400 km long line, 60 MVA at 220 kV

Short answer

Using exact long-line model: total Z=156.46∠74.43° Ω, Y=j1.1288×10⁻³ S, γl=0.4203∠82.21°, Zc=372.3∠−7.79° Ω, A=0.9163∠1.44°, B=152.1∠74.89° Ω. Sending line voltage V_S=231.59 kV, current I_S=152.7 A, pf=0.9244 leading, active loss 2.64 MW, reactive loss −49.53 Mvar.

A 3-Φ line is 400 km long. The line constants are z = 0.105 + j0.3768 Ω per phase per kilometre and y = 0 + j2.822 × 10⁻⁶ ℧ per kilometre. The line delivers 60 MVA at 0.9 power factor lagging at 220 kV. Find the sending end voltage, current, power factor, active and reactive power loss of the line.

Given: l=400l = 400 km, z=0.105+j0.3768 Ωz = 0.105 + j0.3768\ \Omega/km, y=j2.822×10−6y = j2.822\times10^{-6} S/km, load 60 MVA at 0.9 p.f. lagging, 220 kV. A 400 km line is a long line, so the exact (distributed) model is used. Values are per phase.

Step 1: Total parameters

Z=zl=42+j150.72=156.46∠74.43∘ ΩY=yl=j1.1288×10−3 S\begin{aligned} Z &= zl = 42 + j150.72 = 156.46\angle 74.43^\circ\ \Omega \\ Y &= yl = j1.1288\times10^{-3}\ \text{S} \end{aligned}

Step 2: Propagation constant and surge impedance

γl=ZY=0.4203∠82.21∘=0.05693+j0.41638Zc=Z/Y=372.3∠−7.79∘ Ω\begin{aligned} \gamma l &= \sqrt{ZY} = 0.4203\angle 82.21^\circ = 0.05693 + j0.41638 \\ Z_c &= \sqrt{Z/Y} = 372.3\angle -7.79^\circ\ \Omega \end{aligned}

Step 3: ABCD constants

A=D=cosh⁡γl=0.91604+j0.02304=0.9163∠1.44∘sinh⁡γl=0.05209+j0.40511=0.4084∠82.67∘B=Zcsinh⁡γl=152.1∠74.89∘ ΩC=sinh⁡γlZc=1.097×10−3∠90.46∘ S\begin{aligned} A = D &= \cosh\gamma l = 0.91604 + j0.02304 = 0.9163\angle 1.44^\circ \\ \sinh\gamma l &= 0.05209 + j0.40511 = 0.4084\angle 82.67^\circ \\ B &= Z_c\sinh\gamma l = 152.1\angle 74.89^\circ\ \Omega \\ C &= \frac{\sinh\gamma l}{Z_c} = 1.097\times10^{-3}\angle 90.46^\circ\ \text{S} \end{aligned}

Step 4: Receiving-end quantities

VR=2203=127.02∠0∘ kVIR=60×1063×220×103=157.46∠−25.84∘=141.71−j68.64 A\begin{aligned} V_R &= \frac{220}{\sqrt3} = 127.02\angle 0^\circ\ \text{kV} \\ I_R &= \frac{60\times10^6}{\sqrt3\times220\times10^3} = 157.46\angle -25.84^\circ = 141.71 - j68.64\ \text{A} \end{aligned}

PR=60×0.9=54P_R = 60 \times 0.9 = 54 MW, QR=60×0.4359=26.15Q_R = 60 \times 0.4359 = 26.15 Mvar

Step 5: Sending-end voltage and current

VS=AVR+BIR=(116,350+j2926)+(15,695+j18,083)=132,050+j21,009=133.71∠9.04∘ kV/phaseVS(L)=3×133.71=231.59 kVIS=CVR+DIR=(−1.11+j139.34)+(131.40−j59.61)=130.28+j79.74=152.7∠31.47∘ A\begin{aligned} V_S &= AV_R + BI_R = (116{,}350 + j2926) + (15{,}695 + j18{,}083) \\ &= 132{,}050 + j21{,}009 = 133.71\angle 9.04^\circ\ \text{kV/phase} \\ V_{S(L)} &= \sqrt3\times133.71 = 231.59\ \text{kV} \\ I_S &= CV_R + DI_R = (-1.11 + j139.34) + (131.40 - j59.61) \\ &= 130.28 + j79.74 = 152.7\angle 31.47^\circ\ \text{A} \end{aligned}

Step 6: Power factor and power

Angle between VSV_S and ISI_S =9.04∘−31.47∘=−22.43∘= 9.04^\circ - 31.47^\circ = -22.43^\circ (current leads).

Sending-end p.f. =cos⁡22.43∘=0.9244= \cos 22.43^\circ = 0.9244 leading

SS=3VSIS∗=56.64−j23.38 MVAS_S = 3V_SI_S^* = 56.64 - j23.38\ \text{MVA}

Step 7: Losses

Ploss=PS−PR=56.64−54=2.64 MWQloss=QS−QR=−23.38−26.15=−49.53 Mvar\begin{aligned} P_{loss} &= P_S - P_R = 56.64 - 54 = 2.64\ \text{MW} \\ Q_{loss} &= Q_S - Q_R = -23.38 - 26.15 = -49.53\ \text{Mvar} \end{aligned}

The negative reactive loss means the line's shunt capacitance generates 49.53 Mvar more than its series inductance absorbs. This is why the sending-end current leads.

Answer: VS=231.59V_S = 231.59 kV (line), IS=152.7I_S = 152.7 A, p.f. =0.9244= 0.9244 leading, active power loss =2.64= 2.64 MW, reactive power loss =−49.53= -49.53 Mvar (net 49.53 Mvar generated by the line). Efficiency =54/56.64=95.35%= 54/56.64 = 95.35\%.