Transformer no-load operation and ideal transformer properties

Short answer

At no load the primary draws a small current I0 with magnetising component Im lagging voltage by 90 degrees and core-loss component Ic in phase with voltage; no-load pf is low. An ideal transformer has zero resistance, no leakage flux, infinite permeability, no core loss, 100% efficiency, and V1/V2 = N1/N2 = I2/I1.

Explain no load operation of single phase transformers. What are properties of ideal transformer?

No-load operation of a single-phase transformer

With the secondary open (I2=0I_2 = 0), the primary draws a small no-load current I0I_0 (2–5% of rated) from the supply. It does two jobs, so it has two components:

  • Magnetising component Im=I0sin⁡ϕ0I_m = I_0\sin\phi_0: in phase with the flux, lags V1V_1 by 90°; it sets up the core flux.
  • Core-loss (working) component Ic=I0cos⁡ϕ0I_c = I_0\cos\phi_0: in phase with V1V_1; it supplies hysteresis and eddy losses (and a very small I02R1I_0^2 R_1).
I0=Im2+Ic2,P0=V1I0cos⁡ϕ0≈core lossI_0 = \sqrt{I_m^2 + I_c^2}, \qquad P_0 = V_1 I_0\cos\phi_0 \approx \text{core loss}
        V1
        ^
        |    I0
        |   /
     Ic |  /  phi0 (about 75-85 deg)
        | /
        +--------> phi, Im
        |
        v E1, E2

The no-load power factor is low (0.1–0.3 lag). The shunt branch of the equivalent circuit is R0=V1/IcR_0 = V_1/I_c and X0=V1/ImX_0 = V_1/I_m.

Properties of an ideal transformer

  1. Zero winding resistance (no I2RI^2R loss).
  2. No leakage flux; all flux links both windings.
  3. Core of infinite permeability, so negligible magnetising current.
  4. No hysteresis or eddy current loss.
  5. 100% efficiency, zero regulation, and V1/V2=N1/N2=I2/I1V_1/V_2 = N_1/N_2 = I_2/I_1.