Load sharing of 50 kVA and 25 kVA transformers in parallel
Short answer
The 60 kVA load divides inversely with impedance: A takes 40 kVA and B takes 20 kVA. LV currents are A=181.82 A and B=90.91 A, so each transformer is loaded to 80% of rating.
A 50 kVA, 4400/220 V transformer with an equivalent impedance of (0.01+j0.02) ohm is to operate in parallel with a 25 kVA, 4400/220 V transformer with an equivalent impedance of (0.02+j0.04) ohm. The two transformers are connected in parallel and made to carry a load of 60 kVA. (i) Find the individual transformer currents. (ii) What percent of the rated capacity is used in each transformer?
For two transformers with the same voltage ratio in parallel, the load is shared in inverse ratio of their equivalent impedances:
Assumption: both impedances are referred to the 220 V (secondary) side; the load power factor is not given, but it is not needed because both impedances have the same angle.
Load sharing
Since the angles are equal, the ratios are real numbers:
Both share the load at the same power factor as the load.
(i) Individual transformer currents
Total load current on the 220 V side:
Check: A.
(ii) Percentage of rated capacity used
Both are loaded to the same fraction of their rating because the 25 kVA unit has exactly twice the ohmic impedance of the 50 kVA unit, i.e. both have the same per-unit impedance:
| Quantity | 50 kVA (A) | 25 kVA (B) |
|---|---|---|
| Impedance | 0.0224 Ω | 0.0447 Ω |
| Load shared | 40 kVA | 20 kVA |
| Secondary current | 181.82 A | 90.91 A |
| Loading | 80% | 80% |
Answer: A, A (LV side); each transformer runs at 80% of its rated capacity.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Equivalent impedance and copper loss of 50 kVA transformer · Electrical Machines I, chapter 2
- Parallel transformers and per-unit impedance load sharing · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- Efficiency of 25 kVA transformer at half load and overload · Electrical Machines I, chapter 2
- Equivalent circuit of 100 kVA 2200/220 V transformer · Electrical Machines I, chapter 2 · asked 3×
- Load sharing of two transformers in parallel · Electrical Machines, chapter 2
- 50 kVA transformer: equivalent parameters, copper loss · Electrical Machines, chapter 2
- Load sharing between two stations in parallel · Electric Machines II, chapter 1
- G-S two iterations, lines 0.02+j0.11 · Power System Analysis II, chapter 2