Transformer no-load and load operation, constant core flux

Short answer

No-load: V1 = E1 = 4.44fN1φm; only magnetizing current I0 flows. Loaded: secondary mmf N2I2 tends to reduce φ; primary draws extra load current I2' with N1I2' = N2I2, so net mmf stays N1I0. Since V1 and f are fixed, φm = V1/(4.44fN1) remains constant at any load.

Explain the no-load and loaded operation of an ideal transformer. Prove that the net magnetic flux in the core remains constant at any load.

An ideal transformer has no winding resistance, no leakage flux, no core loss and a core of infinite permeability (so it needs negligible magnetising current). Its primary and secondary are linked by the same mutual flux φ.

No-load operation

          phi (mutual flux)
     +---------------------+
  I0 |                     |
 o-->|]  N1           N2  [|---o
 V1  |]  E1           E2  [|   open
 o---|]               [   |---o
     +---------------------+
  • The primary is connected to V1V_1; the secondary is open, so I2=0I_2 = 0.
  • Since the winding has no resistance, the applied voltage is balanced only by the induced emf: V1=E1=4.44fN1ϕmV_1 = E_1 = 4.44 f N_1\phi_m. This fixes the flux.
  • A very small current I0I_0 (the magnetising current ImI_m) flows. It is in phase with φ and lags V1V_1 by 90°, so the input power is zero.
  • The same flux induces E2=4.44fN2ϕmE_2 = 4.44 f N_2\phi_m in the secondary. E1E_1 and E2E_2 are in phase, both lagging φ by 90°, and
E1E2=N1N2\frac{E_1}{E_2} = \frac{N_1}{N_2}

Phasor diagram (no load): ϕ\phi along the reference, I0I_0 in phase with φ, V1V_1 leading φ by 90°, E1E_1 and E2E_2 opposite to V1V_1.

Loaded operation

  1. A load is connected; current I2I_2 flows in the secondary. It produces mmf N2I2N_2 I_2 which, by Lenz's law, opposes the mutual flux.
  2. If φ fell, E1E_1 would fall below V1V_1. The primary therefore draws an extra load component of current I2′I_2' whose mmf exactly cancels the secondary mmf:
N1I2′=N2I2⇒I2′=N2N1I2N_1 I_2' = N_2 I_2 \Rightarrow I_2' = \frac{N_2}{N_1}I_2
  1. Total primary current I1=I0+I2′I_1 = I_0 + I_2'. Power drawn from the supply rises to match the load: V1I1cos⁡ϕ1=V2I2cos⁡ϕ2V_1 I_1 \cos\phi_1 = V_2 I_2\cos\phi_2.

Proof that the core flux remains constant at any load

Net mmf acting on the core:

Fnet=N1I1−N2I2=N1(I0+I2′)−N2I2=N1I0+(N1I2′−N2I2)=N1I0\begin{aligned} F_{net} &= N_1 I_1 - N_2 I_2 \\ &= N_1 (I_0 + I_2') - N_2 I_2 \\ &= N_1 I_0 + (N_1 I_2' - N_2 I_2) \\ &= N_1 I_0 \end{aligned}

So the net mmf, and hence the flux ϕ=N1I0/S\phi = N_1 I_0 / S, is the same as on no load. The same result follows from the voltage equation: since V1=E1=4.44fN1ϕmV_1 = E_1 = 4.44 f N_1\phi_m at every load and V1V_1, ff and N1N_1 are fixed,

ϕm=V14.44fN1=constant\phi_m = \frac{V_1}{4.44 f N_1} = \text{constant}

Hence the mutual flux of an ideal transformer is independent of load, from no load to full load. In a practical transformer it falls only very slightly because of the small leakage impedance drop.