33 kV, 15 MW line: efficiency and regulation

Short answer

The transmission efficiency is 92.16% and voltage regulation is 20.82% (sending-end line voltage 39.87 kV). The phasor diagram shows VR as reference, I lagging by 25.84°, and VS leading VR by 10.23° with IR and IX drops added.

A 3-phase, 50 Hz, 33 kV transmission line is delivering a load of 15 MW at 0.9 pf lagging. The line series impedance per phase is 5 + j18 Ω. Determine the power transmission efficiency and voltage regulation of the line. Construct the phasor diagram of currents and voltages in the line.

Short line: Z=5+j18 ΩZ = 5 + j18\ \Omega/phase, shunt capacitance neglected.

Current

VR=33 000/3=19 052.6∠0∘ VI=15×1063×33 000×0.9=291.59 A,ϕR=25.84∘ lag\begin{aligned} V_R &= 33\,000/\sqrt3 = 19\,052.6\angle0^\circ\ \text{V} \\ I &= \frac{15\times10^6}{\sqrt3\times33\,000\times0.9} = 291.59\ \text{A},\quad \phi_R = 25.84^\circ\ \text{lag} \end{aligned}

Efficiency

Ploss=3I2R=3(291.59)2(5)=1.275 MWη=1515+1.275×100=92.16%\begin{aligned} P_{loss} &= 3I^2R = 3(291.59)^2(5) = 1.275\ \text{MW} \\ \eta &= \frac{15}{15 + 1.275}\times100 = 92.16\% \end{aligned}

Voltage regulation

IR=1458.0∠−25.84∘ V,IX=5248.6∠64.16∘ VVS=VR+I(R+jX)=19 052.6+5447.4∠48.63∘=23 018.5∠10.23∘ V\begin{aligned} IR &= 1458.0\angle-25.84^\circ\ \text{V},\quad IX = 5248.6\angle64.16^\circ\ \text{V} \\ V_S &= V_R + I(R + jX) = 19\,052.6 + 5447.4\angle48.63^\circ \\ &= 23\,018.5\angle10.23^\circ\ \text{V} \end{aligned}

Line value =3×23.019=39.87= \sqrt3\times23.019 = 39.87 kV.

%VR=23 018.5−19 052.619 052.6×100=20.82%\%VR = \frac{23\,018.5 - 19\,052.6}{19\,052.6}\times100 = 20.82\%

Phasor diagram (lagging load)

                         Vs (23.02 kV, 10.23 deg)
                        /|
                       / | I*X (5.25 kV, leads I by 90)
                      /  |
                     /   |
     O-------------------+--> I*R (1.46 kV, along I)
      \        Vr (19.05 kV, reference)
       \
        \  phi_R = 25.84 deg
         v
          I (291.6 A)
  • VRV_R is the reference.
  • II lags VRV_R by ϕR=25.84∘\phi_R = 25.84^\circ.
  • IRIR is drawn from the tip of VRV_R parallel to II; IXIX is drawn from its tip, perpendicular to II (leading).
  • VSV_S joins OO to the end of IXIX and leads VRV_R by δ=10.23∘\delta = 10.23^\circ; II lags VSV_S by 36.07∘36.07^\circ (sending pf 0.808 lag).

Answer: Efficiency ≈ 92.16 %, regulation ≈ 20.82 % (VSV_S = 39.87 kV).