CT ratio and connection for 11/132 kV
Short answer
For delta-star transformer, LV delta-side CTs 200/1 are star connected, giving 1 A pilot. HV line current is 200 x 11/132 = 16.67 A; HV star-side CTs are delta connected, requiring secondary 1/√3 A. HV CT ratio is 16.67 : 1/√3 ≈ 28.87 : 1.
A three phase, 11/132 kV, delta-star connected power transformer is protected by differential protection. The CTs on the LV side have a current ratio of 200/1. What must be the current ratio of the CTs on the HV side? How the CTs on both the sides of the transformer are connected?
For differential protection, CTs on the delta winding side are connected in star, and CTs on the star winding side are connected in delta. This compensates the 30° phase shift of the transformer and prevents zero-sequence currents (from earth faults on the earthed star side) from causing false trips.
Data: 11/132 kV, delta (LV) / star (HV); LV CTs 200/1.
CT ratio on HV side
LV line current = 200 A → LV CT secondary (pilot) = 1 A
(LV CTs in star)
HV line current = 200 × 11/132 = 16.67 A
HV CTs in delta: pilot current = √3 × CT secondary
CT secondary = 1/√3 = 0.5774 A
HV CT ratio = 16.67 : 0.5774 = 28.87 : 1
Connection of CTs
- LV (11 kV, delta winding): CTs of 200/1 connected in star.
- HV (132 kV, star winding): CTs of 16.67 : 1/√3 (≈ 28.87/1) connected in delta.
- Pilot wires join corresponding phases of the two CT groups; the operating (and restraining) coils of the differential relays are connected between the pilots and the star point.
11 kV delta ──[CTs 200/1, star]──┐
├─ pilots ─ 87 relays
132 kV star ──[CTs 28.87/1, delta]┘
Answer: HV CT ratio = 16.67 : 1/√3 ≈ 28.87 : 1; LV CTs in star, HV CTs in delta.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- CT ratio for 33/6.6 kV star/delta (300:5) · Switchgear and Protection, chapter 7
- CT ratio for 33/6.6 kV star/delta (400/5) · Switchgear and Protection, chapter 7
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- IDMT relays across 132/11 kV transformer (3500 A) · Switchgear and Protection, chapter 7
- Percentage differential relay: 125 MVA transformer · Switchgear and Protection, chapter 7
- Percentage differential relay: 150 MVA transformer · Switchgear and Protection, chapter 7
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×