- 2078 Chaitra · 10 marks
400 km long line, 60 MVA at 220 kV
Short answer
Using exact long-line model: total Z=156.46∠74.43° Ω, Y=j1.1288×10⁻³ S, γl=0.4203∠82.21°, Zc=372.3∠−7.79° Ω, A=0.9163∠1.44°, B=152.1∠74.89° Ω. Sending line voltage V_S=231.59 kV, current I_S=152.7 A, pf=0.9244 leading, active loss 2.64 MW, reactive loss −49.53 Mvar.
A 3-Φ line is 400 km long. The line constants are z = 0.105 + j0.3768 Ω per phase per kilometre and y = 0 + j2.822 × 10⁻⁶ ℧ per kilometre. The line delivers 60 MVA at 0.9 power factor lagging at 220 kV. Find the sending end voltage, current, power factor, active and reactive power loss of the line.
Given: km, /km, S/km, load 60 MVA at 0.9 p.f. lagging, 220 kV. A 400 km line is a long line, so the exact (distributed) model is used. Values are per phase.
Step 1: Total parameters
Step 2: Propagation constant and surge impedance
Step 3: ABCD constants
Step 4: Receiving-end quantities
MW, Mvar
Step 5: Sending-end voltage and current
Step 6: Power factor and power
Angle between and (current leads).
Sending-end p.f. leading
Step 7: Losses
The negative reactive loss means the line's shunt capacitance generates 49.53 Mvar more than its series inductance absorbs. This is why the sending-end current leads.
Answer: kV (line), A, p.f. leading, active power loss MW, reactive power loss Mvar (net 49.53 Mvar generated by the line). Efficiency .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- 150 mile, 60 Hz line: ABCD and sending end · Power System Analysis I, chapter 5
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×
- Nominal-T 100 km line, 20 MW at 110 kV · Power System Analysis I, chapter 5
- Peterson coil for 33 kV 60 km line · Switchgear and Protection, chapter 5 · asked 6×
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Power loss, 10 km 11 kV UDL feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3