- 2070 Bhadra · 4 marks
Constant flux from no load to full load
Short answer
Primary voltage V1 ≈ E1 = 4.44 f N1 φm; since V1 and f are fixed, φm is practically constant. Also, load current's mmf is balanced by primary load component N1 I1' = N2 I2, leaving net core mmf unchanged. Thus flux remains nearly constant from no-load to full-load.
The flux in transformer remains practically constant from no load to full load. Justify the statement.
The core flux of a transformer is fixed by the applied primary voltage, not by the load. Therefore it stays practically constant from no load to full load.
Reason 1: voltage balance in the primary
The primary impedance drop is only 1 to 3% of at full load. Since the supply voltage and frequency are constant, stays practically constant.
Reason 2: mmf balance
When a load current flows, its mmf tends to reduce the flux. The primary current immediately increases by , so that
The net mmf in the core is then again , the no-load value, so the flux does not change.
Conclusion: the only change in flux comes from the small primary impedance drop , which is about 1 to 3% at full load. Because the flux is constant, the core (iron) loss is constant at all loads, and the core loss measured at no load can be taken as the core loss at full load.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer no-load and load operation, constant core flux · Electrical Machines I, chapter 2 · asked 5×
- No-load and loaded operation, constant flux · Electrical Machines, chapter 2 · asked 3×
- Real transformer no-load operation and amp-turn balance · Electrical Machines I, chapter 2
- No-load current components, iron loss and core flux · Electrical Machines I, chapter 2
- Starting, no-load and full-load current of slip ring motor · Electrical Machines I, chapter 5
- Slip ring motor: starting, no-load, full-load currents · Electrical Machines, chapter 5
- Transformer operation; flux constant at any load · Electrical Machine, chapter 2 · asked 3×
- No load current of single phase transformer · Electric Machine Design, chapter 3
- Ideal transformer no-load, load, ratios · Electrical Machine, chapter 2 · asked 2×
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2