220 kV line, 200 MW: sending end from ABCD
Short answer
The sending-end line voltage is 346.5 kV and current is 516.8 A. Sending-end power is 200.03 MW and 237.03 MVAr. Real power loss is 0.03 MW, reactive loss 87.03 MVAr; voltage regulation is 75% and efficiency is 99.99%.
A three phase 220 kV, 50 Hz transmission line supplies a power of 200 MW at a power factor of 0.8 lagging and the line has ABCD parameters as follows: A = 0.9∠0.001°, B = B Ω (value not printed), C = 1.14 × 10⁻³∠90°, D = 0.9∠0.001°. Determine the following: (i) sending end voltage and current (ii) real and reactive power at sending end at full load (iii) real and reactive power loss in line at full load (iv) voltage regulation and line efficiency at full load.
Assumption: is not printed, so it is found from the reciprocity condition :
Receiving-end quantities
(i) Sending-end voltage and current
Sending-end line voltage kV.
(ii) Sending-end power
= 200.03 MW, = 237.03 MVAr (pf 0.645 lag).
(iii) Losses
Receiving end: MVA.
The active loss is almost zero because the given , have nearly zero angle, i.e. the line is practically lossless.
(iv) Regulation and efficiency
Answer: = 346.5 kV (line), = 516.8 A; = 200.03 MW, = 237.03 MVAr; losses 0.03 MW and 87.03 MVAr; regulation ≈ 75 %, efficiency ≈ 99.99 %. (The very high regulation shows the line is loaded far above its surge impedance loading of about 127 MW.)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 150 mile, 60 Hz line: ABCD and sending end · Power System Analysis I, chapter 5
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- Sending end active power from ABCD, 132/130.5 kV · Power System Analysis I, chapter 6
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.95 pf · Power System Analysis I, chapter 5
- Conductor selection, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Air clearances, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- 220 kV double circuit efficiency and regulation · Transmission and Distribution System Design, chapter 4
- Initial line design for 200 MW over 120 km · Transmission and Distribution System Design, chapter 2