Copper losses (three phases):
Total losses kW.
(The leakage reactances do not cause power loss, so they are not needed for efficiency.)
| Quantity | Value |
|---|---|
| Secondary line current | 262.43 A |
| Secondary phase current | 151.52 A |
| Primary line current | 21.87 A |
| Copper loss | 15.73 kW |
| Efficiency | 99.11% |
Answer: (i) A, A; (ii) A; (iii) .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2