Transformer operation; flux constant at any load
Short answer
At no-load, primary mmf N₁I₀ establishes flux Φ. On load, secondary mmf N₂I₂ opposes flux, so primary draws extra current I₂′ with N₁I₂′ = N₂I₂, making net mmf N₁I₀ unchanged. Since V₁ ≈ E₁ = 4.44 f N₁ Φₘ and V₁, f are constant, core flux remains the same at all loads.
Explain the no-load and loaded operation of a transformer. Prove that the net magnetic flux in the core remains constant at any load.
A transformer works on mutual induction. Its operation is explained at no-load and on load, and the same net flux is present in both.
No-load operation
I0 <-- Primary Secondary (open)
o--+ +-------------+ +--o
V1 |N1| core Φ |N2| E2 = V2 (no current)
o--+ +-------------+ +--o
- The primary is connected to the supply V1 and the secondary is open.
- A small no-load current I0 flows. It has a magnetising component Iμ (in phase with Φ, produces the flux) and a core-loss component Iw (in phase with V1, supplies the iron loss). So I0 = √(Iμ² + Iw²) = 2 to 5 % of full-load current.
- The alternating flux Φ links both windings: E1 = 4.44 f N1 Φm, E2 = 4.44 f N2 Φm. Since E1 ≈ V1, the flux is fixed by V1.
- Primary current lags V1 by nearly 90°, so the no-load power factor is very low.
Loaded operation
- A load is connected to the secondary. A secondary current I2 flows and produces an mmf N2 I2 which, by Lenz's law, opposes the flux Φ.
- The flux tends to fall, so E1 falls slightly and the primary draws a larger current. The extra current I2′ gives an mmf N1 I2′ that cancels N2 I2: N1 I2′ = N2 I2 or I2′ = (N2/N1) I2.
- Total primary current: I1 = I0 + I2′ (phasor sum).
Proof that the net flux is constant
Net mmf acting on the core = N1 I1 − N2 I2
= N1 (I0 + I2′) − N2 I2
= N1 I0 + N1 I2′ − N2 I2
= N1 I0 + 0 (because N1 I2′ = N2 I2)
So the net mmf is N1 I0, the same as at no-load. Since the flux produced by this mmf is Φ, the core flux is the same at all loads. This is also clear from V1 ≈ E1 = 4.44 f N1 Φm. V1 and f are constant, so Φm is constant.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer no-load and load operation, constant core flux · Electrical Machines I, chapter 2 · asked 5×
- No-load and loaded operation, constant flux · Electrical Machines, chapter 2 · asked 3×
- Real transformer no-load operation and amp-turn balance · Electrical Machines I, chapter 2
- Constant flux from no load to full load · Electrical Machines, chapter 2
- No-load current components, iron loss and core flux · Electrical Machines I, chapter 2
- Ideal transformer no-load and loaded, ratios · Electrical Machines, chapter 2 · asked 2×
- No load current of single phase transformer · Electric Machine Design, chapter 3