Voltage regulation of 2 MVA Δ-Y transformer

Short answer

Refer secondary resistance to primary: R01=14 ohm. At full load, %R=0.857% and %X=6.947%, so regulation at 0.75 pf lagging is 0.857*0.75+6.947*0.6614=5.24%.

A 2 MVA, Delta-star, 33/6.6 kV, three phase transformer has primary and secondary resistance of 8 ohm and 0.08 ohm per phase. The percentage impedance is 7 percent. Calculate the voltage regulation at full load at 0.75 pf lagging.

Regulation is worked out per phase. The primary is delta (phase voltage = line voltage) and the secondary is star (phase voltage = line voltage/3\sqrt{3}).

Step 1: Per-phase voltages and turns ratio

V1ph=33000 V,V2ph=66003=3810.5 VK=V2phV1ph=3810.533000=0.11547\begin{aligned} V_{1ph} &= 33000\ \text{V}, \quad V_{2ph} = \frac{6600}{\sqrt{3}} = 3810.5\ \text{V} \\ K &= \frac{V_{2ph}}{V_{1ph}} = \frac{3810.5}{33000} = 0.11547 \end{aligned}

Step 2: Equivalent resistance referred to primary (per phase)

R2′=R2K2=0.080.115472=6.0 ΩR01=R1+R2′=8+6=14 Ω\begin{aligned} R_2' &= \frac{R_2}{K^2} = \frac{0.08}{0.11547^2} = 6.0\ \Omega \\ R_{01} &= R_1 + R_2' = 8 + 6 = 14\ \Omega \end{aligned}

Step 3: Percentage resistance and reactance

Full-load primary phase current:

I1ph=2×1063×33000=20.2 AI_{1ph} = \frac{2 \times 10^6}{3 \times 33000} = 20.2\ \text{A} %R=I1phR01V1ph×100=20.2×1433000×100=0.857%%Z=7% (given)%X=72−0.8572=6.947%\begin{aligned} \%R &= \frac{I_{1ph} R_{01}}{V_{1ph}} \times 100 = \frac{20.2 \times 14}{33000} \times 100 = 0.857\% \\ \%Z &= 7\% \ (\text{given}) \\ \%X &= \sqrt{7^2 - 0.857^2} = 6.947\% \end{aligned}

Step 4: Regulation at 0.75 pf lagging

cos⁡ϕ=0.75\cos\phi = 0.75, sin⁡ϕ=1−0.752=0.6614\sin\phi = \sqrt{1 - 0.75^2} = 0.6614.

%Reg≈%Rcos⁡ϕ+%Xsin⁡ϕ=0.857×0.75+6.947×0.6614=0.643+4.595=5.24%\begin{aligned} \%\text{Reg} &\approx \%R\cos\phi + \%X\sin\phi \\ &= 0.857 \times 0.75 + 6.947 \times 0.6614 \\ &= 0.643 + 4.595 = 5.24\% \end{aligned}

If the more exact formula is used, adding the second-order term (%Xcos⁡ϕ−%Rsin⁡ϕ)2200\frac{(\%X\cos\phi - \%R\sin\phi)^2}{200} gives about 5.35%.

Answer: Full-load voltage regulation at 0.75 pf lagging is about 5.24% (approximate formula).