Per-unit transformer impedance same on both sides
Short answer
With base voltages chosen in the transformer turns ratio and a common base MVA, the per-unit impedance is identical on both sides because the impedance and base impedance scale by the square of the turns ratio, cancelling out. Thus Z_pu,LV = Z_pu,HV.
Verify mathematically the following statement: "The per unit impedance of a transformer remains the same when referred to the high voltage side or low voltage side of the transformer."
The statement is true. The per-unit impedance of a transformer is the same on both sides, provided the base voltages on the two sides are in the ratio of the transformer turns (with the same VA base).
Proof
Consider a transformer of rating (VA), with voltages (LV) and (HV) and turns ratio . Choose:
- the same base VA, , on both sides
- base voltages and , so that
Base impedances:
Let be the equivalent impedance referred to the LV side. Referred to the HV side, it becomes:
Per-unit values:
So is the same whichever side it is referred to.
Numerical check
Take a 10 kVA, 200/400 V transformer with referred to the LV side.
- LV side: , so .
- HV side: and , so .
Significance
The ideal transformer disappears from the per-unit equivalent circuit, leaving only a series impedance. Manufacturers can therefore quote a single % or p.u. impedance without naming a side. The result holds only when the bases follow the turns ratio. If they do not, an off-nominal tap must be included.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Maximum voltage of 3-disc string, 17.5 kV per unit · Power System Analysis I, chapter 2
- Per unit values: 100 MVA generator, two motors · Power System Analysis I, chapter 3
- Per unit system and its advantages · Power System Analysis I, chapter 3 · asked 3×
- Per unit advantages and choice of bases · Power System Analysis I, chapter 3 · asked 3×
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Major advantages of per unit system · Power System Analysis I, chapter 3
- 250/500 V transformer, parameters both sides · Electrical Machines, chapter 2
- Parallel transformers and per-unit impedance load sharing · Electrical Machines I, chapter 2
- Equivalent impedance and copper loss of 50 kVA transformer · Electrical Machines I, chapter 2
- Per unit resistance drop of core type transformer · Electric Machine Design, chapter 3