3-phase 500 kVA transformer primary current
Short answer
For ideal transformer, primary line current I_L1 = S/(√3 V_L) = 500×10³/(√3×11000) = 26.24 A. Phase current in delta winding = 26.24/√3 = 15.15 A. Current drawn is 26.24 A at 0.8 lagging pf.
A 500 kVA, 50 Hz, 11 kV/400 V, 3-phase transformer has delta/star connection. Calculate the current drawn by the transformer from primary side when it delivers full load at rated terminal voltage at 0.8 lagging p.f. Assume ideal transformer operation.
For an ideal transformer, losses and voltage drops are zero, so input VA equals output VA. The primary is delta connected, so the line current is times the phase current.
Output at full load: kVA, power factor 0.8 lagging.
Primary line current
Primary phase current (delta)
(Check: A.)
Power drawn
For an ideal transformer the input power factor equals the load power factor (0.8 lagging), so the current lags the voltage by .
Answer: the transformer draws a line current of from the 11 kV supply (phase current in each delta winding) at 0.8 lagging power factor.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 25 kVA transformer: load voltage and primary current · Electrical Machines, chapter 2
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- Full-load efficiency of 500 kVA transformer · Electrical Machines I, chapter 2
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2