- 2074 Bhadra · 8 marks
Efficiency and regulation of 5 kVA transformer
Short answer
Assuming iron loss 100 W, full-load copper loss is scaled from SC test: 200×(12.5/11.4)^2 = 240.5 W. Output 4500 W at 0.9 pf. Efficiency = 92.97%. Voltage regulation using R02=1.539 Ω, X02=3.153 Ω and 0.9 pf lagging = 8.62%.
Open circuit and Short circuit test on 5 kVA, 220/400 V, 50 Hz, single phase transformer gave the following results. Short circuit test (on H.V. side): 40 V, 11.4 A, 200 watts. Determine the efficiency and the voltage regulation of the transformer at full load at 0.9 pf lagging.
Only the short-circuit data is given; the open-circuit result is needed for iron loss. Assumption: the usual OC data for this textbook problem, 220 V, 2 A, 100 W on the LV side, i.e. iron loss W. (If a different OC wattmeter reading is given, replace 100 W.)
Rated HV current: A. The SC test was done at 11.4 A, so its copper loss must be scaled to full load.
Parameters from SC test (HV side)
Full-load copper loss
Efficiency at full load, 0.9 pf lagging
Voltage regulation at full load, 0.9 pf lagging
, .
The regulation does not depend on the OC test, so 8.62% holds whatever the iron loss is.
Answer: Full-load efficiency at 0.9 pf lagging 92.97% (with = 100 W); voltage regulation = 8.62%.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- Efficiency and loading of 50 kVA transformer at 40 kW · Electrical Machines I, chapter 2
- OC/SC test of 2200/110 V, 40 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×
- 5 kVA 220/400 V efficiency and regulation · Electrical Machines, chapter 2
- 10 kVA 200/400 V LV-side parameters · Electrical Machine, chapter 2
- 10 kVA 200/400 V tests, parameters on LV side · Electrical Machines, chapter 2
- 20 kVA 250/2500 V tests, regulation, efficiency · Electrical Machines, chapter 2