50 kVA transformer: equivalent parameters, copper loss

Short answer

Referred to primary: Req = 7.050 Ω, Xeq = 11.200 Ω, Zeq = 13.234 Ω. Referred to secondary: Req = 0.01762 Ω, Xeq = 0.02800 Ω, Zeq = 0.03309 Ω. Total copper loss = 910.4 W.

A 50 kVA, 4400/220 V transformer has R1=3.45 ΩR_1 = 3.45\ \Omega, R2=0.009 ΩR_2 = 0.009\ \Omega, X1=5.2 ΩX_1 = 5.2\ \Omega and X2=0.015 ΩX_2 = 0.015\ \Omega. Calculate (i) equivalent resistance, reactance and impedance as referred to both primary and secondary sides (ii) total copper loss using individual resistance of the two windings and using equivalent resistances as referred to each side.

The equivalent values are found by moving one winding's impedance to the other side using the square of the turns ratio.

Turns ratio: a=V1V2=4400220=20a = \dfrac{V_1}{V_2} = \dfrac{4400}{220} = 20

Rated currents:

I1=500004400=11.364 A,I2=50000220=227.27 AI_1 = \frac{50000}{4400} = 11.364\ \text{A}, \qquad I_2 = \frac{50000}{220} = 227.27\ \text{A}

(i) Equivalent resistance, reactance and impedance

Referred to primary:

R01=R1+a2R2=3.45+400(0.009)=7.050 ΩX01=X1+a2X2=5.2+400(0.015)=11.200 ΩZ01=R012+X012=7.0502+11.2002=13.234 Ω\begin{aligned} R_{01} &= R_1 + a^2R_2 = 3.45 + 400(0.009) = 7.050\ \Omega \\ X_{01} &= X_1 + a^2X_2 = 5.2 + 400(0.015) = 11.200\ \Omega \\ Z_{01} &= \sqrt{R_{01}^2 + X_{01}^2} = \sqrt{7.050^2 + 11.200^2} = 13.234\ \Omega \end{aligned}

Referred to secondary:

R02=R2+R1a2=0.009+3.45400=0.01762 ΩX02=X2+X1a2=0.015+5.2400=0.02800 ΩZ02=R022+X022=0.03309 Ω\begin{aligned} R_{02} &= R_2 + \frac{R_1}{a^2} = 0.009 + \frac{3.45}{400} = 0.01762\ \Omega \\ X_{02} &= X_2 + \frac{X_1}{a^2} = 0.015 + \frac{5.2}{400} = 0.02800\ \Omega \\ Z_{02} &= \sqrt{R_{02}^2 + X_{02}^2} = 0.03309\ \Omega \end{aligned}

(ii) Total copper loss

Using individual resistances:

Pcu=I12R1+I22R2=(11.364)2(3.45)+(227.27)2(0.009)=445.5+464.9=910.4 WP_{cu} = I_1^2R_1 + I_2^2R_2 = (11.364)^2(3.45) + (227.27)^2(0.009) = 445.5 + 464.9 = 910.4\ \text{W}

Using equivalent resistance referred to primary:

Pcu=I12R01=(11.364)2(7.050)=910.4 WP_{cu} = I_1^2R_{01} = (11.364)^2(7.050) = 910.4\ \text{W}

Using equivalent resistance referred to secondary:

Pcu=I22R02=(227.27)2(0.01762)=910.4 WP_{cu} = I_2^2R_{02} = (227.27)^2(0.01762) = 910.4\ \text{W}

All three methods give the same loss.