- 2068 Bhadra · 8 marks
Primary current and efficiency of 100 kVA Δ/Y transformer
Short answer
Per-phase V2ph = 400/√3 = 230.94 V, turns ratio K = 230.94/11000 = 0.020995. Primary line current = √3 * K * 100 A = 3.636 A. Output = 3*230.94*100*0.85 = 58.89 kW. Total copper loss = 3*(2.0995^2*25 + 100^2*0.04) = 1530.58 W. Iron loss = 1000 W. Efficiency = 58890/(58890+2530.58)*100 = 95.88%.
A 100 kVA, 11 kV/400 V Delta/star 3-phase transformer has following parameters: R1 = 25 Ω, X1 = 50 Ω, R2 = 0.04 Ω, X2 = 0.4 Ω, Iron loss = 1000 Watts. A 3-phase balanced load draws per phase current of 100 Amp at 0.85 power factor lagging. Calculate primary line current and efficiency of the transformer.
Primary delta (phase voltage 11 kV), secondary star (phase voltage ). are per-phase values. Load current 100 A per phase (= line current, star) at 0.85 pf lagging.
Turns ratio per phase
Primary line current
Neglecting no-load current:
Check: A.
Output power
Copper losses
Efficiency
| Quantity | Value |
|---|---|
| Primary phase current | 2.0995 A |
| Primary line current | 3.636 A |
| Output | 58.89 kW |
| Copper loss | 1530.58 W |
| Efficiency | 95.88% |
Answer: Primary line current = 3.636 A; efficiency = 95.88%.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×
- Equivalent impedance and copper loss of 50 kVA transformer · Electrical Machines I, chapter 2
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
- 25 kVA transformer: load voltage and primary current · Electrical Machines, chapter 2