- 2079 Chaitra · 10 marks
220 kV double circuit efficiency and regulation
Short answer
Using nominal-π model, two parallel circuits, 0.9 pf lag: efficiency is98.93%, voltage regulation2.57%, no-load receiving-end voltage225.65 kV (5.65 kV rise above rated). The line already exceeds the94% efficiency and12% regulation limits; if needed, larger conductors, shunt capacitors, or series compensation could further improve performance.
A double circuit, 220 kV, 50 Hz, three phase transmission line is designed to carry 144 MW for 130 km. The line constants are given as: R = 0.0544 Ω/km (at max allowable temp.), L = 0.494 mH/km, C = 23.1 nF/km. Calculate the following: a) Transmission line efficiency b) Percentage of voltage regulation c) Value of receiving end voltage rise at no load if sending end voltage is held constant. Suggest the options to get efficiency > 94% and voltage regulation < 12%.
The line is 130 km long, so it is a medium line and the nominal-π model is used. The two circuits are in parallel.
Assumptions: power factor 0.9 lagging (not given in the question); receiving-end voltage held at 220 kV.
Line parameters (per phase)
Per circuit:
Two circuits in parallel:
Constants and currents
a) Efficiency
b) Voltage regulation
At no load, :
c) Receiving-end voltage rise at no load (Ferranti effect)
With held at 223.51 kV and the load removed:
The no-load voltage is 5.65 kV above the rated 220 kV.
Answer: η = 98.93%, VR = 2.57%, no-load rise = 2.15 kV above (receiving end 225.65 kV).
The line already meets η > 94% and VR < 12% by a wide margin.
Options if the limits were not met
- Larger conductor (lower ) for higher efficiency, or bundled conductors (lower ) for better regulation.
- Raise the power factor with shunt capacitors or SVCs at the load end. At unity pf the regulation falls to about 1.1%.
- Series capacitor compensation to cut and the voltage drop.
- More circuits or a higher voltage (for example 400 kV), which reduces the current and therefore and .
- Shunt reactors at the receiving end to limit the no-load (Ferranti) rise.
- On-load tap-changing transformers to correct the receiving-end voltage.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Tower dimensions for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- Air clearances for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Conductor selection, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Air clearances, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Initial line design for 200 MW over 120 km · Transmission and Distribution System Design, chapter 2
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- Regulation and efficiency of 100 km, 110 kV line · Power System Analysis I, chapter 6 · asked 2×
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- 33 kV, 15 MW line: efficiency and regulation · Power System Analysis I, chapter 6
All Transmission and Distribution System Design chapter 4 questions →