Voltage regulation of transformer for lagging load
Short answer
Voltage regulation is the rise in secondary voltage from full load to no load expressed as a percentage of no-load voltage. For lagging load, approximate percentage regulation equals %R cos phi plus %X sin phi, so V2 falls below E2.
Define voltage regulation of a transformer. Deduce the expression for the voltage regulation when it is connected with lagging load.
Voltage regulation
Voltage regulation of a transformer is the change in secondary terminal voltage from no load to full load, expressed as a fraction (or percentage) of the no-load voltage, with the primary voltage held constant:
where is the no-load secondary voltage and is the full-load secondary voltage. A small regulation is desirable (power transformers: about 2-6%).
Expression for lagging load
Use the equivalent circuit referred to the secondary: . Take as reference; lags by .
Phasor diagram (approximate):
C
/
/ I2.X02
/ (perp. to I2)
O -------------------- A /
V2 \ /
\ /
I2.R02 B
(parallel to I2)
E2 = OC (join O to C); I2 lags V2 by phi
Construction: from O draw = OA. Draw = AB parallel to , and = BC perpendicular to (leading it by 90°). Then OC = . Drop a perpendicular from C to the extended OA line, meeting it at D.
Because the angle between and is very small, :
Therefore, for a lagging power factor:
or, in per-unit form,
where and .
A more exact expression keeps the CD term:
Notes
- For lagging loads regulation is always positive ().
- For leading loads the sign of the term becomes negative, so regulation can be zero or negative.
- Regulation is zero when (a leading pf), and maximum when (a lagging pf).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Voltage regulation of 2 MVA Δ-Y transformer · Electrical Machines I, chapter 2
- Efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Regulation and zero-regulation power factor of 100 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Efficiency of 5 kVA transformer at 2 kW load · Electrical Machines I, chapter 2
- Transformer no-load and load operation, constant core flux · Electrical Machines I, chapter 2 · asked 5×
- Voltage regulation expression for inductive load · Electrical Machines, chapter 2
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- 4.2 kV/120 V transformer voltage regulation · Electrical Machines, chapter 2
- Secondary voltage, regulation, pf for max regulation · Electrical Machines, chapter 2