Percentage differential relay: 125 MVA transformer
Short answer
At full load, HV star CT output is 328.04/80 = 4.10 A, LV delta CT line output is √3 x 546.73/240 = 3.95 A. Full-load unbalance is 0.1548 A; at 15% overload relay current is 0.178 A. Minimum setting for 25% overload is 1.25 x 0.1548 = 0.194 A.
A 125 MVA, 220/132 kV three phase power transformer is protected by percentage differential relays. The current transformers located on HV and LV sides of the power transformer are 400/5 A and 1200/5 respectively. If the HV side is delta connected and the LV side is star connected, determine: i) The output line currents of both CT at full load ii) The relay current at 15% overload iii) The minimum relay current setting to permit 25% overload.
HV is delta connected, so its CTs are connected in star; LV is star connected, so its CTs are connected in delta. The relay current is the difference of the CT output line currents.
Data: 125 MVA, 220/132 kV; HV CTs 400/5 (ratio 80); LV CTs 1200/5 (ratio 240).
i) CT output line currents at full load
I_HV = 125 × 10⁶ / (√3 × 220 × 10³) = 328.04 A
I_LV = 125 × 10⁶ / (√3 × 132 × 10³) = 546.73 A
HV CTs (star): output = 328.04 / 80 = 4.100 A
LV CTs (delta): CT secondary = 546.73 / 240 = 2.278 A
output line = √3 × 2.278 = 3.946 A
ii) Relay current at 15% overload
Relay current at full load = 4.100 − 3.946 = 0.1548 A
At 115% load = 1.15 × 0.1548 = 0.178 A
iii) Minimum relay setting for 25% overload
The relay must not operate up to 125% load:
Setting ≥ 1.25 × 0.1548 = 0.1935 A
| Quantity | Value |
|---|---|
| HV CT output (FL) | 4.100 A |
| LV CT output (FL) | 3.946 A |
| Relay current at 115% | 0.178 A |
| Minimum setting (125%) | 0.194 A |
Answer: (i) 4.10 A (HV) and 3.95 A (LV); (ii) 0.178 A; (iii) minimum relay setting ≈ 0.194 A (about 3.9% of 5 A).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Percentage differential relay: 150 MVA transformer · Switchgear and Protection, chapter 7
- IDMT relays across 132/11 kV transformer (3500 A) · Switchgear and Protection, chapter 7
- IDMT relays across 132/33 kV transformer (2000 A) · Switchgear and Protection, chapter 7
- IDMT relays across 132/33 kV transformer (2700 A) · Switchgear and Protection, chapter 7
- CT ratio and connection for 11/132 kV · Switchgear and Protection, chapter 7
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- Design: 125 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3