Real transformer no-load operation and amp-turn balance

Short answer

At no load, primary draws I0 consisting of magnetizing Iμ and core-loss Iw components, with low pf. When loaded, secondary ampere-turns N2I2 are balanced by primary load component I2' (N1I2'= N2I2), so net MMF equals N1I0. Thus core flux φm = V1/(4.44fN1) remains essentially constant from no load to full load.

Explain no-load operation of a real transformer. What do you mean by Amp-turn balance in loaded transformer? Prove that the magnetic flux in the core remains constant irrespective of load on transformer.

No-load operation of a real transformer

At no load the secondary is open, so I2=0I_2 = 0. The primary draws a small no-load current I0I_0 (2-5% of rated current). In a real transformer I0I_0 does two jobs, so it has two components:

  • Magnetizing component Iμ=I0sin⁡ϕ0I_\mu = I_0\sin\phi_0: in phase with flux, lags V1V_1 by 90°, sets up the core flux. It is the larger part.
  • Working (core-loss) component Iw=I0cos⁡ϕ0I_w = I_0\cos\phi_0: in phase with V1V_1, supplies hysteresis and eddy-current losses (plus a tiny I02R1I_0^2R_1).
I0=Iμ2+Iw2,P0=V1I0cos⁡ϕ0≈PiI_0 = \sqrt{I_\mu^2 + I_w^2}, \qquad P_0 = V_1I_0\cos\phi_0 \approx P_i

The no-load pf cos⁡ϕ0\cos\phi_0 is low (0.1-0.3), so ϕ0\phi_0 is close to 90°.

        V1 = -E1
          ^
          |   . I0
       Iw |  /
          | /  phi0 (near 90 deg)
          |/
  --------O----------> phi
          |   Im
          v E1, E2

Amp-turn balance in a loaded transformer

When load is connected, secondary current I2I_2 produces MMF N2I2N_2I_2 which opposes the flux (Lenz's law). The primary immediately draws an extra load component I2′I_2' whose MMF exactly cancels it:

N1I2′=N2I2⇒I2′=N2N1I2=KI2N_1I_2' = N_2I_2 \quad\Rightarrow\quad I_2' = \frac{N_2}{N_1}I_2 = KI_2

This equality of opposing ampere-turns is called ampere-turn (MMF) balance. The total primary current is Iˉ1=Iˉ0+Iˉ2′\bar I_1 = \bar I_0 + \bar I_2'; since I0I_0 is small, N1I1≈N2I2N_1I_1 \approx N_2I_2.

Proof that core flux is (nearly) constant at all loads

  1. The applied voltage V1V_1 is fixed. Neglecting the small primary drop, V1≈E1=4.44fN1ϕmV_1 \approx E_1 = 4.44fN_1\phi_m. Hence
ϕm=V14.44fN1=constant\phi_m = \frac{V_1}{4.44fN_1} = \text{constant}
  1. MMF view: net core MMF with load is
N1Iˉ1−N2Iˉ2=N1(Iˉ0+Iˉ2′)−N2Iˉ2=N1Iˉ0+(N1Iˉ2′−N2Iˉ2)=N1Iˉ0N_1\bar I_1 - N_2\bar I_2 = N_1(\bar I_0 + \bar I_2') - N_2\bar I_2 = N_1\bar I_0 + (N_1\bar I_2' - N_2\bar I_2) = N_1\bar I_0

because the bracket is zero by amp-turn balance. The net MMF equals the no-load MMF N1I0N_1I_0, so the core flux ϕ=N1I0R\phi = \frac{N_1I_0}{\mathcal R} is the same as at no load. 3. Self-regulation: if load rises, I2I_2 rises, flux tends to fall, E1E_1 falls slightly, so (V1−E1)(V_1 - E_1) rises and the primary draws more current until the flux is restored.

Hence the core flux, and therefore iron loss, remain practically constant from no load to full load. (Strictly, ϕ\phi falls a little at full load because of the I1Z1I_1Z_1 drop, about 1-2%.)