- 2078 Chaitra · 6 marks
CT ratio for 33/6.6 kV star/delta (400/5)
Short answer
With LV delta-side CTs 400/5 in star, pilot current is 5 A. HV line current is 400 x 6.6/33 = 80 A; HV CTs are in delta, so CT secondary is 5/√3 A. HV CT ratio is 80 : 5/√3 ≈ 138.6 : 5.
A 3-phase transformer rated for 33 kV/6.6 kV is connected star/delta and the protecting current transformer on the low voltage side have a ratio of 400/5. Determine the ratio of the current transformer on the HV side.
For differential protection of a star/delta transformer, the CTs on the star (HV) side are connected in delta and those on the delta (LV) side in star. This corrects the 30° phase shift and keeps zero-sequence current out of the relay. The CT ratios are chosen so that equal currents flow in the pilot wires.
Data: 33/6.6 kV, star/delta; LV CTs 400/5 (star connected).
Step 1: Pilot current from LV side
Take LV line current = 400 A, so the LV CT secondary (and pilot) current = 5 A.
Step 2: HV line current for the same load
I_HV = 400 × 6.6/33 = 80 A
Step 3: HV CT ratio
HV CTs are in delta; the line current from the delta is √3 × CT secondary current. For a pilot current of 5 A:
CT secondary = 5/√3 = 2.887 A
HV CT ratio = 80 : 5/√3 = 80 : 2.887
= 138.56 : 5 (≈ 27.71 : 1)
Connection
33 kV star ─── HV CTs (delta) ─┐
├─ pilots + relay
6.6 kV delta ─ LV CTs (star) ──┘
Answer: HV CT ratio = 80 : 5/√3 ≈ 138.6 : 5, HV CTs connected in delta and LV CTs in star.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- CT ratio for 33/6.6 kV star/delta (300:5) · Switchgear and Protection, chapter 7
- CT ratio and connection for 11/132 kV · Switchgear and Protection, chapter 7
- IDMT relays across 132/33 kV transformer (2000 A) · Switchgear and Protection, chapter 7
- IDMT relays across 132/33 kV transformer (2700 A) · Switchgear and Protection, chapter 7
- Merz-Price CT ratio for 66000/6600 V · Switchgear and Protection, chapter 7
- Pilot current with tap change (10 MVA) · Switchgear and Protection, chapter 7
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- 8 kVA 400/120 V tests, parameters on HV side · Electrical Machines, chapter 2