Skip to main content

Chapter 3 · 8 hours

Computational Technique

IOE past exam questions

Past questions and answers

46 questions set from this chapter, 5 of them more than once. Most asked first.

  • Asked 4 times
  • 2080 Chaitra · 4 marks
  • 2079 Chaitra · 4 marks
  • 2075 Bhadra · 4 marks
  • 2070 Magh · 6 marks

What will be the consequences if AC complex power is calculated as S = V*I? Explain with necessary phasor diagrams.

Answer

The standard definition of complex power is S=VI∗=P+jQS = VI^* = P + jQ. With this convention, a lagging (inductive) load absorbs positive QQ. Using S=V∗IS = V^*I gives the same PP but reverses the sign of QQ.

Derivation

Let V=∣V∣∠θvV = |V|\angle\theta_v and I=∣I∣∠θiI = |I|\angle\theta_i, with ϕ=θv−θi\phi = \theta_v - \theta_i (positive for a lagging current).

VI∗=∣V∣∣I∣∠(θv−θi)=∣V∣∣I∣cos⁡ϕ+j∣V∣∣I∣sin⁡ϕV∗I=∣V∣∣I∣∠(θi−θv)=∣V∣∣I∣cos⁡ϕ−j∣V∣∣I∣sin⁡ϕ\begin{aligned} VI^* &= |V||I|\angle(\theta_v-\theta_i) = |V||I|\cos\phi + j|V||I|\sin\phi\\ V^*I &= |V||I|\angle(\theta_i-\theta_v) = |V||I|\cos\phi - j|V||I|\sin\phi \end{aligned}

So V∗I=(VI∗)∗=P−jQV^*I = (VI^*)^* = P - jQ.

Phasor diagrams (inductive load, current lags)

 S = V I*                 S = V* I
      Q>0  S                 V
     ^    /                 /
     |   / phi             / phi  (V ref)
     |  /                 /------> P
     | /                   \
     |/-------> P           \  S
                             v  Q<0
 Inductive load:           Inductive load:
 Q positive (absorbs)      Q appears negative

Consequences of using S=V∗IS = V^*I

  • The real power PP is unchanged, since cos⁡ϕ\cos\phi is even.
  • The sign of QQ is reversed: an inductor (lagging current) would appear to supply reactive power, and a capacitor to absorb it.
  • This contradicts the standard convention (IEEE/IEC) that inductive loads absorb VAr. Generator, motor and load data would be read wrongly.
  • The power factor angle and the power triangle are flipped, so lagging and leading would be confused.
  • In load flow and compensation studies, capacitor banks would be sized in the wrong direction.

Example: Take V=100∠0∘V = 100\angle0^\circ V and I=10∠−30∘I = 10\angle-30^\circ A (inductive load).

  • VI∗=1000∠30∘=866+j500VI^* = 1000\angle30^\circ = 866 + j500: the load absorbs 500 var, which is correct.
  • V∗I=1000∠−30∘=866−j500V^*I = 1000\angle-30^\circ = 866 - j500: this wrongly shows the inductive load as a source of 500 var.

S=VI∗S = VI^* is used so that inductive Q is positive.

  • Asked 4 times
  • 2080 Chaitra · 4 marks
  • 2079 Chaitra · 4 marks
  • 2075 Bhadra · 6 marks
  • 2074 Bhadra · 2+4 marks

Verify mathematically the following statement: "The per unit impedance of a transformer remains the same when referred to the high voltage side or low voltage side of the transformer."

Answer

The statement is true. The per-unit impedance of a transformer is the same on both sides, provided the base voltages on the two sides are in the ratio of the transformer turns (with the same VA base).

Proof

Consider a transformer of rating SS (VA), with voltages V1V_1 (LV) and V2V_2 (HV) and turns ratio a=V1/V2=N1/N2a = V_1/V_2 = N_1/N_2. Choose:

  • the same base VA, SbS_b, on both sides
  • base voltages Vb1=V1V_{b1} = V_1 and Vb2=V2V_{b2} = V_2, so that Vb1/Vb2=aV_{b1}/V_{b2} = a

Base impedances:

Zb1=Vb12Sb,Zb2=Vb22Sb  ⇒  Zb1Zb2=a2Z_{b1} = \frac{V_{b1}^2}{S_b},\qquad Z_{b2} = \frac{V_{b2}^2}{S_b} \;\Rightarrow\; \frac{Z_{b1}}{Z_{b2}} = a^2

Let Z1Z_1 be the equivalent impedance referred to the LV side. Referred to the HV side, it becomes:

Z2=Z1(N2N1)2=Z1a2Z_2 = Z_1\left(\frac{N_2}{N_1}\right)^2 = \frac{Z_1}{a^2}

Per-unit values:

Z1,pu=Z1Zb1,Z2,pu=Z2Zb2=Z1/a2Zb1/a2=Z1Zb1=Z1,puZ_{1,pu} = \frac{Z_1}{Z_{b1}},\qquad Z_{2,pu} = \frac{Z_2}{Z_{b2}} = \frac{Z_1/a^2}{Z_{b1}/a^2} = \frac{Z_1}{Z_{b1}} = Z_{1,pu}

So ZpuZ_{pu} is the same whichever side it is referred to.

Numerical check

Take a 10 kVA, 200/400 V transformer with Z=0.4 ΩZ = 0.4\ \Omega referred to the LV side.

  • LV side: Zb=2002/10000=4 ΩZ_b = 200^2/10000 = 4\ \Omega, so Zpu=0.4/4=0.1Z_{pu} = 0.4/4 = 0.1.
  • HV side: Z=0.4×(400/200)2=1.6 ΩZ = 0.4\times(400/200)^2 = 1.6\ \Omega and Zb=4002/10000=16 ΩZ_b = 400^2/10000 = 16\ \Omega, so Zpu=1.6/16=0.1Z_{pu} = 1.6/16 = 0.1.

Significance

The ideal transformer disappears from the per-unit equivalent circuit, leaving only a series impedance. Manufacturers can therefore quote a single % or p.u. impedance without naming a side. The result holds only when the bases follow the turns ratio. If they do not, an off-nominal tap must be included.

  • Asked 3 times
  • 2077 Chaitra · 4 marks
  • 2076 Bhadra · 4 marks
  • 2075 Baisakh · 4 marks

What is per unit system? What are the advantages of per unit representation?

Answer

In the per-unit system, every quantity (voltage, current, power, impedance) is expressed as a fraction of a chosen base value of the same unit:

per-unit value=actual valuebase value\text{per-unit value} = \frac{\text{actual value}}{\text{base value}}

Usually the base MVA (SbS_b) and the base kV (VbV_b) are chosen. The other bases follow from them:

Ib=Sb3Vb,Zb=Vb2SbI_b = \frac{S_b}{\sqrt3 V_b},\qquad Z_b = \frac{V_b^2}{S_b}

For example, at 100 MVA and 132 kV, Zb=174.24 ΩZ_b = 174.24\ \Omega, so a 50 Ω line has Z=0.287Z = 0.287 p.u.

Advantages

  1. Transformers disappear: The p.u. impedance of a transformer is the same on both sides, so the ideal transformers drop out of the equivalent circuit.
  2. Compact ranges: The p.u. impedances of machines and transformers of similar type lie in a narrow range whatever their size. This makes it easy to check data and to estimate missing values.
  3. Manufacturers' data: Impedances are given in % or p.u. on the equipment's own rating, so they can be used directly after a simple change of base.
  4. Three-phase and single-phase are the same: In p.u. the line and phase values are equal and the factor 3\sqrt3 disappears from the calculations.
  5. Easier hand and computer calculation: The numbers are of order 1, so errors are easy to spot. Load flow and fault programs use p.u. throughout.
  6. Meaningful comparison: A voltage of 0.95 p.u. immediately shows a 5 % drop at any voltage level.
  • Asked 3 times
  • 2072 Asoj · 3+3 marks
  • 2071 Bhadra · 5 marks
  • 2069 Bhadra · 6 marks

List out the advantages of the per unit system. How are the base voltages and base power chosen?

Answer

Advantages of the per-unit system

  1. The p.u. impedance of a transformer is the same on the HV and LV sides, so ideal transformers vanish from the equivalent circuit.
  2. The p.u. impedances of similar equipment lie in a narrow band, whatever the rating. This makes it easy to check data and to assume typical values.
  3. Manufacturers give impedances in % or p.u. on the rating of the equipment, and these can be used directly.
  4. Line and phase quantities have the same p.u. value, and 3\sqrt3 factors disappear. Single-phase and three-phase calculations look alike.
  5. The numbers are near 1, which reduces arithmetic errors. It is easy to see abnormal conditions, for example V=0.9V = 0.9 p.u.
  6. It is ideal for computer studies (load flow, fault and stability analysis).

Choosing base power and base voltages

  1. Base power (SbS_b, MVA): Choose one value for the whole system. It is usually the rating of the largest machine or a round figure such as 100 MVA.
  2. Base voltage (VbV_b, kV): Choose it in one section, usually the generator or line section, often equal to that section's rated voltage.
  3. Other sections: Carry the base voltage through each transformer by its line-to-line voltage ratio:
Vb,new=Vb,old×Vrated, new sideVrated, old sideV_{b,new} = V_{b,old}\times\frac{V_{rated,\ new\ side}}{V_{rated,\ old\ side}}

For single-phase units in a Y–Δ bank, use the line voltage ratio (3V\sqrt3 V on the Y side).

  1. Derived bases:
Ib=Sb3Vb,Zb=Vb2SbI_b = \frac{S_b}{\sqrt3V_b},\qquad Z_b = \frac{V_b^2}{S_b}
  1. Change of base: Convert each equipment value to the common base:
Zpu,new=Zpu,old×Sb,newSb,old×(Vb,oldVb,new)2Z_{pu,new} = Z_{pu,old}\times\frac{S_{b,new}}{S_{b,old}}\times\left(\frac{V_{b,old}}{V_{b,new}}\right)^2

Example: Take Sb=100S_b = 100 MVA and 11 kV in the generator circuit, with an 11/132 kV transformer. The line base is 132 kV and Zb=1322/100=174.24 ΩZ_b = 132^2/100 = 174.24\ \Omega.

  • Asked 2 times
  • 2070 Magh · 4 marks
  • 2069 Bhadra · 4 marks

Discuss complex power and its significance in circuit analysis.

Answer

Complex power SS is the product of the voltage phasor and the conjugate of the current phasor. Its real part is the active power and its imaginary part is the reactive power:

S=VI∗=∣V∣∣I∣∠ϕ=P+jQS = VI^* = |V||I|\angle\phi = P + jQ

where:

  • P=∣V∣∣I∣cos⁡ϕP = |V||I|\cos\phi (W)
  • Q=∣V∣∣I∣sin⁡ϕQ = |V||I|\sin\phi (var)
  • ∣S∣=∣V∣∣I∣|S| = |V||I| (VA) is the apparent power
  • ϕ=θv−θi\phi = \theta_v - \theta_i

For a three-phase system, S3ϕ=3VphIph∗=3VLIL∠ϕS_{3\phi} = 3V_{ph}I_{ph}^* = \sqrt3 V_LI_L\angle\phi.

Power triangle

        S (VA)
       /|
      / |  Q (var)
     /phi|
    /____|
      P (W)

Significance in circuit and power system analysis

  • One complex number gives both PP and QQ, together with their signs, so power flow is described completely.
  • Sign convention: With S=VI∗S = VI^*, an inductive load absorbs +Q+Q and a capacitor absorbs −Q-Q (that is, it supplies Q). A source delivers power when SS, computed with current leaving its + terminal, is positive.
  • Conservation: The sum of complex power over all elements is zero (Tellegen's theorem), so ∑P\sum P and ∑Q\sum Q each balance. This is the basis of load flow equations.
  • It gives the power factor directly, cos⁡ϕ=P/∣S∣\cos\phi = P/|S|, and so the size of the compensation needed.
  • Equipment such as generators, transformers and cables is rated in VA (that is, ∣S∣|S|), because heating depends on ∣I∣|I|.
  • With S=I2Z=∣V∣2/Z∗S = I^2Z = |V|^2/Z^* it gives the losses and the reactive drop in lines directly.

Example: If V=230∠0∘V = 230\angle0^\circ V and I=10∠−36.87∘I = 10\angle-36.87^\circ A, then S=2300∠36.87∘=1840+j1380S = 2300\angle36.87^\circ = 1840 + j1380 VA. The load absorbs 1840 W and 1380 var at a power factor of 0.8 lagging.

  • 2082 Kartik (new course) · 4 marks

A voltage source Ean = -120∠210° V and the current through the source Ina = 10∠60° A. Find the values of real power (P) and reactive power (Q) and state whether the source is delivering or receiving each.

Answer

Use S=EI∗S = EI^*. The current InaI_{na} flows from n to a inside the source, so it leaves the positive terminal a. A positive PP or QQ therefore means the source is delivering that power.

Simplify the voltage

Ean=−120∠210∘=120∠(210∘−180∘)=120∠30∘ VE_{an} = -120\angle210^\circ = 120\angle(210^\circ - 180^\circ) = 120\angle30^\circ\ \text{V}

Complex power

S=EanIna∗=(120∠30∘)(10∠−60∘)=1200∠−30∘=1200(cos⁡30∘−jsin⁡30∘)=1039.2−j600 VA\begin{aligned} S &= E_{an}I_{na}^* = (120\angle30^\circ)(10\angle-60^\circ)\\ &= 1200\angle-30^\circ\\ &= 1200(\cos30^\circ - j\sin30^\circ)\\ &= 1039.2 - j600\ \text{VA} \end{aligned}

Interpretation

QuantityValueMeaning
PP1039.2 WPositive, so the source delivers real power
QQ−600 varNegative, so the source receives (absorbs) 600 var

The current leads the voltage by 30°, so the source sees a leading (capacitive) load. That load returns reactive power to the source.

Answer: P=1039.2P = 1039.2 W, delivered by the source. Q=600Q = 600 var, absorbed by the source (delivered Q=−600Q = -600 var).

  • 2082 Kartik (new course) · 2+6 marks

Figure below shows a single line diagram of a power system. Draw its impedance diagram without showing their values. Also, redraw the circuit with per unit values in the reactance diagram. Take 5,000 VA base and common system base voltage of 250 V. [Figure: generators G1 (2000 VA, 250 V, Z = j0.2 p.u.) and G2 (2000 VA, 250 V, Z = j0.3 p.u.) in parallel on a common bus, feeding transformer T1 (4000 VA, 250/800 V, Z = j0.2 p.u.), then a line Z = 40 + j150 Ω, then transformer T2 (8000 VA, 1000/500 V, Z = j0.06 p.u.) supplying a load.]

Answer

(a) Impedance diagram (no values)

Each generator is shown as an EMF behind its internal impedance. Each transformer is shown as series leakage impedance with a shunt magnetising branch. The line is a series R+jXR + jX (short line), and the load is an impedance.

  G1        T1                  T2
 (~)-Zg1-+-Zt1-+--R+jX line--+-Zt2-+-- Load
         |     |             |     |   Z_L
 (~)-Zg2-+    Ym             Ym     |
  G2     |     |             |     |
 ref ----+-----+-------------+-----+---

(b) Selecting the bases

  • Sb=5000S_b = 5000 VA for the whole system.
  • Generator section: Vb=250V_b = 250 V.
  • Line section: through T1 (250/800 V), Vb=250×800/250=800V_b = 250\times800/250 = 800 V.
  • Load section: through T2 (rated 1000 V on the line side), Vb=800×500/1000=400V_b = 800\times500/1000 = 400 V.

Per-unit values

Use Znew=Zold Sb,newSold(VoldVb,new)2Z_{new} = Z_{old}\,\dfrac{S_{b,new}}{S_{old}}\left(\dfrac{V_{old}}{V_{b,new}}\right)^2.

G1:j0.2×50002000×1=j0.5G2:j0.3×50002000=j0.75T1:j0.2×50004000×(250250)2=j0.25\begin{aligned} G_1&: j0.2\times\frac{5000}{2000}\times1 = j0.5\\ G_2&: j0.3\times\frac{5000}{2000} = j0.75\\ T_1&: j0.2\times\frac{5000}{4000}\times\left(\frac{250}{250}\right)^2 = j0.25 \end{aligned}

Line: the base impedance is

Zb=80025000=128 ΩZ_b = \frac{800^2}{5000} = 128\ \Omega Zline=40+j150128=0.3125+j1.1719 p.u.Z_{line} = \frac{40 + j150}{128} = 0.3125 + j1.1719\ \text{p.u.}

T2 (rated 1000 V, while the base on its side is 800 V):

j0.06×50008000×(1000800)2=j0.0586j0.06\times\frac{5000}{8000}\times\left(\frac{1000}{800}\right)^2 = j0.0586

Reactance (per-unit) diagram

  j0.5         j0.25   0.3125+j1.172   j0.0586
 (G1)--+------/\/\---------/\/\--------/\/\----Load
       |                                       |
 (G2)--+ j0.75                                 |
       |                                       |
 ------+------------ reference ----------------+
Elementp.u. value
G1j0.50
G2j0.75
T1j0.25
Line0.3125 + j1.1719
T2j0.0586

The magnetising branches are neglected in the reactance diagram. The load impedance is not given, so it is shown as a block. Its p.u. value would be ZL/ZbZ_L/Z_b with Zb=4002/5000=32 ΩZ_b = 400^2/5000 = 32\ \Omega.

  • 2081 Chaitra (new course) · 8 marks

A 90 MVA, 11 kV 3-phase generator has a reactance of 15%. The generator supplies two motors through transformers and transmission line shown in figure below. The transformer T1 is a 3-phase transformer, 100 MVA, 10/132 kV, 6% reactance. The transformer T2 is composed of 3 single phase units each rated at 30 MVA, 66/10 kV with 5% reactance. The connection of T1 and T2 are as shown. The motors rated at 50 MVA and 40 MVA, both 10 kV and 20% reactance. Taking the generator rating as base, draw the reactance diagram and indicate the reactance in per unit. The reactance of the line is 100 Ω. [Figure: G (Y, grounded) → T1 (Δ–Y, Y grounded) → Line → T2 (Y grounded–Δ) → bus feeding motor M1 (Y, grounded) and motor M2 (Δ).]

Answer

Choice of bases

  • Sb=90S_b = 90 MVA and Vb=11V_b = 11 kV in the generator circuit.
  • Line: through T1 (10/132 kV), Vb=11×13210=145.2V_b = 11\times\dfrac{132}{10} = 145.2 kV.
  • T2 is a Y–Δ bank of three single-phase 66/10 kV units. Its line-voltage ratio is 3×66=114.32\sqrt3\times66 = 114.32 kV / 10 kV, and its three-phase rating is 3×30=903\times30 = 90 MVA.
  • Motor circuit: Vb=145.2×10114.32=12.70V_b = 145.2\times\dfrac{10}{114.32} = 12.70 kV.

Per-unit reactances

Use Xnew=Xold SbSrated(VratedVb)2X_{new} = X_{old}\,\dfrac{S_{b}}{S_{rated}}\left(\dfrac{V_{rated}}{V_b}\right)^2.

G:0.15 (same base)T1:0.06×90100×(1011)2=0.0446Line:Zb=145.2290=234.26 Ω,X=100234.26=0.4269T2:0.05×9090×(1012.70)2=0.0310M1:0.2×9050×(1012.70)2=0.2231M2:0.2×9040×(1012.70)2=0.2789\begin{aligned} G&: 0.15\ \text{(same base)}\\ T_1&: 0.06\times\frac{90}{100}\times\left(\frac{10}{11}\right)^2 = 0.0446\\ \text{Line}&: Z_b = \frac{145.2^2}{90} = 234.26\ \Omega,\quad X = \frac{100}{234.26} = 0.4269\\ T_2&: 0.05\times\frac{90}{90}\times\left(\frac{10}{12.70}\right)^2 = 0.0310\\ M_1&: 0.2\times\frac{90}{50}\times\left(\frac{10}{12.70}\right)^2 = 0.2231\\ M_2&: 0.2\times\frac{90}{40}\times\left(\frac{10}{12.70}\right)^2 = 0.2789 \end{aligned}

(T2 gives the same value on its HV side: 0.05×(114.32/145.2)2=0.03100.05\times(114.32/145.2)^2 = 0.0310.)

Elementp.u. reactance (90 MVA base)
Generatorj0.150
T1j0.0446
Linej0.4269
T2j0.0310
Motor M1j0.2231
Motor M2j0.2789

Reactance diagram

  j0.15    j0.0446   j0.4269   j0.031
 +-/\/\-----/\/\------/\/\-----/\/\---+-----+
 |                                     |     |
(Eg)                              j0.2231 j0.2789
 |                                     |     |
 |                                   (Em1) (Em2)
 +------------- reference --------------+-----+

The transformer winding connections (Y, Δ, earthing) do not change the positive-sequence p.u. reactances. They only introduce a phase shift, which is ignored in the reactance diagram.

  • 2080 Chaitra · 8 marks

What is the significance of reactance diagram? The single line diagram of a three phase power system is shown in the figure. Draw a reactance diagram considering a base of 100 MVA and 13.8 kV on generator side. G: 90 MVA, 13.8 kV, Xg = 18%; T1 = 50 MVA, 13.8/220 kV, XT1 = 10%; T2 = 50 MVA, 220/11 kV, XT2 = 10%; T3 = 50 MVA, 13.8/132 kV, XT3 = 10%; T4 = 50 MVA, 132/11 kV, XT4 = 10%; M: 80 MVA, 10.45 kV, Xm = 20%; Load: 57 MVA, 0.8 pf lagging at 10.45 kV; Xline1 = 50 Ω, Xline2 = 70 Ω. [Figure: generator G at bus 1 feeds two parallel paths to bus 4: T1 (bus 1–2) → Line-1 at 220 kV (bus 2–3) → T2 (bus 3–4); and T3 (bus 1–5) → Line-2 at 132 kV (bus 5–6) → T4 (bus 6–4). Motor M and the load are connected at bus 4.]

Answer

Significance of the reactance diagram

A reactance diagram is the per-phase equivalent circuit of the system, drawn from the single line diagram, in which:

  • resistances, magnetising branches and line charging are neglected
  • all values are in p.u. on a common base

It is used for short-circuit (fault) calculations and stability studies, where the reactances dominate. It gives a simple network that can be reduced quickly.

Base values

  • Sb=100S_b = 100 MVA, and Vb=13.8V_b = 13.8 kV at the generator (bus 1).
SectionBase kVZbZ_b (Ω)
Bus 1 (generator)13.8–
Line 1 (via T1 13.8/220)2202202/100=484220^2/100 = 484
Line 2 (via T3 13.8/132)1321322/100=174.24132^2/100 = 174.24
Bus 4 (via T2 220/11 or T4 132/11)11–

Both paths give 11 kV at bus 4, so the bases are consistent.

Per-unit values

XG=0.18×10090=0.2XT1=XT2=XT3=XT4=0.1×10050=0.2XL1=50484=0.1033XL2=70174.24=0.4017XM=0.2×10080×(10.4511)2=0.2256\begin{aligned} X_G &= 0.18\times\frac{100}{90} = 0.2\\ X_{T1} = X_{T2} = X_{T3} = X_{T4} &= 0.1\times\frac{100}{50} = 0.2\\ X_{L1} &= \frac{50}{484} = 0.1033\\ X_{L2} &= \frac{70}{174.24} = 0.4017\\ X_M &= 0.2\times\frac{100}{80}\times\left(\frac{10.45}{11}\right)^2 = 0.2256 \end{aligned}

Load: S=57/100=0.57S = 57/100 = 0.57 p.u. at a power factor of 0.8 lagging, and V=10.45/11=0.95V = 10.45/11 = 0.95 p.u. As a series impedance:

ZL=∣V∣2S∗=0.9520.57∠36.87∘=1.5833∠36.87∘=1.2667+j0.95 p.u.Z_L = \frac{|V|^2}{S^*} = \frac{0.95^2}{0.57}\angle36.87^\circ = 1.5833\angle36.87^\circ = 1.2667 + j0.95\ \text{p.u.}

Reactance diagram

               T1     L1      T2
          +--j0.2--j0.1033--j0.2--+
  j0.2    |                       |
 +-/\/\---+ bus1            bus4  +---+------+
 |        |                       |   |      |
(Eg)      +--j0.2--j0.4017--j0.2--+ j0.2256 1.2667
 |             T3     L2      T4     |   +j0.95
 |                                  (Em)  |
 +------------- reference -----------+----+
Elementp.u.
Gj0.2
T1, T2, T3, T4j0.2 each
Line 1j0.1033
Line 2j0.4017
Motorj0.2256
Load1.2667 + j0.95
  • 2079 Chaitra · 8 marks

Prepare an impedance diagram of the system shown in the figure below and show all impedances in per unit on a 100 MVA, 132 kV base in the transmission line circuit. [Figure: G1 (50 MVA, 13.8 kV, X = 0.15 p.u.) → T1 (80 MVA, Y-Y, 12.2/161 kV, Xt = 0.1 p.u.) → HV bus; from this bus a line of 40 + j160 Ω goes to the HV side of T2, and a parallel path of two sections 20 + j80 Ω and 20 + j80 Ω also joins the two buses, with a load of 50 MVA, cos φ = 0.8 lag, V = 154 kV tapped at the junction of the two sections; T2 (40 MVA, Y-Y, 161/13.8 kV, Xt2 = 0.1 p.u.) → G2 (20 MVA, 13.8 kV, X = 0.15 p.u.).]

Answer

Base values

  • Sb=100S_b = 100 MVA, and Vb=132V_b = 132 kV in the transmission circuit, so Zb=1322/100=174.24 ΩZ_b = 132^2/100 = 174.24\ \Omega.
  • G1 side, through T1 (12.2/161 kV): Vb=132×12.2161=10.0025V_b = 132\times\dfrac{12.2}{161} = 10.0025 kV.
  • G2 side, through T2 (161/13.8 kV): Vb=132×13.8161=11.3143V_b = 132\times\dfrac{13.8}{161} = 11.3143 kV.

Per-unit impedances

Use Znew=ZoldSbSrated(VratedVb)2Z_{new} = Z_{old}\dfrac{S_b}{S_{rated}}\left(\dfrac{V_{rated}}{V_b}\right)^2.

G1:0.15×10050(13.810.0025)2=j0.5710T1:0.1×10080(161132)2=j0.1860T2:0.1×10040(161132)2=j0.3719G2:0.15×10020(13.811.3143)2=j1.1157\begin{aligned} G_1&: 0.15\times\frac{100}{50}\left(\frac{13.8}{10.0025}\right)^2 = j0.5710\\ T_1&: 0.1\times\frac{100}{80}\left(\frac{161}{132}\right)^2 = j0.1860\\ T_2&: 0.1\times\frac{100}{40}\left(\frac{161}{132}\right)^2 = j0.3719\\ G_2&: 0.15\times\frac{100}{20}\left(\frac{13.8}{11.3143}\right)^2 = j1.1157 \end{aligned}

Lines:

Z40+j160=40+j160174.24=0.2296+j0.9183Z20+j80=20+j80174.24=0.1148+j0.4591 (each section)\begin{aligned} Z_{40+j160} &= \frac{40 + j160}{174.24} = 0.2296 + j0.9183\\ Z_{20+j80} &= \frac{20 + j80}{174.24} = 0.1148 + j0.4591\ \text{(each section)} \end{aligned}

Load (50 MVA, 0.8 lagging, 154 kV): V=154/132=1.1667V = 154/132 = 1.1667 p.u. and S=0.5S = 0.5 p.u.

ZL=∣V∣2S∗=1.166720.5∠36.87∘=2.7222∠36.87∘=2.1778+j1.6333 p.u.Z_L = \frac{|V|^2}{S^*} = \frac{1.1667^2}{0.5}\angle36.87^\circ = 2.7222\angle36.87^\circ = 2.1778 + j1.6333\ \text{p.u.}

Impedance diagram

 j0.571  j0.186      0.2296+j0.9183      j0.3719  j1.1157
+-/\/\----/\/\--+-------/\/\/\/\-------+--/\/\----/\/\--+
|               |                      |               |
(E1)            +-0.1148+j0.4591-+-0.1148+j0.4591-+   (E2)
|                                |                     |
|                        2.1778+j1.6333 (load)         |
|                                |                     |
+---------------- reference -----+---------------------+
Elementp.u. (100 MVA, 132 kV line base)
G1j0.5710
T1j0.1860
Line (40 + j160 Ω)0.2296 + j0.9183
Each section (20 + j80 Ω)0.1148 + j0.4591
Load2.1778 + j1.6333
T2j0.3719
G2j1.1157
  • 2078 Chaitra · 6 marks

Two three-phase machines have generated EMF of 11∠0° kV and 11∠40° kV. They are connected through a 3-phase line having an impedance of 0 + j15 Ω per phase. Find: (i) whether each machine is acting as generator or motor and the real power generated or consumed by them; (ii) whether each machine is delivering or consuming reactive power and the amount of reactive power.

Answer

Assumption: 11 kV is the line-to-line EMF. The per-phase EMFs are therefore E1=6.351∠0∘E_1 = 6.351\angle0^\circ kV and E2=6.351∠40∘E_2 = 6.351\angle40^\circ kV. The current II is taken as flowing from machine 1 to machine 2 through Z=j15 ΩZ = j15\ \Omega.

Current

I=E1−E2jX=6351∠0∘−6351∠40∘j15=289.6∠−160∘ A\begin{aligned} I &= \frac{E_1 - E_2}{jX} = \frac{6351\angle0^\circ - 6351\angle40^\circ}{j15}\\ &= 289.6\angle-160^\circ\ \text{A} \end{aligned}

Complex power (three-phase)

Machine 1, with power taken out of its terminal:

S1=3E1I∗=−5.185+j1.887 MVAS_1 = 3E_1I^* = -5.185 + j1.887\ \text{MVA}

Machine 2, with power taken into it (since II enters it):

S2=3E2I∗=−5.185−j1.887 MVAS_2 = 3E_2I^* = -5.185 - j1.887\ \text{MVA}

Check with the standard formulas:

P=E1E2sin⁡δX=11×11×sin⁡40∘15=5.185 MWQ=E2(1−cos⁡δ)X=121(1−cos⁡40∘)15=1.887 Mvar\begin{aligned} P &= \frac{E_1E_2\sin\delta}{X} = \frac{11\times11\times\sin40^\circ}{15} = 5.185\ \text{MW}\\ Q &= \frac{E^2(1-\cos\delta)}{X} = \frac{121(1-\cos40^\circ)}{15} = 1.887\ \text{Mvar} \end{aligned}

(i) Real power

  • Machine 1: P1=−5.185P_1 = -5.185 MW out of it, so it consumes 5.185 MW and acts as a motor.
  • Machine 2: P2,in=−5.185P_{2,in} = -5.185 MW, so it generates 5.185 MW and acts as a generator.

Machine 2's EMF leads by 40°, so real power flows from 2 to 1. The line is lossless (R=0R = 0), so the two powers are equal.

(ii) Reactive power

  • Machine 1: Q1=+1.887Q_1 = +1.887 Mvar out of it, so it delivers 1.887 Mvar.
  • Machine 2: Q2,in=−1.887Q_{2,in} = -1.887 Mvar, so it also delivers 1.887 Mvar.

Both machines supply reactive power to the line, which absorbs:

3∣I∣2X=3×289.62×15=3.774 Mvar3|I|^2X = 3\times289.6^2\times15 = 3.774\ \text{Mvar}

Answer: Machine 1 is a motor consuming 5.185 MW, and machine 2 is a generator producing 5.185 MW. Each machine supplies 1.887 Mvar, a total of 3.774 Mvar absorbed by the line reactance.

  • 2078 Chaitra · 10 marks

A 20 MVA, 11 kV three-phase synchronous generator has a sub-transient reactance of 10%. It is connected through three identical single-phase Δ-Y connected transformers of 5000 kVA, 11/127.02 kV with a reactance of 15% to a high voltage transmission line having a total series reactance of j180 Ω. At the end of the HT transmission line, three identical single-phase star/star connected transformers of 5000 kVA, 127.02/12.702 kV with a reactance of 20%. The load is drawing 15 MVA at 20 kV at 0.9 pf lagging. Draw a single line diagram of the network and determine the reactance diagram. Choose a common base of 15 kV and 25 MVA.

Answer

Single line diagram

  G         T1 (3 x 1-ph)     line       T2 (3 x 1-ph)
 (~)--||--[ D | Y ]----------j180----[ Y | Y ]----> Load
 20 MVA     5 MVA each                  5 MVA each   15 MVA
 11 kV      11/127.02 kV                127.02/      20 kV
 X"=10%     X=15%                       12.702 kV    0.9 lag
                                        X=20%

Transformer bank ratings

  • T1 (Δ–Y): 3×5=153\times5 = 15 MVA. Line voltages: 11 kV / 3×127.02=220\sqrt3\times127.02 = 220 kV.
  • T2 (Y–Y): 15 MVA, 220 kV / 3×12.702=22\sqrt3\times12.702 = 22 kV.

Base values

Assumption: the 15 kV base is taken in the generator circuit, with Sb=25S_b = 25 MVA.

SectionBase kVZbZ_b (Ω)
Generator159
Line15×220/11=30015\times220/11 = 3003002/25=3600300^2/25 = 3600
Load300×22/220=30300\times22/220 = 3036

Per-unit reactances

XG=0.10×2520(1115)2=0.0672XT1=0.15×2515(1115)2=0.1344Xline=1803600=0.05XT2=0.20×2515(220300)2=0.1793\begin{aligned} X_G &= 0.10\times\frac{25}{20}\left(\frac{11}{15}\right)^2 = 0.0672\\ X_{T1} &= 0.15\times\frac{25}{15}\left(\frac{11}{15}\right)^2 = 0.1344\\ X_{line} &= \frac{180}{3600} = 0.05\\ X_{T2} &= 0.20\times\frac{25}{15}\left(\frac{220}{300}\right)^2 = 0.1793 \end{aligned}

Load

15 MVA at 20 kV and 0.9 lagging: S=15/25=0.6S = 15/25 = 0.6 p.u., V=20/30=0.6667V = 20/30 = 0.6667 p.u.

S=0.6∠25.84∘=0.54+j0.2615 p.u.S = 0.6\angle25.84^\circ = 0.54 + j0.2615\ \text{p.u.}

As a series impedance:

ZL=∣V∣2S∗=0.666720.6∠25.84∘=0.7407∠25.84∘=0.6667+j0.3229 p.u.Z_L = \frac{|V|^2}{S^*} = \frac{0.6667^2}{0.6}\angle25.84^\circ = 0.7407\angle25.84^\circ = 0.6667 + j0.3229\ \text{p.u.}

Reactance diagram

  j0.0672   j0.1344    j0.05    j0.1793
 +-/\/\------/\/\------/\/\------/\/\----+
 |                                       |
(Eg)                              0.6667 + j0.3229
 |                                     (load)
 +----------------- reference -----------+
Elementp.u. (25 MVA, 15 kV gen base)
Generatorj0.0672
T1j0.1344
Linej0.0500
T2j0.1793
Load0.6667 + j0.3229 (0.54 + j0.2615 p.u. power)
  • 2077 Chaitra · 4 marks

What do you mean by single line diagram? Write its significance in power system analysis.

Answer

A single line diagram (SLD), or one-line diagram, shows a balanced three-phase power system using one line to represent all three phases. Standard symbols show the generators, transformers, lines, breakers, buses and loads, together with their ratings and connections.

Typical SLD

  G1                                  M
 (~)--[x]--8|8--+===== line =====+--8|8--[x]--(M)
       CB   T1  |                |   T2
               Bus 1           Bus 2
                |                |
               Load            Load
  (~) generator   8|8 transformer   [x] breaker

Information shown

  • Ratings: MVA, kV and % reactance of machines and transformers
  • Transformer winding connections (Y, Δ) and neutral earthing
  • Line impedances, buses, and the location of breakers, CTs and PTs
  • The points where loads and generators connect

Significance in power system analysis

  1. Simplicity: A balanced three-phase system is solved on a per-phase basis, so one line gives all the needed information without clutter.
  2. Starting point for analysis: The impedance and reactance diagrams, the bus admittance matrix, load flow, fault studies and stability studies are all built from the SLD.
  3. Planning and operation: It shows the system layout clearly to planners, operators and protection engineers.
  4. Protection coordination: It shows the locations of breakers and relays and the fault paths.
  5. Data in one place: All the ratings needed for p.u. calculation are on one drawing.

A simple example is a generator, a step-up transformer, a transmission line, a step-down transformer and a load in series, each shown by its symbol and rating.

  • 2077 Chaitra · 8 marks

Draw the reactance diagram with all values in p.u. on a base of 30 MVA, 6.6 kV in the circuit of generator G1. Required data are as follows: G1: 25 MVA, 6.6 kV, j0.2 p.u.; G2: 15 MVA, 6.6 kV, j0.15 p.u.; G3: 30 MVA, 13.2 kV, j0.15 p.u.; T1: 30 MVA, 6.6 (delta) kV/115 (star) kV, j0.1 p.u.; T2: 15 MVA, 6.6 (delta) kV/115 (star) kV, j0.1 p.u.; T3: single phase units each rated 10 MVA, 69/6.9 kV, j0.1 p.u. [Figure: G1 (Y, grounded) → T1 (Δ–Y grounded) → line j120 Ω → junction bus; from the junction, T2 (Y grounded on HV side, Δ on LV side) up to G2 (Y, grounded); and a line j90 Ω → T3 (Y–Y, grounded) → G3 (Y, grounded).]

Answer

Base values

  • Sb=30S_b = 30 MVA, and Vb=6.6V_b = 6.6 kV in the G1 circuit.
  • Line section (through T1, 6.6/115 kV): Vb=115V_b = 115 kV, so Zb=1152/30=440.83 ΩZ_b = 115^2/30 = 440.83\ \Omega.
  • G2 circuit (through T2, 115/6.6 kV): Vb=6.6V_b = 6.6 kV.
  • T3 is a Y–Y bank of single-phase 69/6.9 kV units. Its line ratio is 3×69=119.5\sqrt3\times69 = 119.5 kV / 3×6.9=11.95\sqrt3\times6.9 = 11.95 kV, and its rating is 3×10=303\times10 = 30 MVA.
  • G3 circuit: Vb=115×11.95119.5=11.5V_b = 115\times\dfrac{11.95}{119.5} = 11.5 kV.

Per-unit reactances

G1:0.2×3025=0.24G2:0.15×3015=0.30G3:0.15×3030(13.211.5)2=0.1976T1:0.1×3030=0.10T2:0.1×3015=0.20T3:0.1×3030(119.5115)2=0.1080Line j120:120440.83=0.2722Line j90:90440.83=0.2042\begin{aligned} G_1&: 0.2\times\frac{30}{25} = 0.24\\ G_2&: 0.15\times\frac{30}{15} = 0.30\\ G_3&: 0.15\times\frac{30}{30}\left(\frac{13.2}{11.5}\right)^2 = 0.1976\\ T_1&: 0.1\times\frac{30}{30} = 0.10\\ T_2&: 0.1\times\frac{30}{15} = 0.20\\ T_3&: 0.1\times\frac{30}{30}\left(\frac{119.5}{115}\right)^2 = 0.1080\\ \text{Line } j120&: \frac{120}{440.83} = 0.2722\\ \text{Line } j90&: \frac{90}{440.83} = 0.2042 \end{aligned}
Elementp.u. (30 MVA base)
G1j0.24
T1j0.10
Line (j120 Ω)j0.2722
T2j0.20
G2j0.30
Line (j90 Ω)j0.2042
T3j0.108
G3j0.1976

Reactance diagram

 j0.24  j0.10   j0.2722        j0.2042  j0.108  j0.1976
+-/\/\--/\/\----/\/\----+(J)+---/\/\----/\/\----/\/\--+
|                        |                            |
(E1)                   j0.20 (T2)                   (E3)
|                        |                            |
|                      j0.30 (G2)                     |
|                        |                            |
|                      (E2)                           |
+------------------- reference -----------------------+

Here J is the junction bus. Winding connections and earthing do not affect these positive-sequence reactances.

  • 2076 Baisakh · 10 marks

Draw the reactance diagram of the following figure with its equivalent per unit system. Take base MVA = 100 MVA and base voltage = 11 kV for generator. Compute the reactance diagram. [Figure: G1 → T1 and G2 → T2 feed a common 220 kV bus at the sending side; Line-1 and Line-2 run in parallel from there to a receiving bus, which feeds G3 through T3. Data: G1 100 MVA, 11 kV, X = 25%; G2 100 MVA, 11 kV, X = 20%; G3 100 MVA, 11 kV, X = 20%; T1 100 MVA, 11/220 kV, X = 6%; T2 100 MVA, 11/220 kV, X = 7%; T3 100 MVA, 220/11 kV, X = 7%; Line-1 100 MVA, 220 kV, X = 10%; Line-2 100 MVA, 220 kV, X = 10%.]

Answer

Base values

  • Sb=100S_b = 100 MVA, and Vb=11V_b = 11 kV in the generator circuits.
  • Line section (through 11/220 kV transformers): Vb=220V_b = 220 kV, so Zb=2202/100=484 ΩZ_b = 220^2/100 = 484\ \Omega.
  • G3 circuit (through T3, 220/11 kV): Vb=11V_b = 11 kV.

Conversion to the common base

Xpu,new=Xpu,old×Sb,newSb,old×(Vb,oldVb,new)2X_{pu,new} = X_{pu,old}\times\frac{S_{b,new}}{S_{b,old}}\times\left(\frac{V_{b,old}}{V_{b,new}}\right)^2

Every component is rated at 100 MVA, and its rated voltage equals the base voltage of its section. Both correction factors are therefore 1, and each p.u. value equals its percentage reactance divided by 100.

ElementRatingCalculationp.u. reactance
G1100 MVA, 11 kV, 25 %0.25×1×10.25\times1\times1j0.25
G2100 MVA, 11 kV, 20 %0.20×1×10.20\times1\times1j0.20
G3100 MVA, 11 kV, 20 %0.20×1×10.20\times1\times1j0.20
T1100 MVA, 11/220 kV, 6 %0.06×1×10.06\times1\times1j0.06
T2100 MVA, 11/220 kV, 7 %0.07×1×10.07\times1\times1j0.07
T3100 MVA, 220/11 kV, 7 %0.07×1×10.07\times1\times1j0.07
Line 1100 MVA, 220 kV, 10 %0.10×1×10.10\times1\times1j0.10
Line 2100 MVA, 220 kV, 10 %0.10×1×10.10\times1\times1j0.10

In ohms, each line is 0.10×484=48.4 Ω0.10\times484 = 48.4\ \Omega.

Reactance diagram

 j0.25  j0.06          j0.10 (L1)
+-/\/\--/\/\--+------+--/\/\--+------+ j0.07  j0.20
|             |      |        |      +--/\/\--/\/\--+
(E1)          |      +--/\/\--+                     |
|             |        j0.10 (L2)                  (E3)
|  j0.20 j0.07|                                     |
+-/\/\--/\/\--+                                     |
|                                                   |
(E2)                                                |
+----------------------- reference -----------------+

Simplified values (useful for fault studies)

  • The two lines in parallel: j0.10 ∥ j0.10=j0.05j0.10\,\|\,j0.10 = j0.05.
  • G1–T1 branch: j0.31j0.31. G2–T2 branch: j0.27j0.27.
  • These two branches in parallel: 0.31×0.270.58=j0.1443\dfrac{0.31\times0.27}{0.58} = j0.1443.
  • G3–T3 branch: j0.27j0.27.
  • 2076 Bhadra · 10 marks

A 300 MVA, 20 kV three-phase generator has a sub-transient reactance of 20%. The generator supplies two synchronous motors over a 65 kilometre line having transformers at both ends, as shown on the single line diagram. The neutral of one of the motors M1 is grounded while M2 is ungrounded. Rated inputs to the motors are 200 MVA at 13.2 kV and 100 MVA at 13.2 kV for M1 and M2 respectively. For both motors X"d = 20%. The three phase transformer T1 is rated 350 MVA, 230/20 kV with leakage reactance of 10%. Transformer T2 is composed of three single phase transformers, each rated 127/13.2 kV, 100 MVA with leakage reactance of 10%. Series reactance of the transmission line is 0.8 ohm/km. Draw the reactance diagram with all the reactances marked in p.u. Select the generator rating as base in the generator circuit. [Figure: G (Y, neutral grounded through an impedance) → T1 (Δ on generator side, Y grounded on line side) → transmission line TL → T2 (Y grounded on line side, Δ on motor side) → motors M1 (Y, grounded) and M2 (Y, ungrounded).]

Answer

In a per-unit reactance diagram every element is expressed on one common MVA base, and the base voltage changes from zone to zone in the ratio of the transformer line-to-line voltages. Resistances, magnetising branches and the grounding impedances are neglected (they carry no current under balanced conditions).

Step 1: Base values in each zone

  • Base MVA (all zones): Sb=300S_b = 300 MVA
  • Generator zone: Vb1=20V_{b1} = 20 kV (given)
  • Line zone (T1 is 20/230 kV): Vb2=20×23020=230V_{b2} = 20 \times \frac{230}{20} = 230 kV
  • T2 is a Y–Δ bank of single-phase units 127/13.2 kV, so its line-to-line ratio is 3×127/13.2=220/13.2\sqrt{3}\times127 / 13.2 = 220/13.2 kV. Motor zone:
Vb3=230×13.2220=13.8 kVV_{b3} = 230 \times \frac{13.2}{220} = 13.8\ \text{kV} Zb,line=Vb22Sb=2302300=176.33 ΩZ_{b,\text{line}} = \frac{V_{b2}^2}{S_b} = \frac{230^2}{300} = 176.33\ \Omega

Step 2: Change of base

Xpu,new=Xpu,old×Sb,newSb,old×(VoldVb,new)2X_{pu,new} = X_{pu,old}\times\frac{S_{b,new}}{S_{b,old}}\times\left(\frac{V_{old}}{V_{b,new}}\right)^2

Step 3: Per-unit reactances

XG=0.20 pu (already on its own rating)XT1=0.10×300350=0.0857 puXline=0.8×65176.33=52176.33=0.2949 puXT2=0.10×300300×(13.213.8)2=0.0915 puXM1=0.20×300200×(13.213.8)2=0.2744 puXM2=0.20×300100×(13.213.8)2=0.5488 pu\begin{aligned} X_G &= 0.20\ \text{pu (already on its own rating)}\\ X_{T1} &= 0.10\times\frac{300}{350} = 0.0857\ \text{pu}\\ X_{line} &= \frac{0.8\times 65}{176.33} = \frac{52}{176.33} = 0.2949\ \text{pu}\\ X_{T2} &= 0.10\times\frac{300}{300}\times\left(\frac{13.2}{13.8}\right)^2 = 0.0915\ \text{pu}\\ X_{M1} &= 0.20\times\frac{300}{200}\times\left(\frac{13.2}{13.8}\right)^2 = 0.2744\ \text{pu}\\ X_{M2} &= 0.20\times\frac{300}{100}\times\left(\frac{13.2}{13.8}\right)^2 = 0.5488\ \text{pu} \end{aligned}

(The three-phase rating of T2 is 3×100=3003\times100 = 300 MVA.)

ElementRating usedX (pu on 300 MVA)
Generator G300 MVA, 20 kV0.2000
T1350 MVA, 20/230 kV0.0857
Line52 Ω, base 176.33 Ω0.2949
T2300 MVA, 220/13.2 kV0.0915
Motor M1200 MVA, 13.2 kV0.2744
Motor M2100 MVA, 13.2 kV0.5488

Step 4: Reactance diagram

     j0.0857   j0.2949   j0.0915
 +---/\/\/-----/\/\/-----/\/\/---+--------+
 |    T1        line       T2    |        |
j0.2                          j0.2744  j0.5488
 |                               |        |
(Eg)                           (Em1)    (Em2)
 |                               |        |
 +-------------------------------+--------+
            reference (neutral) bus

Answer: On 300 MVA base, XG=0.2X_G = 0.2, XT1=0.0857X_{T1} = 0.0857, Xline=0.2949X_{line} = 0.2949, XT2=0.0915X_{T2} = 0.0915, XM1=0.2744X_{M1} = 0.2744 and XM2=0.5488X_{M2} = 0.5488 pu, with base voltages 20 kV, 230 kV and 13.8 kV in the three zones.

  • 2075 Baisakh · 6 marks

Draw the reactance diagram using a base of 50 MVA and 13.8 kV on generator G1 of a given single line diagram of a power system. The ratings of the generators and transformers are given below: G1: 20 MVA, 13.8 kV, X" = 20%; G2: 30 MVA, 18 kV, X" = 20%; G3: 30 MVA, 20 kV, X" = 20%; T1: 25 MVA, 220/13.8 kV, X = 10%; T2: 3 single phase units each rated 10 MVA, 127/18 kV, X = 10%; T3: 35 MVA, 220/22 kV, X = 10%. [Figure: G1 (Y, grounded) → T1 (Δ on generator side, Y grounded on HV side) → line Section 1, j80 Ω [?] → central bus; from the central bus T2 (Y on HV side, Δ on LV side) → G2; and line Section 2, j100 Ω → T3 (Y grounded on HV side, Δ on LV side) → G3.]

Answer

All reactances are converted to a common base of 50 MVA; base voltages follow the transformer line-to-line ratios starting from 13.8 kV at G1.

Base values

  • G1 zone: Vb=13.8V_b = 13.8 kV
  • Line zone (T1 13.8/220 kV): Vb=220V_b = 220 kV, Zb=220250=968 ΩZ_b = \frac{220^2}{50} = 968\ \Omega
  • G2 zone: T2 is a Y–Δ bank of 127/18 kV units, line-to-line ratio 3×127/18=220/18\sqrt{3}\times127/18 = 220/18 kV, so Vb=220×18220=18V_b = 220\times\frac{18}{220} = 18 kV
  • G3 zone (T3 220/22 kV): Vb=22V_b = 22 kV

Formula: Xnew=Xold Sb,newSold(VoldVb,new)2X_{new} = X_{old}\,\frac{S_{b,new}}{S_{old}}\left(\frac{V_{old}}{V_{b,new}}\right)^2

Per-unit values

XG1=0.2×5020=0.5 puXG2=0.2×5030×(1818)2=0.3333 puXG3=0.2×5030×(2022)2=0.2755 puXT1=0.1×5025=0.2 puXT2=0.1×503×10=0.1667 puXT3=0.1×5035=0.1429 puXL1=80968=0.0826 puXL2=100968=0.1033 pu\begin{aligned} X_{G1} &= 0.2\times\frac{50}{20} = 0.5\ \text{pu}\\ X_{G2} &= 0.2\times\frac{50}{30}\times\left(\frac{18}{18}\right)^2 = 0.3333\ \text{pu}\\ X_{G3} &= 0.2\times\frac{50}{30}\times\left(\frac{20}{22}\right)^2 = 0.2755\ \text{pu}\\ X_{T1} &= 0.1\times\frac{50}{25} = 0.2\ \text{pu}\\ X_{T2} &= 0.1\times\frac{50}{3\times10} = 0.1667\ \text{pu}\\ X_{T3} &= 0.1\times\frac{50}{35} = 0.1429\ \text{pu}\\ X_{L1} &= \frac{80}{968} = 0.0826\ \text{pu}\\ X_{L2} &= \frac{100}{968} = 0.1033\ \text{pu} \end{aligned}
ElementX (pu, 50 MVA base)
G10.5000
G20.3333
G30.2755
T10.2000
T20.1667
T30.1429
Line section 1 (j80 Ω)0.0826
Line section 2 (j100 Ω)0.1033

Reactance diagram

   j0.2   j0.0826        j0.1033   j0.1429
 +-/\/\/--/\/\/---+------/\/\/------/\/\/--+
 |  T1     L1     |        L2         T3   |
j0.5           j0.1667 (T2)              j0.2755
 |                |                        |
(E1)           j0.3333                   (E3)
 |                |                        |
 |              (E2)                       |
 |                |                        |
 +----------------+------------------------+
            reference (neutral) bus

Answer: XG1=0.5X_{G1}=0.5, XG2=0.333X_{G2}=0.333, XG3=0.276X_{G3}=0.276, XT1=0.2X_{T1}=0.2, XT2=0.167X_{T2}=0.167, XT3=0.143X_{T3}=0.143, XL1=0.0826X_{L1}=0.0826 and XL2=0.1033X_{L2}=0.1033 pu on 50 MVA, with base voltages 13.8, 220, 18 and 22 kV.

  • 2075 Baisakh · 4 marks

A single phase voltage source with V = 100∠0° volts delivers a current I = 10∠10° A, which leaves the positive terminal of the source. Calculate the source real and reactive power and state whether the source delivers or absorbs each of these.

Answer

Complex power delivered by a source whose current leaves its positive terminal is S=VI∗S = VI^* (generator convention). A positive P or Q then means the source delivers it; a negative value means it absorbs it.

S=VI∗=(100∠0∘)(10∠−10∘)=1000∠−10∘ VA=1000cos⁡10∘−j 1000sin⁡10∘=984.81−j 173.65 VA\begin{aligned} S &= VI^* = (100\angle0^\circ)(10\angle-10^\circ)\\ &= 1000\angle-10^\circ\ \text{VA}\\ &= 1000\cos10^\circ - j\,1000\sin10^\circ\\ &= 984.81 - j\,173.65\ \text{VA} \end{aligned}
  • P=+984.81P = +984.81 W: positive, so the source delivers real power.
  • Q=−173.65Q = -173.65 var: negative, so the source absorbs 173.65 var (equivalently it delivers −173.65-173.65 var).

The current leads the voltage by 10°, so the load connected to the source is capacitive; a capacitive load supplies reactive power, which flows back into the source.

Answer: P = 984.8 W delivered; Q = 173.6 var absorbed by the source.

  • 2075 Bhadra · 8 marks

A 90 MVA, 11 kV 3-phase generator has a reactance of 25%. The generator supplies two motors through transformers and transmission line shown in figure below. The transformer T1 is a 3-phase, 100 MVA, 10/132 kV, 6% reactance. The transformer T2 is composed of three single phase units each rated at 30 MVA, 66/10 kV with 5% reactance. The connection of T1 and T2 are shown in figure. The motors are rated at 50 MVA and 40 MVA, both 10 kV and 20% reactance. Taking the generator rating as base, draw the per unit reactance diagram. The reactance of the line is 100 Ω. [Figure: G1 → T1 (Δ on generator side, Y grounded on line side) → Line → T2 (Y grounded on line side, Δ on motor side) → bus feeding M1 (Y, grounded) and M2 (Δ).]

Answer

Base: 90 MVA and 11 kV in the generator circuit (generator rating). Base voltages in other zones follow the line-to-line turns ratios.

Base voltages

  • Generator zone: Vb1=11V_{b1} = 11 kV
  • Line zone (T1 is 10/132 kV): Vb2=11×13210=145.2V_{b2} = 11\times\frac{132}{10} = 145.2 kV
  • T2: three single-phase 66/10 kV units connected Y (line side) – Δ (motor side), so line-to-line ratio is 663/10=114.32/1066\sqrt{3}/10 = 114.32/10 kV. Motor zone:
Vb3=145.2×10114.32=12.70 kVV_{b3} = 145.2\times\frac{10}{114.32} = 12.70\ \text{kV} Zb2=145.2290=234.26 ΩZ_{b2} = \frac{145.2^2}{90} = 234.26\ \Omega

Per-unit reactances (on 90 MVA)

XG=0.25 puXT1=0.06×90100×(1011)2=0.0446 puXline=100234.26=0.4269 puXT2=0.05×903×30×(1012.70)2=0.0310 puXM1=0.2×9050×(1012.70)2=0.2231 puXM2=0.2×9040×(1012.70)2=0.2789 pu\begin{aligned} X_G &= 0.25\ \text{pu}\\ X_{T1} &= 0.06\times\frac{90}{100}\times\left(\frac{10}{11}\right)^2 = 0.0446\ \text{pu}\\ X_{line} &= \frac{100}{234.26} = 0.4269\ \text{pu}\\ X_{T2} &= 0.05\times\frac{90}{3\times30}\times\left(\frac{10}{12.70}\right)^2 = 0.0310\ \text{pu}\\ X_{M1} &= 0.2\times\frac{90}{50}\times\left(\frac{10}{12.70}\right)^2 = 0.2231\ \text{pu}\\ X_{M2} &= 0.2\times\frac{90}{40}\times\left(\frac{10}{12.70}\right)^2 = 0.2789\ \text{pu} \end{aligned}
ElementX (pu, 90 MVA base)
Generator0.2500
T10.0446
Line (100 Ω)0.4269
T20.0310
Motor M10.2231
Motor M20.2789

Reactance diagram

     j0.0446   j0.4269   j0.0310
 +---/\/\/-----/\/\/-----/\/\/---+--------+
 |    T1        line       T2    |        |
j0.25                         j0.2231  j0.2789
 |                               |        |
(Eg)                           (Em1)    (Em2)
 |                               |        |
 +-------------------------------+--------+
            reference bus

Answer: On 90 MVA base: XG=0.25X_G = 0.25, XT1=0.0446X_{T1} = 0.0446, Xline=0.4269X_{line} = 0.4269, XT2=0.0310X_{T2} = 0.0310, XM1=0.2231X_{M1} = 0.2231, XM2=0.2789X_{M2} = 0.2789 pu; base voltages 11 kV, 145.2 kV and 12.70 kV.

  • 2074 Bhadra · 6 marks

Two ideal voltage sources designated as machine 1 and 2 are connected as shown in figure below. If E1 = 100∠0° V and E2 = ∠30° V and Z = 0.5 + j5 Ω, determine (i) whether each machine is generating or consuming real power and the amount, (ii) whether each machine is receiving or supplying reactive power and the amount, and (iii) the P and Q absorbed by the impedance. [Figure: source E1 on the left and source E2 on the right, connected through series impedance Z = 0.5 + j5 Ω; current I flows from E1 towards E2.]

Answer

The magnitude of E2E_2 is not printed; it is taken as 100 V, i.e. E2=100∠30∘E_2 = 100\angle30^\circ V (the usual textbook data).

Current I flows from machine 1 to machine 2. With this direction:

  • S1=E1I∗S_1 = E_1 I^* is the power supplied by machine 1 (current leaves its + terminal).
  • S2=E2I∗S_2 = E_2 I^* is the power absorbed by machine 2 (current enters its + terminal).

Current

E1−E2=100−(86.60+j50)=13.40−j50I=13.40−j500.5+j5=10.30∠−159.29∘ A=−9.635−j3.643 A\begin{aligned} E_1 - E_2 &= 100 - (86.60 + j50) = 13.40 - j50\\ I &= \frac{13.40 - j50}{0.5 + j5} = 10.30\angle-159.29^\circ\ \text{A}\\ &= -9.635 - j3.643\ \text{A} \end{aligned}

(i) and (ii) Machine powers

S1=E1I∗=100(−9.635+j3.643)=−963.57+j364.31 VAS2=E2I∗=−1016.63−j166.29 VA\begin{aligned} S_1 &= E_1I^* = 100(-9.635 + j3.643) = -963.57 + j364.31\ \text{VA}\\ S_2 &= E_2I^* = -1016.63 - j166.29\ \text{VA} \end{aligned}
MachinePQ
1 (S1S_1 = supplied)P1=−963.57P_1 = -963.57 W, so it consumes 963.57 W (motor)Q1=+364.31Q_1 = +364.31 var, so it supplies 364.31 var
2 (S2S_2 = absorbed)P2=−1016.63P_2 = -1016.63 W absorbed, so it generates 1016.63 WQ2=−166.29Q_2 = -166.29 var absorbed, so it supplies 166.29 var

(iii) Power absorbed by the impedance

∣I∣2=10.302=106.12SZ=∣I∣2Z=106.12(0.5+j5)=53.06+j530.59 VA\begin{aligned} |I|^2 &= 10.30^2 = 106.12\\ S_Z &= |I|^2 Z = 106.12(0.5 + j5) = 53.06 + j530.59\ \text{VA} \end{aligned}

Check: P: 1016.63−963.57=53.061016.63 - 963.57 = 53.06 W. Q: 364.31+166.29=530.6364.31 + 166.29 = 530.6 var. Both balance.

Real power flows from machine 2 to machine 1 because E2E_2 leads E1E_1. Both machines supply reactive power, and all of it is used up in the line reactance.

Answer: Machine 1 consumes 963.6 W and supplies 364.3 var. Machine 2 generates 1016.6 W and supplies 166.3 var. The impedance absorbs 53.1 W and 530.6 var.

  • 2074 Bhadra · 8 marks

A one-line diagram of a three-phase power system is shown in figure below. Compute the per unit values taking generator rating as the base in the generator circuit and draw the impedance diagram of the power system shown in figure below. The system has the following data: G1: 25 MVA, 13.8 kV, X = 0.15 p.u.; T1: 30 MVA, 13.2/115 kV, X = 0.11 p.u.; T2: Three single units each rated 10 MVA, 69Y/13.2Δ kV, X = 0.11 p.u.; M1: 15 MVA, 13 kV, X = 0.15 p.u.; M2: 10 MVA, 13 kV, X = 0.15 p.u.; Series impedance of transmission line: Z = 20 + j65 Ω. [Figure: G1 → T1 (Δ on generator side, Y grounded on line side) → transmission line → T2 (Y grounded on line side, Δ on motor side) → bus feeding motors M1 (Y, grounded) and M2 (Y, grounded).]

Answer

Base: 25 MVA and 13.8 kV in the generator circuit. T2 is read as three single-phase units of 69/13.2 kV connected Y (line side) – Δ (motor side).

Base voltages

  • Generator zone: Vb1=13.8V_{b1} = 13.8 kV
  • Line zone (T1 13.2/115 kV): Vb2=13.8×11513.2=120.23V_{b2} = 13.8\times\frac{115}{13.2} = 120.23 kV
  • T2 line-to-line ratio: 693/13.2=119.51/13.269\sqrt{3}/13.2 = 119.51/13.2 kV. Motor zone: Vb3=120.23×13.2119.51=13.28V_{b3} = 120.23\times\frac{13.2}{119.51} = 13.28 kV
Zb2=120.23225=578.18 ΩZ_{b2} = \frac{120.23^2}{25} = 578.18\ \Omega

Per-unit values (25 MVA base)

XG1=0.15 puXT1=0.11×2530×(13.213.8)2=0.0839 puZline=20+j65578.18=0.0346+j0.1124 puXT2=0.11×2530×(13.213.28)2=0.0906 puXM1=0.15×2515×(1313.28)2=0.2396 puXM2=0.15×2510×(1313.28)2=0.3594 pu\begin{aligned} X_{G1} &= 0.15\ \text{pu}\\ X_{T1} &= 0.11\times\frac{25}{30}\times\left(\frac{13.2}{13.8}\right)^2 = 0.0839\ \text{pu}\\ Z_{line} &= \frac{20 + j65}{578.18} = 0.0346 + j0.1124\ \text{pu}\\ X_{T2} &= 0.11\times\frac{25}{30}\times\left(\frac{13.2}{13.28}\right)^2 = 0.0906\ \text{pu}\\ X_{M1} &= 0.15\times\frac{25}{15}\times\left(\frac{13}{13.28}\right)^2 = 0.2396\ \text{pu}\\ X_{M2} &= 0.15\times\frac{25}{10}\times\left(\frac{13}{13.28}\right)^2 = 0.3594\ \text{pu} \end{aligned}
ElementBase kVpu value
G113.8j0.15
T113.8j0.0839
Line120.230.0346 + j0.1124
T2 (30 MVA bank)13.28j0.0906
M113.28j0.2396
M213.28j0.3594

Impedance diagram

    j0.0839  0.0346+j0.1124  j0.0906
 +--/\/\/-------/\/\/--------/\/\/--+-------+
 |   T1          line          T2   |       |
j0.15                          j0.2396  j0.3594
 |                                  |       |
(Eg)                             (Em1)   (Em2)
 |                                  |       |
 +----------------------------------+-------+
              reference bus

Answer: XG1=0.15X_{G1}=0.15, XT1=0.0839X_{T1}=0.0839, Zline=0.0346+j0.1124Z_{line}=0.0346+j0.1124, XT2=0.0906X_{T2}=0.0906, XM1=0.2396X_{M1}=0.2396, XM2=0.3594X_{M2}=0.3594 pu (25 MVA; 13.8 / 120.23 / 13.28 kV).

  • 2073 Bhadra · 4 marks

Define the meaning of complex power in power system. Explain the sign conventions of power for sources and loads.

Answer

Complex power is the phasor product of voltage and the conjugate of current. Its real part is the active power and its imaginary part is the reactive power:

S=VI∗=∣V∣∣I∣∠(θv−θi)=P+jQS = VI^* = |V||I|\angle(\theta_v - \theta_i) = P + jQ
  • P=∣V∣∣I∣cos⁡ϕP = |V||I|\cos\phi (W), the average power converted to work or heat.
  • Q=∣V∣∣I∣sin⁡ϕQ = |V||I|\sin\phi (var), the power that oscillates between source and the fields of L and C.
  • ∣S∣=P2+Q2|S| = \sqrt{P^2+Q^2} (VA), the apparent power. Equipment is rated in VA.
  • ϕ=θv−θi\phi = \theta_v - \theta_i is the power-factor angle. Q is positive for a lagging (inductive) current.

Sign conventions

Load (motor) convention: the current enters the positive terminal. S=VI∗S = VI^* is then the power absorbed.

  • P > 0: the element absorbs real power (resistor, motor).
  • Q > 0: it absorbs reactive power (inductor, lagging load).
  • Q < 0: it supplies reactive power (capacitor).

Source (generator) convention: the current leaves the positive terminal. S=VI∗S = VI^* is then the power delivered.

  • P > 0: the source delivers real power (generator action). P < 0 means it absorbs P (motor action).
  • Q > 0: it delivers reactive power (over-excited machine). Q < 0 means it absorbs Q.
 Load convention          Source convention
   I -->  +                 +  --> I
   +------o                 o------+
   | Load |  S absorbed     | Src  |  S delivered
   +------o                 o------+
          -                 -
ElementPQ (load convention)
Resistor+0
Inductor0+ (absorbs)
Capacitor0− (supplies)
Induction motor++

Example: V=100∠0∘V = 100\angle0^\circ V and the current leaving the + terminal is I=5∠−30∘I = 5\angle-30^\circ A. Then S=500∠30∘=433+j250S = 500\angle30^\circ = 433 + j250 VA, so the source delivers 433 W and 250 var.

  • 2073 Bhadra · 10 marks

Develop the reactance diagram of the following network and express all the parameters in p.u. values based on power 1000 kVA and base voltage of 11 kV at low voltage side: G1: 1000 kVA, 11 kV, X = 2.5%; G2: 500 kVA, 11 kV, X = 0.1%; Tr-1: 1000 kVA, 11 kV/66 kV, X = 2%; Tr-2: 500 kVA, 12.5 kV/75 kV, X = 2%; Tr-3: 1500 kVA, 66 kV/400 kV, X = 2%; TL: 10 Ω/phase. If the load draws a current of 1200 A, calculate the current supplied by G1 and G2.

Answer

No figure is printed, so the usual arrangement is assumed: G1–Tr1 and G2–Tr2 feed a common 66 kV bus; from it the line TL and Tr3 (66/400 kV) supply the load. The two generator emfs are taken as equal, so the load current divides between the two generator branches in inverse ratio of their impedances. The 1200 A load current is taken as referred to the 11 kV level, since its voltage level is not stated.

 G1--Tr1(11/66)--+
                 |66 kV bus
 G2--Tr2(12.5/75)+--TL(10 ohm)--Tr3(66/400)--Load

Base values (SbS_b = 1000 kVA)

  • G1 side: 11 kV (given). 66 kV bus: 11×6611=6611\times\frac{66}{11} = 66 kV.
  • G2 side through Tr2: 66×12.575=1166\times\frac{12.5}{75} = 11 kV.
  • Load side: 66×40066=40066\times\frac{400}{66} = 400 kV.
  • ZbZ_b at 66 kV =6621=4356 Ω= \frac{66^2}{1} = 4356\ \Omega. IbI_b at 11 kV =10003×11=52.49= \frac{1000}{\sqrt3\times11} = 52.49 A.

Per-unit reactances

XG1=0.025 puXG2=0.001×1000500×(1111)2=0.002 puXTr1=0.02 puXTr2=0.02×1000500×(12.511)2=0.0517 puXTL=104356=0.0023 puXTr3=0.02×10001500=0.0133 pu\begin{aligned} X_{G1} &= 0.025\ \text{pu}\\ X_{G2} &= 0.001\times\frac{1000}{500}\times\left(\frac{11}{11}\right)^2 = 0.002\ \text{pu}\\ X_{Tr1} &= 0.02\ \text{pu}\\ X_{Tr2} &= 0.02\times\frac{1000}{500}\times\left(\frac{12.5}{11}\right)^2 = 0.0517\ \text{pu}\\ X_{TL} &= \frac{10}{4356} = 0.0023\ \text{pu}\\ X_{Tr3} &= 0.02\times\frac{1000}{1500} = 0.0133\ \text{pu} \end{aligned}
ElementX (pu, 1000 kVA)
G10.0250
G20.0020
Tr-10.0200
Tr-20.0517
TL0.0023
Tr-30.0133

Reactance diagram

 j0.025  j0.02
+-/\/\/--/\/\/--+
|  G1     Tr1   |   j0.0023  j0.0133
(E1)            +---/\/\/----/\/\/---> Load
|  G2     Tr2   |     TL      Tr3
+-/\/\/--/\/\/--+
 j0.002  j0.0517
(E1, E2 return to the common reference bus)

Current shared by G1 and G2

Branch impedances: Z1=0.025+0.02=0.045Z_1 = 0.025 + 0.02 = 0.045 pu and Z2=0.002+0.0517=0.0537Z_2 = 0.002 + 0.0517 = 0.0537 pu.

IG1=ILZ2Z1+Z2=1200×0.05370.0987=1200×0.5439=652.6 AIG2=ILZ1Z1+Z2=1200×0.4561=547.4 A\begin{aligned} I_{G1} &= I_L\frac{Z_2}{Z_1+Z_2} = 1200\times\frac{0.0537}{0.0987} = 1200\times0.5439 = 652.6\ \text{A}\\ I_{G2} &= I_L\frac{Z_1}{Z_1+Z_2} = 1200\times0.4561 = 547.4\ \text{A} \end{aligned}

(In per unit the load current is 1200/52.49=22.861200/52.49 = 22.86 pu. G1 carries 12.43 pu and G2 carries 10.43 pu.)

Answer: G1 supplies about 652.6 A and G2 about 547.4 A (54.4 % and 45.6 % of the load current).

Note: if the G2 reactance of 0.1 % is a misprint for 10 %, then XG2=0.2X_{G2} = 0.2 pu, Z2=0.2517Z_2 = 0.2517 pu, and the shares become 1018.0 A (G1) and 182.0 A (G2).

  • 2073 Magh · 10 marks

Compute the per unit values taking power base of 30 MVA and 6.6 kV in the circuit of generator G1 and draw the reactance diagram of a power system shown in figure below. The system has the following data: G1: 25 MVA, 6.6 kV, X = 0.2 p.u.; G2: 15 MVA, 6.6 kV, X = 0.15 p.u.; M: 30 MVA, 13.2 kV, X = 0.15 p.u.; T1: 30 MVA, 6.6/115 kV, X = 0.1 p.u.; T2: 15 MVA, 6.6/115 kV, X = 0.1 p.u. [Figure: G1 (Y, grounded) → T1 (Y grounded–Y grounded) → bus; Line-1 from this bus to a junction; Line-3 from the junction to a bus feeding T3 (Y grounded on line side, Δ on motor side) → motor M; Line-2 from the junction down to a bus feeding T2 (grounded windings) → G2 (Y, grounded). No line impedances or T3 rating are printed.]

Answer

Base: 30 MVA and 6.6 kV in the G1 circuit. The line impedances and the T3 rating are not printed, so T3 is assumed to be 30 MVA, 115/13.2 kV, X = 0.1 pu, and the line reactances are kept as symbols X1,X2,X3X_1, X_2, X_3 (Ω).

Base voltages

  • G1 zone: 6.6 kV
  • Line zone (T1 6.6/115 kV): 115 kV, Zb=115230=440.83 ΩZ_b = \frac{115^2}{30} = 440.83\ \Omega
  • G2 zone (T2 115/6.6 kV): 6.6 kV
  • Motor zone (T3 115/13.2 kV): 13.2 kV

Per-unit values (30 MVA base)

XG1=0.2×3025=0.24 puXG2=0.15×3015=0.30 puXM=0.15×3030×(13.213.2)2=0.15 puXT1=0.1×3030=0.10 puXT2=0.1×3015=0.20 puXT3=0.10 pu (assumed rating)XLine k=Xk440.83 pu\begin{aligned} X_{G1} &= 0.2\times\frac{30}{25} = 0.24\ \text{pu}\\ X_{G2} &= 0.15\times\frac{30}{15} = 0.30\ \text{pu}\\ X_{M} &= 0.15\times\frac{30}{30}\times\left(\frac{13.2}{13.2}\right)^2 = 0.15\ \text{pu}\\ X_{T1} &= 0.1\times\frac{30}{30} = 0.10\ \text{pu}\\ X_{T2} &= 0.1\times\frac{30}{15} = 0.20\ \text{pu}\\ X_{T3} &= 0.10\ \text{pu (assumed rating)}\\ X_{Line\,k} &= \frac{X_k}{440.83}\ \text{pu} \end{aligned}

For example, a line reactance of 100 Ω would be 100/440.83=0.2268100/440.83 = 0.2268 pu.

ElementX (pu, 30 MVA)
G10.24
G20.30
Motor M0.15
T10.10
T20.20
T3 (assumed)0.10
Lines 1, 2, 3Xk/440.83X_k/440.83

Reactance diagram

     j0.10   jXL1      jXL3    j0.10
 +---/\/\/---/\/\/--+--/\/\/---/\/\/---+
 |    T1     Line1  |  Line3    T3     |
j0.24               |                 j0.15
 |                jXL2 (Line2)         |
(E1)                |                 (Em)
 |                 j0.20 (T2)          |
 |                  |                  |
 |                 j0.30 (G2)          |
 |                  |                  |
 |                 (E2)                |
 +------------------+------------------+
           reference (neutral) bus

Answer: XG1=0.24X_{G1}=0.24, XG2=0.30X_{G2}=0.30, XM=0.15X_M=0.15, XT1=0.10X_{T1}=0.10, XT2=0.20X_{T2}=0.20, XT3=0.10X_{T3}=0.10 pu, and each line =X(Ω)/440.83= X(\Omega)/440.83 pu on the 30 MVA, 115 kV base.

  • 2072 Asoj · 6 marks

Two ideal voltage sources designated as machine 1 and 2 are connected as shown in figure. If E1 = 120∠10° V, E2 = 120∠30° V and Z = 1 + j5 Ω, determine: (i) whether each machine is consuming P and Q or generating P and Q (ii) P and Q absorbed by the impedance (iii) direction of power flow. [Figure: source E1 on the left and source E2 on the right, both with + terminal at top, connected through series impedance Z; current I flows from E1 towards E2.]

Answer

Take I flowing from machine 1 to machine 2 through Z. Then S1=E1I∗S_1 = E_1I^* is the power supplied by machine 1 and S2=E2I∗S_2 = E_2I^* is the power absorbed by machine 2.

Current

E1=120∠10∘=118.18+j20.84 VE2=120∠30∘=103.92+j60.00 VI=E1−E2Z=14.26−j39.161+j5=8.173∠−148.69∘ A\begin{aligned} E_1 &= 120\angle10^\circ = 118.18 + j20.84\ \text{V}\\ E_2 &= 120\angle30^\circ = 103.92 + j60.00\ \text{V}\\ I &= \frac{E_1-E_2}{Z} = \frac{14.26 - j39.16}{1 + j5} = 8.173\angle-148.69^\circ\ \text{A} \end{aligned}

(i) Machine powers

S1=E1I∗=(120∠10∘)(8.173∠148.69∘)=−913.73+j356.43 VAS2=E2I∗=(120∠30∘)(8.173∠148.69∘)=−980.53+j22.42 VA\begin{aligned} S_1 &= E_1I^* = (120\angle10^\circ)(8.173\angle148.69^\circ) = -913.73 + j356.43\ \text{VA}\\ S_2 &= E_2I^* = (120\angle30^\circ)(8.173\angle148.69^\circ) = -980.53 + j22.42\ \text{VA} \end{aligned}
MachineReal powerReactive power
1supplies −913.73 W, so it consumes 913.73 W (motor)generates 356.43 var
2absorbs −980.53 W, so it generates 980.53 W (generator)consumes 22.42 var

(ii) Power absorbed by Z

∣I∣2=8.1732=66.80SZ=∣I∣2(1+j5)=66.80+j334.01 VA\begin{aligned} |I|^2 &= 8.173^2 = 66.80\\ S_Z &= |I|^2(1 + j5) = 66.80 + j334.01\ \text{VA} \end{aligned}

Check: 980.53−913.73=66.80980.53 - 913.73 = 66.80 W and 356.43−22.42=334.01356.43 - 22.42 = 334.01 var.

(iii) Direction of power flow

  • Real power flows from machine 2 to machine 1, because E2E_2 leads E1E_1 by 20°. Real power flows from the leading-angle end to the lagging end.
  • Reactive power flows from machine 1 towards machine 2. Machine 1 supplies 356.43 var: 334.01 var is used in the line reactance and 22.42 var reaches machine 2. The magnitudes are equal here, so Q is decided by the angle and the R/X of the line.

Answer: Machine 1 is a motor drawing 913.7 W and supplying 356.4 var. Machine 2 generates 980.5 W and draws 22.4 var. Z absorbs 66.8 W and 334.0 var. P flows 2 → 1.

  • 2072 Asoj · 4 marks

Draw the p.u. impedance diagram for the system shown below. [Figure: G (6.6 kV, 20 MVA, X = 0.15 p.u.) → T1 (11/132 kV, 25 MVA, X = 0.1 p.u.) → line 10 + j60 Ω → T2 (132/11 kV, 20 MVA, X = 0.1) → motor M (11 kV, 15 MVA, X = 0.15 p.u.).]

Answer

Choose the generator rating as base: 20 MVA, 6.6 kV in the generator circuit. (The 6.6 kV generator feeds the 11 kV winding of T1, so the transformer and motor values need voltage correction.)

Base voltages

  • Generator zone: Vb1=6.6V_{b1} = 6.6 kV
  • Line zone (T1 11/132 kV): Vb2=6.6×13211=79.2V_{b2} = 6.6\times\frac{132}{11} = 79.2 kV
  • Motor zone (T2 132/11 kV): Vb3=79.2×11132=6.6V_{b3} = 79.2\times\frac{11}{132} = 6.6 kV
Zb2=79.2220=313.63 ΩZ_{b2} = \frac{79.2^2}{20} = 313.63\ \Omega

Per-unit values

XG=0.15 puXT1=0.1×2025×(116.6)2=0.2222 puZline=10+j60313.63=0.0319+j0.1913 puXT2=0.1×2020×(13279.2)2=0.2778 puXM=0.15×2015×(116.6)2=0.5556 pu\begin{aligned} X_G &= 0.15\ \text{pu}\\ X_{T1} &= 0.1\times\frac{20}{25}\times\left(\frac{11}{6.6}\right)^2 = 0.2222\ \text{pu}\\ Z_{line} &= \frac{10 + j60}{313.63} = 0.0319 + j0.1913\ \text{pu}\\ X_{T2} &= 0.1\times\frac{20}{20}\times\left(\frac{132}{79.2}\right)^2 = 0.2778\ \text{pu}\\ X_M &= 0.15\times\frac{20}{15}\times\left(\frac{11}{6.6}\right)^2 = 0.5556\ \text{pu} \end{aligned}

Impedance diagram

     j0.2222  0.0319+j0.1913  j0.2778
 +---/\/\/-------/\/\/--------/\/\/---+
 |    T1          line          T2    |
j0.15                              j0.5556
 |                                    |
(Eg)                                 (Em)
 |                                    |
 +------------------------------------+
            reference bus

Answer: On 20 MVA (base 6.6 / 79.2 / 6.6 kV): XG=0.15X_G = 0.15, XT1=0.2222X_{T1} = 0.2222, Zline=0.0319+j0.1913Z_{line} = 0.0319 + j0.1913, XT2=0.2778X_{T2} = 0.2778, XM=0.5556X_M = 0.5556 pu.

  • 2072 Magh · 6 marks

Figure below shows a single line diagram of a power system. The ratings of the generators and transformers are given below: G1: 25 MVA, 6.6 kV, XG1 = 0.20 pu; G2: 15 MVA, 6.6 kV, XG2 = 0.15 pu; G3: 30 MVA, 13.2 kV, XG3 = 0.15 pu; T1: 30 MVA, 6.6Δ–115Y kV, XT1 = 0.10 pu; T2: 15 MVA, 6.6Δ–115Y kV, XT2 = 0.10 pu; T3: single phase units each rated 10 MVA, 6.9/69 kV, XT3 = 0.10 pu. Draw the per unit circuit diagram using base values of 30 MVA and 6.6 kV in the circuit of generator 1. [Figure: G1 (25 MVA, 6.6 kV, Y grounded) → T1 (Δ–Y grounded, 6.6/115 kV) → Line-1 j120 Ω → junction bus; from the junction T2 (Δ–Y grounded, 6.6/115 kV) up to G2 (15 MVA, 6.6 kV, Y grounded); and Line-2 j90 Ω → T3 (Y–Y grounded, √3×69/√3×6.9 kV) → G3 (30 MVA, 13.2 kV, Y grounded).]

Answer

Base: 30 MVA, 6.6 kV in the G1 circuit. Base voltages change by the line-to-line turns ratio of each transformer.

Base voltages

  • G1 zone: 6.6 kV
  • Line zone (T1 6.6/115 kV): 115 kV, Zb=115230=440.83 ΩZ_b = \frac{115^2}{30} = 440.83\ \Omega
  • G2 zone (T2 115/6.6 kV): 6.6 kV
  • G3 zone: T3 is a Y–Y bank of 6.9/69 kV single-phase units, so its line-to-line ratio is 3×69/3×6.9=119.5/11.95\sqrt3\times69/\sqrt3\times6.9 = 119.5/11.95 kV, i.e. 10 : 1:
Vb,G3=115×6.969=11.5 kVV_{b,G3} = 115\times\frac{6.9}{69} = 11.5\ \text{kV}

Per-unit values (30 MVA base)

XG1=0.20×3025=0.24 puXG2=0.15×3015=0.30 puXG3=0.15×3030×(13.211.5)2=0.1976 puXT1=0.10 puXT2=0.10×3015=0.20 puXT3=0.10×303×10×(11.9511.5)2=0.1080 puXL1=120440.83=0.2722 puXL2=90440.83=0.2042 pu\begin{aligned} X_{G1} &= 0.20\times\frac{30}{25} = 0.24\ \text{pu}\\ X_{G2} &= 0.15\times\frac{30}{15} = 0.30\ \text{pu}\\ X_{G3} &= 0.15\times\frac{30}{30}\times\left(\frac{13.2}{11.5}\right)^2 = 0.1976\ \text{pu}\\ X_{T1} &= 0.10\ \text{pu}\\ X_{T2} &= 0.10\times\frac{30}{15} = 0.20\ \text{pu}\\ X_{T3} &= 0.10\times\frac{30}{3\times10}\times\left(\frac{11.95}{11.5}\right)^2 = 0.1080\ \text{pu}\\ X_{L1} &= \frac{120}{440.83} = 0.2722\ \text{pu}\\ X_{L2} &= \frac{90}{440.83} = 0.2042\ \text{pu} \end{aligned}
ElementBase kVX (pu)
G16.60.2400
G26.60.3000
G311.50.1976
T16.6/1150.1000
T26.6/1150.2000
T3115/11.50.1080
Line-11150.2722
Line-21150.2042

Per-unit circuit

    j0.10   j0.2722       j0.2042   j0.108
 +--/\/\/---/\/\/----+----/\/\/-----/\/\/---+
 |   T1     Line-1   |    Line-2     T3     |
j0.24              j0.20 (T2)            j0.1976
 |                   |                      |
(E1)               j0.30 (G2)             (E3)
 |                   |                      |
 |                 (E2)                     |
 +-------------------+----------------------+
            reference (neutral) bus

Answer: XG1=0.24X_{G1}=0.24, XG2=0.30X_{G2}=0.30, XG3=0.1976X_{G3}=0.1976, XT1=0.10X_{T1}=0.10, XT2=0.20X_{T2}=0.20, XT3=0.108X_{T3}=0.108, XL1=0.2722X_{L1}=0.2722, XL2=0.2042X_{L2}=0.2042 pu.

  • 2072 Magh · 4 marks

What is complex power? Why is complex power taken as VI* rather than V*I in power systems? Explain.

Answer

Complex power is S=P+jQS = P + jQ, the phasor quantity whose real part is the active power (W), whose imaginary part is the reactive power (var) and whose magnitude is the apparent power (VA). It is defined as S=VI∗S = VI^*.

Why VI∗VI^*

Let V=∣V∣∠θvV = |V|\angle\theta_v and I=∣I∣∠θiI = |I|\angle\theta_i. The power-factor angle is ϕ=θv−θi\phi = \theta_v - \theta_i.

VI∗=∣V∣∣I∣∠(θv−θi)=∣V∣∣I∣cos⁡ϕ+j∣V∣∣I∣sin⁡ϕ=P+jQV∗I=∣V∣∣I∣∠(θi−θv)=∣V∣∣I∣cos⁡ϕ−j∣V∣∣I∣sin⁡ϕ=P−jQ\begin{aligned} VI^* &= |V||I|\angle(\theta_v - \theta_i) = |V||I|\cos\phi + j|V||I|\sin\phi = P + jQ\\ V^*I &= |V||I|\angle(\theta_i - \theta_v) = |V||I|\cos\phi - j|V||I|\sin\phi = P - jQ \end{aligned}
  1. Both give the same P. Only the sign of Q differs.
  2. Sign agreement with the accepted convention. With VI∗VI^*, a lagging (inductive) load (θi<θv\theta_i < \theta_v, ϕ>0\phi > 0) gives Q>0Q > 0. Inductive loads "absorb" vars and capacitors "supply" vars. This is the convention adopted by IEEE/IEC and used in load-flow studies, generator capability charts and var meters. With V∗IV^*I, an inductive load would show negative Q, which conflicts with the convention.
  3. Consistency with impedance. With S=VI∗=∣I∣2Z=∣I∣2(R+jX)S = VI^* = |I|^2Z = |I|^2(R + jX), inductive reactance (+X) gives +Q. The power triangle is then the impedance triangle scaled by ∣I∣2|I|^2. With V∗IV^*I the triangle would be the mirror image of the impedance triangle.
  4. Independence from reference. Taking the conjugate removes the absolute phase angles and keeps only the difference θv−θi\theta_v - \theta_i. So S does not depend on which phasor is chosen as reference. (VIVI without a conjugate would give the angle θv+θi\theta_v + \theta_i, which changes with the reference and has no meaning.)
 Im(Q)
  ^        S = VI*
  |      /
  |    /  Q = |V||I| sin(phi) > 0
  |  / phi    (lagging load)
  +----------> Re (P)

Example: V=100∠0∘V = 100\angle0^\circ V and I=10∠−30∘I = 10\angle-30^\circ A (lagging). Then VI∗=866+j500VI^* = 866 + j500 VA, which is correct: the load absorbs 500 var. But V∗I=866−j500V^*I = 866 - j500 VA would wrongly suggest that the inductive load supplies vars.

  • 2072 Magh · 6 marks

Two 3-phase synchronous generators connected in star with neutral grounded are connected to each other through a line with series impedance per phase of 2 + j8 Ω. The terminal voltages of generators 1 and 2 are 200∠30° V and 210∠50° V respectively. Determine the active and reactive power generated/consumed by each generator.

Answer

The given terminal voltages are taken as per-phase (line-to-neutral) values, since the generators are star connected with neutral grounded and the impedance is per phase. Three-phase power is 3 times the per-phase power.

Let I flow from G1 to G2 through Z=2+j8 ΩZ = 2 + j8\ \Omega. Then S1=V1I∗S_1 = V_1I^* is the power delivered by G1 and S2=V2I∗S_2 = V_2I^* is the power received by G2.

Current

V1=200∠30∘=173.21+j100.00 VV2=210∠50∘=134.99+j160.87 VI=V1−V2Z=38.22−j60.872+j8=−6.037−j6.287=8.716∠−133.84∘ A\begin{aligned} V_1 &= 200\angle30^\circ = 173.21 + j100.00\ \text{V}\\ V_2 &= 210\angle50^\circ = 134.99 + j160.87\ \text{V}\\ I &= \frac{V_1 - V_2}{Z} = \frac{38.22 - j60.87}{2 + j8}\\ &= -6.037 - j6.287 = 8.716\angle-133.84^\circ\ \text{A} \end{aligned}

Powers per phase

S1=V1I∗=(200∠30∘)(8.716∠133.84∘)=−1674.31+j485.19 VAS2=V2I∗=(210∠50∘)(8.716∠133.84∘)=−1826.24−j122.55 VASline=∣I∣2Z=75.97(2+j8)=151.94+j607.74 VA\begin{aligned} S_1 &= V_1I^* = (200\angle30^\circ)(8.716\angle133.84^\circ) = -1674.31 + j485.19\ \text{VA}\\ S_2 &= V_2I^* = (210\angle50^\circ)(8.716\angle133.84^\circ) = -1826.24 - j122.55\ \text{VA}\\ S_{line} &= |I|^2Z = 75.97(2 + j8) = 151.94 + j607.74\ \text{VA} \end{aligned}

Interpretation

QuantityPer phaseThree-phase
G1 real powerconsumes 1674.31 W (motoring)consumes 5022.92 W
G1 reactive powergenerates 485.19 vargenerates 1455.57 var
G2 real powergenerates 1826.24 Wgenerates 5478.73 W
G2 reactive powergenerates 122.55 vargenerates 367.66 var
Line loss151.94 W, 607.74 var455.81 W, 1823.23 var

Check: 1826.24−1674.31=151.931826.24 - 1674.31 = 151.93 W and 485.19+122.55=607.74485.19 + 122.55 = 607.74 var.

Real power flows from G2 to G1 because V2V_2 leads V1V_1 by 20°. G1 behaves as a synchronous motor. Both machines supply reactive power, which is consumed by the line reactance.

Answer: G2 generates 5.48 kW and 0.37 kvar. G1 absorbs 5.02 kW (motor) and generates 1.46 kvar. The line absorbs 0.46 kW and 1.82 kvar (three-phase totals).

  • 2071 Bhadra · 6 marks

Determine the amount of power generated by each of the generators in the power system network below. Also specify the direction of power flow in the network. [Figure: E1 = 1.05∠5° pu behind reactance j0.08 pu, connected through a line of resistance 0.025 pu and reactance j0.1 pu to E2 = 1.05∠20° pu behind reactance j0.08 pu.]

Answer

The two internal reactances and the line form one series path between the two emfs:

Z=j0.08+(0.025+j0.1)+j0.08=0.025+j0.26 puZ = j0.08 + (0.025 + j0.1) + j0.08 = 0.025 + j0.26\ \text{pu}

Let I flow from E1E_1 to E2E_2. Then S1=E1I∗S_1 = E_1I^* is the power generated by G1 and S2=E2I∗S_2 = E_2I^* is the power absorbed by G2.

  j0.08    0.025+j0.1    j0.08
 +-/\/\/-----/\/\/-------/\/\/-+
 |       I -->                 |
(E1) 1.05/5 deg      1.05/20 deg (E2)
 |                             |
 +-----------------------------+

Current

E1=1.05∠5∘=1.0460+j0.0915E2=1.05∠20∘=0.9867+j0.3591I=E1−E2Z=0.0593−j0.26760.025+j0.26=−0.9981−j0.3242=1.0494∠−162.01∘ pu\begin{aligned} E_1 &= 1.05\angle5^\circ = 1.0460 + j0.0915\\ E_2 &= 1.05\angle20^\circ = 0.9867 + j0.3591\\ I &= \frac{E_1 - E_2}{Z} = \frac{0.0593 - j0.2676}{0.025 + j0.26}\\ &= -0.9981 - j0.3242 = 1.0494\angle-162.01^\circ\ \text{pu} \end{aligned}

Powers

S1=E1I∗=−1.0737+j0.2477 puS2=E2I∗=−1.1012−j0.0386 pu (absorbed by G2)Sloss=∣I∣2Z=1.1013(0.025+j0.26)=0.0275+j0.2863 pu\begin{aligned} S_1 &= E_1I^* = -1.0737 + j0.2477\ \text{pu}\\ S_2 &= E_2I^* = -1.1012 - j0.0386\ \text{pu}\ \text{(absorbed by G2)}\\ S_{loss} &= |I|^2Z = 1.1013(0.025 + j0.26) = 0.0275 + j0.2863\ \text{pu} \end{aligned}
GeneratorReal powerReactive power
G1absorbs 1.0737 pu (acts as motor)generates 0.2477 pu
G2generates 1.1012 pugenerates 0.0386 pu

Check: 1.1012−1.0737=0.02751.1012 - 1.0737 = 0.0275 pu (I²R loss) and 0.2477+0.0386=0.28630.2477 + 0.0386 = 0.2863 pu (I²X).

Direction of power flow

  • Real power flows from G2 to G1, since E2E_2 leads E1E_1 by 15°.
  • Both generators supply reactive power to the network, and it is consumed in the series reactances. With equal emf magnitudes, each machine supplies part of the I2XI^2X.

Answer: G2 generates 1.101 pu real power and G1 receives 1.074 pu. The loss is 0.0275 pu. G1 and G2 supply 0.248 pu and 0.039 pu reactive power. P flows G2 → G1.

  • 2071 Bhadra · 6 marks

Draw the per-unit reactance diagram for the power system shown below, choosing suitable base values. G1: 25 kV, 20 MVA, 20%; G2: 25 kV, 30 MVA, 30%; T1: 50 MVA, 33/220 kV, 15%; T2: 50 MVA, 220/11 kV; M1: 20 MVA, 11 kV, 30%; M1: 30 MVA, 11 kV, 20% (second motor, printed as M1). [Figure: G1 and G2 in parallel on a bus → T1 → line j50 Ω/phase → T2 → bus feeding motors M1 and M2.]

Answer

Choice of base: 50 MVA (transformer rating) and 220 kV on the line. Then the generator side base is 33 kV (T1 33/220 kV) and the motor side base is 11 kV (T2 220/11 kV). The reactance of T2 is not printed; it is assumed to be 15 % on its own rating (same as T1).

Zb,line=220250=968 ΩZ_{b,line} = \frac{220^2}{50} = 968\ \Omega

Per-unit reactances (50 MVA base)

XG1=0.20×5020×(2533)2=0.2870 puXG2=0.30×5030×(2533)2=0.2870 puXT1=0.15 puXline=50968=0.0517 puXT2=0.15 pu (assumed)XM1=0.30×5020=0.75 puXM2=0.20×5030=0.3333 pu\begin{aligned} X_{G1} &= 0.20\times\frac{50}{20}\times\left(\frac{25}{33}\right)^2 = 0.2870\ \text{pu}\\ X_{G2} &= 0.30\times\frac{50}{30}\times\left(\frac{25}{33}\right)^2 = 0.2870\ \text{pu}\\ X_{T1} &= 0.15\ \text{pu}\\ X_{line} &= \frac{50}{968} = 0.0517\ \text{pu}\\ X_{T2} &= 0.15\ \text{pu (assumed)}\\ X_{M1} &= 0.30\times\frac{50}{20} = 0.75\ \text{pu}\\ X_{M2} &= 0.20\times\frac{50}{30} = 0.3333\ \text{pu} \end{aligned}
ElementBase kVX (pu)
G1 (20 MVA, 25 kV)330.2870
G2 (30 MVA, 25 kV)330.2870
T133/2200.1500
Line (j50 Ω)2200.0517
T2 (assumed 15 %)220/110.1500
M1 (20 MVA)110.7500
M2 (30 MVA)110.3333

Reactance diagram

        j0.15   j0.0517   j0.15
 +--+---/\/\/---/\/\/-----/\/\/---+------+
 |  |    T1      line      T2     |      |
j0.287 j0.287                  j0.75  j0.3333
 |  |                             |      |
(E1)(E2)                        (Em1)  (Em2)
 |  |                             |      |
 +--+-----------------------------+------+
             reference bus

Answer: On 50 MVA with 33 / 220 / 11 kV bases: XG1=XG2=0.287X_{G1} = X_{G2} = 0.287, XT1=0.15X_{T1} = 0.15, Xline=0.0517X_{line} = 0.0517, XT2=0.15X_{T2} = 0.15 (assumed), XM1=0.75X_{M1} = 0.75, XM2=0.333X_{M2} = 0.333 pu.

  • 2071 Magh · 5 marks

Two ideal 3-phase synchronous machines A and B are connected by a series impedance of 0 + j5 Ω per phase. The voltages at the two machines are 100∠0° and 120∠30° V respectively. Calculate and analyze the direction of power flow in the system.

Answer

Take the voltages as per-phase values. Let I flow from A to B. Then SA=VAI∗S_A = V_AI^* is the power supplied by A and SB=VBI∗S_B = V_BI^* is the power received by B.

Current

VA=100∠0∘=100 VVB=120∠30∘=103.92+j60 VI=VA−VBj5=−3.92−j60j5=−12.0+j0.785=12.026∠176.26∘ A\begin{aligned} V_A &= 100\angle0^\circ = 100\ \text{V}\\ V_B &= 120\angle30^\circ = 103.92 + j60\ \text{V}\\ I &= \frac{V_A - V_B}{j5} = \frac{-3.92 - j60}{j5} = -12.0 + j0.785\\ &= 12.026\angle176.26^\circ\ \text{A} \end{aligned}

Powers per phase

SA=VAI∗=100(−12.0−j0.785)=−1200−j78.46 VASB=VBI∗=−1200−j801.54 VASlink=∣I∣2(j5)=144.62×j5=j723.08 VA\begin{aligned} S_A &= V_AI^* = 100(-12.0 - j0.785) = -1200 - j78.46\ \text{VA}\\ S_B &= V_BI^* = -1200 - j801.54\ \text{VA}\\ S_{link} &= |I|^2(j5) = 144.62\times j5 = j723.08\ \text{VA} \end{aligned}

Check with the lossless-line formula: P=∣VA∣∣VB∣Xsin⁡(δA−δB)=100×1205sin⁡(−30∘)=−1200P = \frac{|V_A||V_B|}{X}\sin(\delta_A - \delta_B) = \frac{100\times120}{5}\sin(-30^\circ) = -1200 W.

Analysis

MachineReal powerReactive power
Asupplies −1200 W, so it receives 1200 W (motor)supplies −78.46 var, so it receives 78.46 var
Breceives −1200 W, so it generates 1200 Wreceives −801.54 var, so it supplies 801.54 var
Link (j5 Ω)0 W (no resistance)absorbs 723.08 var
  • Real power flows from B to A because VBV_B leads VAV_A by 30°. There is no resistance, so A receives exactly what B sends.
  • Reactive power flows from B (higher voltage, 120 V) to A (lower voltage, 100 V). B supplies 801.54 var: 723.08 var is used in the link and 78.46 var reaches A.
  • Three-phase totals (×3): 3600 W from B to A; B supplies 2404.6 var; the link absorbs 2169.2 var; A receives 235.4 var.

Answer: B is the generator and sends 1200 W per phase (3.6 kW total) to A, which acts as a motor. Q flows from B to A: B supplies 801.5 var, the link uses 723.1 var, and A receives 78.5 var (per phase).

  • 2071 Magh · 6 marks

Starting from voltage and current phasors, derive the expression for complex power. Construct the phasor diagram of complex power and explain the significance of the components.

Answer

Complex power S is the phasor product of the voltage and the conjugate of the current. Its real part is the average (active) power and its imaginary part is the reactive power.

Derivation

Let the instantaneous voltage and current be

v=Vmcos⁡(ωt+θv),i=Imcos⁡(ωt+θi)v = V_m\cos(\omega t + \theta_v), \qquad i = I_m\cos(\omega t + \theta_i)

The instantaneous power is

p=vi=VmIm2[cos⁡(θv−θi)+cos⁡(2ωt+θv+θi)]=∣V∣∣I∣cos⁡ϕ [1+cos⁡2(ωt+θv)]+∣V∣∣I∣sin⁡ϕ sin⁡2(ωt+θv)\begin{aligned} p = vi &= \frac{V_mI_m}{2}\left[\cos(\theta_v - \theta_i) + \cos(2\omega t + \theta_v + \theta_i)\right]\\ &= |V||I|\cos\phi\,[1 + \cos 2(\omega t + \theta_v)] + |V||I|\sin\phi\,\sin 2(\omega t + \theta_v) \end{aligned}

Here ∣V∣=Vm/2|V| = V_m/\sqrt2, ∣I∣=Im/2|I| = I_m/\sqrt2 and ϕ=θv−θi\phi = \theta_v - \theta_i.

  • The first term has average P=∣V∣∣I∣cos⁡ϕP = |V||I|\cos\phi. This is the active power.
  • The second term has zero average and peak Q=∣V∣∣I∣sin⁡ϕQ = |V||I|\sin\phi. This is the reactive power.

In phasor form, V=∣V∣∠θvV = |V|\angle\theta_v and I=∣I∣∠θiI = |I|\angle\theta_i. Then

S=VI∗=∣V∣∠θv⋅∣I∣∠−θi=∣V∣∣I∣∠(θv−θi)=∣V∣∣I∣cos⁡ϕ+j∣V∣∣I∣sin⁡ϕ=P+jQ\begin{aligned} S = VI^* &= |V|\angle\theta_v\cdot|I|\angle-\theta_i = |V||I|\angle(\theta_v - \theta_i)\\ &= |V||I|\cos\phi + j|V||I|\sin\phi = P + jQ \end{aligned}

For a load Z=R+jXZ = R + jX: S=∣I∣2Z=∣I∣2R+j∣I∣2XS = |I|^2Z = |I|^2R + j|I|^2X.

Phasor diagram and power triangle

 V reference (lagging load)       Power triangle
  ---------------> V                  /|
  \  phi                         S  /  | Q = |V||I|sin(phi)
    \                             /    |
      \  I (lags V)             / phi  |
        v                      +-------+
                                P = |V||I|cos(phi)

Multiplying V by the conjugate of I turns the V–I phasor diagram into a right-angled triangle. The hypotenuse is ∣S∣|S|, the base is P, the height is Q, and the angle is ϕ\phi.

Significance of the components

ComponentUnitMeaning
P (real part)WAverage power converted to useful work and losses. It is what energy meters record.
Q (imaginary part)varPower exchanged back and forth with magnetic and electric fields. It is needed for magnetising and sets the voltage levels, but does no net work.
∣S∣\lvert S\rvertVASets the current and the rating of generators, transformers and cables
ϕ\phi, cos⁡ϕ\cos\phi—Power factor: the share of S that is useful power
  • Q > 0 means a lagging (inductive) load and Q < 0 a leading (capacitive) load.
  • A low power factor means more current for the same P. This causes more I2RI^2R loss, more voltage drop and larger equipment. So utilities add capacitors to reduce Q.

Example: V=230∠0∘V = 230\angle0^\circ V and I=10∠−36.87∘I = 10\angle-36.87^\circ A give S=2300∠36.87∘=1840+j1380S = 2300\angle36.87^\circ = 1840 + j1380 VA, with pf 0.8 lagging.

  • 2070 Bhadra · 6 marks

Determine the amount of power generated by each of the generators in the power system network below. Also specify the direction of power flow in the network. [Figure: E1 = 1.1∠15° pu behind reactance j0.1 pu, connected through a line of resistance 0.03 pu and reactance j0.1 pu to E2 = 1.1∠0° pu behind reactance j0.1 pu.]

Answer

Total series impedance between the two emfs:

Z=j0.1+(0.03+j0.1)+j0.1=0.03+j0.3 puZ = j0.1 + (0.03 + j0.1) + j0.1 = 0.03 + j0.3\ \text{pu}

Let I flow from E1E_1 to E2E_2. Then S1=E1I∗S_1 = E_1I^* is the power generated by G1 and S2=E2I∗S_2 = E_2I^* is the power received by G2.

  j0.1     0.03+j0.1     j0.1
 +-/\/\/-----/\/\/-------/\/\/-+
 |       I -->                 |
(E1) 1.1/15 deg         1.1/0 deg (E2)
 |                             |
 +-----------------------------+

Current

E1=1.1∠15∘=1.0625+j0.2847E2=1.1∠0∘=1.1I=E1−E2Z=−0.0375+j0.28470.03+j0.3=0.9272+j0.2177=0.9524∠13.21∘ pu\begin{aligned} E_1 &= 1.1\angle15^\circ = 1.0625 + j0.2847\\ E_2 &= 1.1\angle0^\circ = 1.1\\ I &= \frac{E_1 - E_2}{Z} = \frac{-0.0375 + j0.2847}{0.03 + j0.3}\\ &= 0.9272 + j0.2177 = 0.9524\angle13.21^\circ\ \text{pu} \end{aligned}

Powers

S1=E1I∗=(1.1∠15∘)(0.9524∠−13.21∘)=1.0472+j0.0327 puS2=E2I∗=(1.1)(0.9524∠−13.21∘)=1.0200−j0.2394 puSloss=∣I∣2Z=0.9071(0.03+j0.3)=0.0272+j0.2721 pu\begin{aligned} S_1 &= E_1I^* = (1.1\angle15^\circ)(0.9524\angle-13.21^\circ) = 1.0472 + j0.0327\ \text{pu}\\ S_2 &= E_2I^* = (1.1)(0.9524\angle-13.21^\circ) = 1.0200 - j0.2394\ \text{pu}\\ S_{loss} &= |I|^2Z = 0.9071(0.03 + j0.3) = 0.0272 + j0.2721\ \text{pu} \end{aligned}
GeneratorReal powerReactive power
G1generates 1.0472 pugenerates 0.0327 pu
G2receives 1.0200 pu (acts as motor)Q2Q_2 received = −0.2394, so it generates 0.2394 pu

Check: 1.0472−1.0200=0.02721.0472 - 1.0200 = 0.0272 pu and 0.0327+0.2394=0.27210.0327 + 0.2394 = 0.2721 pu.

Direction of power flow

  • Real power flows from G1 to G2, because E1E_1 leads E2E_2 by 15°. G1 is generating and G2 is motoring.
  • Both machines supply reactive power to the network, and it is all consumed in the series reactances (I2X=0.2721I^2X = 0.2721 pu).

Answer: G1 generates 1.047 pu of real power. G2 receives 1.020 pu. The line and reactances absorb 0.027 pu. Reactive power supplied is 0.033 pu by G1 and 0.239 pu by G2. P flows G1 → G2.

  • 2070 Magh · 6 marks

Two ideal voltage sources designated as machines 1 and 2 are connected to each other via a line with impedance of 0 - j5 Ω. If E1 = 100∠0° V and E2 = 100∠30° V, determine the magnitude and the direction of power flow.

Answer

The line impedance Z=0−j5 ΩZ = 0 - j5\ \Omega is a pure capacitive reactance. Let I flow from machine 1 to machine 2. Then S1=E1I∗S_1 = E_1I^* is the power supplied by machine 1 and S2=E2I∗S_2 = E_2I^* is the power received by machine 2.

Current

E1−E2=100−(86.60+j50)=13.40−j50I=13.40−j50−j5=10+j2.679=10.353∠15∘ A\begin{aligned} E_1 - E_2 &= 100 - (86.60 + j50) = 13.40 - j50\\ I &= \frac{13.40 - j50}{-j5} = 10 + j2.679 = 10.353\angle15^\circ\ \text{A} \end{aligned}

Powers

S1=E1I∗=100(10−j2.679)=1000−j267.95 VAS2=E2I∗=(100∠30∘)(10.353∠−15∘)=1000+j267.95 VASZ=∣I∣2Z=107.18(−j5)=−j535.90 VA\begin{aligned} S_1 &= E_1I^* = 100(10 - j2.679) = 1000 - j267.95\ \text{VA}\\ S_2 &= E_2I^* = (100\angle30^\circ)(10.353\angle-15^\circ) = 1000 + j267.95\ \text{VA}\\ S_Z &= |I|^2Z = 107.18(-j5) = -j535.90\ \text{VA} \end{aligned}

Check with P=∣E1∣∣E2∣Xsin⁡(δ1−δ2)P = \frac{|E_1||E_2|}{X}\sin(\delta_1 - \delta_2) using X=−5X = -5: P=100×100−5sin⁡(−30∘)=+1000P = \frac{100\times100}{-5}\sin(-30^\circ) = +1000 W, from 1 to 2.

Magnitude and direction

QuantityResult
Real power1000 W flows from machine 1 to machine 2 (1 generates, 2 consumes)
Machine 1 reactiveQ1=−267.95Q_1 = -267.95 var, so it absorbs 267.95 var
Machine 2 reactivereceives +267.95 var, so it absorbs 267.95 var
Capacitive linegenerates 535.90 var (= 267.95 + 267.95)

Note: with an inductive link, real power flows from the leading machine (2) to the lagging one. A capacitive link reverses this, so power flows from machine 1 to machine 2 even though E2E_2 leads. The line capacitance supplies reactive power equally to both ends, because the voltage magnitudes are equal.

Answer: P = 1000 W flows from machine 1 to machine 2. Each machine absorbs 267.95 var, all supplied by the capacitive line (535.9 var).

  • 2070 Magh · 8 marks

Compute the per unit values taking a common base and draw the impedance diagram of a power system shown in figure below. The system has the following data: Generators: G1: 25 MVA, 6.6 kV, X = 0.2 p.u.; G2: 15 MVA, 6.6 kV, X = 0.15 p.u.; G3: 30 MVA, 13.2 kV, X = 0.15 p.u. Transformers: T1: 30 MVA, 6.6/115 kV, X = 0.1 p.u.; T2: 15 MVA, 6.6/115 kV, X = 0.1 p.u.; T3: three 1-ph units of 10 MVA, 69/6.9 kV, X = 0.4 p.u. [Figure: G1 (Y, grounded) → T1 (Δ–Y grounded) → line j100 Ω → junction bus; from the junction T2 (Y grounded on bus side, Δ on generator side) up to G2; and line j130 Ω → T3 (Y–Y, grounded) → G3 (Y, grounded).]

Answer

Common base: 30 MVA, 6.6 kV in the G1 circuit. Base voltages in other zones follow the line-to-line ratios.

Base voltages

  • G1 zone: 6.6 kV
  • Line zone (T1 6.6/115 kV): 115 kV, Zb=115230=440.83 ΩZ_b = \frac{115^2}{30} = 440.83\ \Omega
  • G2 zone (T2 115/6.6 kV): 6.6 kV
  • G3 zone: T3 is a Y–Y bank of 69/6.9 kV units, so the line-to-line ratio is 119.5/11.95 kV (10 : 1). Then Vb=115/10=11.5V_b = 115/10 = 11.5 kV

Per-unit values (30 MVA)

XG1=0.2×3025=0.24 puXG2=0.15×3015=0.30 puXG3=0.15×3030×(13.211.5)2=0.1976 puXT1=0.1×3030=0.10 puXT2=0.1×3015=0.20 puXT3=0.4×303×10×(11.9511.5)2=0.432 puXL1=100440.83=0.2268 puXL2=130440.83=0.2949 pu\begin{aligned} X_{G1} &= 0.2\times\frac{30}{25} = 0.24\ \text{pu}\\ X_{G2} &= 0.15\times\frac{30}{15} = 0.30\ \text{pu}\\ X_{G3} &= 0.15\times\frac{30}{30}\times\left(\frac{13.2}{11.5}\right)^2 = 0.1976\ \text{pu}\\ X_{T1} &= 0.1\times\frac{30}{30} = 0.10\ \text{pu}\\ X_{T2} &= 0.1\times\frac{30}{15} = 0.20\ \text{pu}\\ X_{T3} &= 0.4\times\frac{30}{3\times10}\times\left(\frac{11.95}{11.5}\right)^2 = 0.432\ \text{pu}\\ X_{L1} &= \frac{100}{440.83} = 0.2268\ \text{pu}\\ X_{L2} &= \frac{130}{440.83} = 0.2949\ \text{pu} \end{aligned}
ElementX (pu, 30 MVA)
G10.2400
G20.3000
G30.1976
T10.1000
T20.2000
T30.4320
Line j100 Ω0.2268
Line j130 Ω0.2949

Impedance diagram

    j0.10   j0.2268       j0.2949   j0.432
 +--/\/\/---/\/\/----+----/\/\/-----/\/\/---+
 |   T1     line 1   |    line 2     T3     |
j0.24              j0.20 (T2)            j0.1976
 |                   |                      |
(E1)               j0.30 (G2)             (E3)
 |                   |                      |
 |                 (E2)                     |
 +-------------------+----------------------+
           reference (neutral) bus

Answer: XG1=0.24X_{G1}=0.24, XG2=0.30X_{G2}=0.30, XG3=0.1976X_{G3}=0.1976, XT1=0.10X_{T1}=0.10, XT2=0.20X_{T2}=0.20, XT3=0.432X_{T3}=0.432, XL1=0.2268X_{L1}=0.2268, XL2=0.2949X_{L2}=0.2949 pu (base 30 MVA; 6.6 / 115 / 6.6 / 11.5 kV).

  • 2069 Bhadra · 6 marks

Construct a reactance diagram for the system given below and express all the reactances in per unit system. G1, G2: 10 MVA, 11.5 kV, 10%; G3: 15 MVA, 11.5 kV, 12%; T1, T2: 10 MVA, 11/66 kV, 10%; T3: 15 MVA, 11/66, 15%; T4: 35 MVA, 66/11 kV, 18%; L1 = L2 = L3 = L4 = j20 Ω/ph. [Figure: G1 (bus 1) → T1 → bus 2; G2 (bus 3) → T2 → bus 4; line L2 from bus 2 to bus 6, L1 from bus 2 to bus 4, L3 from bus 4 to bus 7, L4 from bus 6 to bus 7; T3 between bus 6 and bus 5 feeding G3; T4 between bus 7 and bus 8 feeding motor M (no motor rating printed).]

Answer

Choice of base: 10 MVA, with 11 kV in the generator circuits (the transformer LV rating) and 66 kV on the lines. The motor rating is not printed, so its reactance is left as XMX_M (pu on its own rating). Its value on the common base is XM10SM(VM11)2X_M\frac{10}{S_M}\left(\frac{V_M}{11}\right)^2.

Zb,66=66210=435.6 ΩZ_{b,66} = \frac{66^2}{10} = 435.6\ \Omega

Per-unit reactances (10 MVA base)

XG1=XG2=0.10×1010×(11.511)2=0.1093 puXG3=0.12×1015×(11.511)2=0.0874 puXT1=XT2=0.10 puXT3=0.15×1015=0.10 puXT4=0.18×1035=0.0514 puXL1=XL2=XL3=XL4=20435.6=0.0459 pu\begin{aligned} X_{G1} = X_{G2} &= 0.10\times\frac{10}{10}\times\left(\frac{11.5}{11}\right)^2 = 0.1093\ \text{pu}\\ X_{G3} &= 0.12\times\frac{10}{15}\times\left(\frac{11.5}{11}\right)^2 = 0.0874\ \text{pu}\\ X_{T1} = X_{T2} &= 0.10\ \text{pu}\\ X_{T3} &= 0.15\times\frac{10}{15} = 0.10\ \text{pu}\\ X_{T4} &= 0.18\times\frac{10}{35} = 0.0514\ \text{pu}\\ X_{L1} = X_{L2} = X_{L3} = X_{L4} &= \frac{20}{435.6} = 0.0459\ \text{pu} \end{aligned}
ElementX (pu, 10 MVA)
G1, G20.1093 each
G30.0874
T1, T20.1000 each
T30.1000
T40.0514
L1 to L40.0459 each

Reactance diagram

 (E1)-j0.1093-[1]-j0.10-[2]---j0.0459(L2)---[6]
                         |                   |
                   j0.0459(L1)          j0.0459(L4)
                         |                   |
 (E2)-j0.1093-[3]-j0.10-[4]---j0.0459(L3)---[7]

 [6]-j0.10(T3)-[5]-j0.0874-(E3)
 [7]-j0.0514(T4)-[8]-jXM-(Em)

 All sources (E1, E2, E3, Em) return to the
 common reference (neutral) bus.

Answer: On 10 MVA (11 kV / 66 kV bases): XG1=XG2=0.1093X_{G1} = X_{G2} = 0.1093, XG3=0.0874X_{G3} = 0.0874, XT1=XT2=XT3=0.10X_{T1} = X_{T2} = X_{T3} = 0.10, XT4=0.0514X_{T4} = 0.0514, and each line 0.0459 pu.

  • 2069 Poush · 6 marks

Two 50 Hz, 3-phase synchronous machines are connected to each other via a line with series impedance of 3 + j10 Ohm/phase. Determine the direction of active and reactive power flow in the line and power generated/consumed by each of these machines. The terminal phase voltages of machines 1 and 2 are 3.81∠0° kV and 3.81∠-18° kV respectively.

Answer

Let I flow from machine 1 to machine 2 through Z=3+j10 ΩZ = 3 + j10\ \Omega. Then S1=V1I∗S_1 = V_1I^* is the power delivered by machine 1 and S2=V2I∗S_2 = V_2I^* is the power received by machine 2 (per phase; three-phase = 3 × per phase).

Current

V1=3810∠0∘ VV2=3810∠−18∘=3623.53−j1177.35 VI=V1−V2Z=186.47+j1177.353+j10=113.15+j15.30=114.18∠7.70∘ A\begin{aligned} V_1 &= 3810\angle0^\circ\ \text{V}\\ V_2 &= 3810\angle-18^\circ = 3623.53 - j1177.35\ \text{V}\\ I &= \frac{V_1 - V_2}{Z} = \frac{186.47 + j1177.35}{3 + j10}\\ &= 113.15 + j15.30 = 114.18\angle7.70^\circ\ \text{A} \end{aligned}

Powers per phase

S1=V1I∗=3810(113.15−j15.30)=431.09−j58.28 kVAS2=V2I∗=(3810∠−18∘)(114.18∠−7.70∘)=391.98−j188.64 kVASline=∣I∣2Z=13036.1(3+j10)=39.11+j130.36 kVA\begin{aligned} S_1 &= V_1I^* = 3810(113.15 - j15.30) = 431.09 - j58.28\ \text{kVA}\\ S_2 &= V_2I^* = (3810\angle-18^\circ)(114.18\angle-7.70^\circ) = 391.98 - j188.64\ \text{kVA}\\ S_{line} &= |I|^2Z = 13036.1(3 + j10) = 39.11 + j130.36\ \text{kVA} \end{aligned}

Check: 431.09−391.98=39.11431.09 - 391.98 = 39.11 kW and 188.64−58.28=130.36188.64 - 58.28 = 130.36 kvar.

Results

QuantityPer phaseThree-phase
Machine 1, Pgenerates 431.09 kW1293.26 kW
Machine 1, QQ1=−58.28Q_1 = -58.28, so it absorbs 58.28 kvar174.84 kvar
Machine 2, Pconsumes 391.98 kW (motor)1175.94 kW
Machine 2, Qreceives −188.64, so it generates 188.64 kvar565.92 kvar
Line loss39.11 kW, 130.36 kvar117.33 kW, 391.08 kvar

Direction of flow

  • Active power flows from machine 1 to machine 2, because V1V_1 leads V2V_2 by 18°.
  • Reactive power flows from machine 2 towards machine 1. Machine 2 supplies 188.64 kvar: 130.36 kvar is used in the line reactance and 58.28 kvar reaches machine 1. Both voltage magnitudes are equal, so the flow of Q depends on the angle and on the line resistance.

Answer: Machine 1 is the generator (1293.3 kW, three-phase) and machine 2 the motor (1175.9 kW). The line loss is 117.3 kW. Q flows from machine 2 (565.9 kvar) to machine 1 (174.8 kvar received). The line absorbs 391.1 kvar.

  • 2069 Poush · 4 marks

What is complex power? Show and explain the symmetry between the impedance triangle and power triangle.

Answer

Complex power is S=VI∗=P+jQS = VI^* = P + jQ. Its real part P (W) is the active power, its imaginary part Q (var) is the reactive power, and its magnitude ∣S∣|S| (VA) is the apparent power. The angle of S is the power-factor angle ϕ=θv−θi\phi = \theta_v - \theta_i.

Symmetry with the impedance triangle

For a load Z=R+jX=∣Z∣∠ϕZ = R + jX = |Z|\angle\phi carrying current I, V=IZV = IZ. So

S=VI∗=(IZ)I∗=∣I∣2Z=∣I∣2R+j∣I∣2XS = VI^* = (IZ)I^* = |I|^2Z = |I|^2R + j|I|^2X

So P=∣I∣2RP = |I|^2R, Q=∣I∣2XQ = |I|^2X and ∣S∣=∣I∣2∣Z∣|S| = |I|^2|Z|. Every side of the impedance triangle is multiplied by the same real number ∣I∣2|I|^2. The power triangle is therefore similar to the impedance triangle:

 Impedance triangle          Power triangle
        /|                        /|
   |Z| / | X              |S|    / | Q = |I|^2 X
      /  |                      /  |
     /phi|                     /phi|
    +----+                    +----+
      R                     P = |I|^2 R
Impedance trianglePower triangleLink
RPP=∣I∣2RP = \lvert I\rvert{}^2R
XQQ=∣I∣2XQ = \lvert I\rvert{}^2X
∣Z∣\lvert Z\rvert{}∣S∣\lvert S\rvert{}∣S∣=∣I∣2∣Z∣\lvert S\rvert{} = \lvert I\rvert{}^2\lvert Z\rvert{}
angle ϕ=tan⁡−1(X/R)\phi = \tan^{-1}(X/R)angle ϕ=tan⁡−1(Q/P)\phi = \tan^{-1}(Q/P)same angle
cos⁡ϕ=R/∣Z∣\cos\phi = R/\lvert Z\rvert{}cos⁡ϕ=P/∣S∣\cos\phi = P/\lvert S\rvert{}same power factor

Significance:

  • The two triangles have the same angle. The power factor of a load can be found either from its impedance or from its powers.
  • Inductive X (+) gives +Q (vars absorbed). Capacitive X (−) gives −Q (vars supplied). Both triangles flip below the axis together.
  • This symmetry holds only because S is defined as VI∗VI^*. With V∗IV^*I, Q would be −∣I∣2X-|I|^2X and the power triangle would be the mirror image of the impedance triangle.

Example: Z=6+j8 ΩZ = 6 + j8\ \Omega with ∣I∣=10|I| = 10 A gives S=600+j800S = 600 + j800 VA. Both triangles have angle 53.13° and pf 0.6 lagging.

  • 2069 Poush · 8 marks

Compute the per unit values of a power system shown in figure below taking the common base of the generator. [Figure: G (100 MVA, 6 kV, X = 6%, Y grounded) → T1 (Δ–Y grounded, 120 MVA, 6.6/132 kV, X = 4%) → transmission line (10 + j50) Ω → T2 (Y grounded on line side, Δ on motor side, 120 MVA, 6.6/132 kV; no reactance printed) → bus feeding motors M1 (50 MVA, 6 kV, X = 6%) and M2 (40 MVA, 6 kV, X = 6%).]

Answer

Common base: 100 MVA, 6 kV in the generator circuit. The reactance of T2 is not printed; it is taken equal to T1, X = 4 % on 120 MVA, 6.6/132 kV (an identical transformer).

Base voltages

  • Generator zone: Vb1=6V_{b1} = 6 kV
  • Line zone (T1 6.6/132 kV): Vb2=6×1326.6=120V_{b2} = 6\times\frac{132}{6.6} = 120 kV, Zb2=1202100=144 ΩZ_{b2} = \frac{120^2}{100} = 144\ \Omega
  • Motor zone (T2 132/6.6 kV): Vb3=120×6.6132=6V_{b3} = 120\times\frac{6.6}{132} = 6 kV

Per-unit values (100 MVA)

XG=0.06×100100=0.06 puXT1=0.04×100120×(6.66)2=0.0403 puZline=10+j50144=0.0694+j0.3472 puXT2=0.04×100120×(6.66)2=0.0403 puXM1=0.06×10050×(66)2=0.12 puXM2=0.06×10040=0.15 pu\begin{aligned} X_G &= 0.06\times\frac{100}{100} = 0.06\ \text{pu}\\ X_{T1} &= 0.04\times\frac{100}{120}\times\left(\frac{6.6}{6}\right)^2 = 0.0403\ \text{pu}\\ Z_{line} &= \frac{10 + j50}{144} = 0.0694 + j0.3472\ \text{pu}\\ X_{T2} &= 0.04\times\frac{100}{120}\times\left(\frac{6.6}{6}\right)^2 = 0.0403\ \text{pu}\\ X_{M1} &= 0.06\times\frac{100}{50}\times\left(\frac{6}{6}\right)^2 = 0.12\ \text{pu}\\ X_{M2} &= 0.06\times\frac{100}{40} = 0.15\ \text{pu} \end{aligned}
ElementBase kVpu value
G6j0.06
T16 / 120j0.0403
Line1200.0694 + j0.3472
T2 (assumed 4 %)120 / 6j0.0403
M16j0.12
M26j0.15

Impedance diagram

    j0.0403  0.0694+j0.3472  j0.0403
 +--/\/\/-------/\/\/--------/\/\/--+-------+
 |   T1          line          T2   |       |
j0.06                             j0.12   j0.15
 |                                  |       |
(Eg)                             (Em1)   (Em2)
 |                                  |       |
 +----------------------------------+-------+
              reference bus

Answer: XG=0.06X_G = 0.06, XT1=XT2=0.0403X_{T1} = X_{T2} = 0.0403, Zline=0.0694+j0.3472Z_{line} = 0.0694 + j0.3472, XM1=0.12X_{M1} = 0.12, XM2=0.15X_{M2} = 0.15 pu on 100 MVA (6 / 120 / 6 kV).

  • 2068 Bhadra · 3 marks

Mention the conditions and advantages of representing a 3-phase system by a single phase system.

Answer

A balanced three-phase system can be solved as a single-phase (per-phase) equivalent: one phase plus a neutral, using line-to-neutral voltages. The other two phases have the same results shifted by ±120°.

Conditions

  1. The sources are balanced: equal magnitudes and 120° apart, with positive sequence.
  2. The loads and network are balanced: equal impedance in each phase, and lines are fully transposed so that mutual effects are equal.
  3. The system operates in steady state under balanced (normal or three-phase symmetrical fault) conditions. Unbalanced faults need symmetrical components.
  4. Δ-connected elements are replaced by their equivalent Y (ZY=ZΔ/3Z_Y = Z_\Delta/3). Transformer phase shifts are ignored or added back later.

Under these conditions the neutral current is zero. So the neutral impedance carries no current and is left out of the per-phase circuit.

Advantages

  • Calculation is reduced to one circuit instead of three coupled circuits. This saves time and effort.
  • One-line (single-line) diagrams and per-phase impedance/reactance diagrams can be used.
  • Per-unit quantities are the same for the per-phase and three-phase circuits, which makes the work simpler.
  • Three-phase power is simply 3×3\times per-phase power: S3ϕ=3VphIph∗S_{3\phi} = 3V_{ph}I_{ph}^*.
  • It is used directly in load-flow, short-circuit (symmetrical fault) and stability studies.
  • 2068 Bhadra · 5 marks

Draw a reactance diagram of the electric power system given below and express all reactances in per unit system by choosing appropriate base values. G1: 14 kV, 30 MVA, 10%; M: 11 kV, 25 MVA, 13%; T1: 66/11 kV, 25 MVA, 12%; T1: 13.8/66 kV, 25 MVA, 12% (as printed; one of these is T2). [Figure: G → T1 → line j18 Ohms/phase → T2 → motor M.]

Answer

The two transformers are read as T1: 13.8/66 kV (at the generator) and T2: 66/11 kV (at the motor), both 25 MVA, 12 %.

Choice of base: 25 MVA (transformer rating), 66 kV on the line. Then the base is 13.8 kV in the generator zone and 11 kV in the motor zone.

Zb,line=66225=174.24 ΩZ_{b,line} = \frac{66^2}{25} = 174.24\ \Omega

Per-unit reactances

XG=0.10×2530×(1413.8)2=0.0858 puXT1=0.12 pu (rating = base)Xline=18174.24=0.1033 puXT2=0.12 puXM=0.13×2525×(1111)2=0.13 pu\begin{aligned} X_G &= 0.10\times\frac{25}{30}\times\left(\frac{14}{13.8}\right)^2 = 0.0858\ \text{pu}\\ X_{T1} &= 0.12\ \text{pu (rating = base)}\\ X_{line} &= \frac{18}{174.24} = 0.1033\ \text{pu}\\ X_{T2} &= 0.12\ \text{pu}\\ X_M &= 0.13\times\frac{25}{25}\times\left(\frac{11}{11}\right)^2 = 0.13\ \text{pu} \end{aligned}
ElementBase kVX (pu, 25 MVA)
G (30 MVA, 14 kV)13.80.0858
T113.8/660.1200
Line j18 Ω660.1033
T266/110.1200
Motor M110.1300

Reactance diagram

      j0.12    j0.1033    j0.12
 +----/\/\/----/\/\/------/\/\/----+
 |     T1       line       T2      |
j0.0858                          j0.13
 |                                 |
(Eg)                              (Em)
 |                                 |
 +---------------------------------+
            reference bus

Answer: On 25 MVA (13.8 / 66 / 11 kV): XG=0.0858X_G = 0.0858, XT1=0.12X_{T1} = 0.12, Xline=0.1033X_{line} = 0.1033, XT2=0.12X_{T2} = 0.12, XM=0.13X_M = 0.13 pu.

  • 2068 Bhadra · 2+3 marks

How are generator and load complex powers expressed? What will happen if the convention of taking the conjugate of current is not followed? Explain with necessary derivation.

Answer

Generator and load complex power

Complex power is always written as S=VI∗=P+jQS = VI^* = P + jQ. What it means depends on the assumed current direction.

  • Generator (source) convention: the current leaves the + terminal. SG=VI∗S_G = VI^* is the power delivered. For an over-excited generator supplying a lagging load, PG>0P_G > 0 and QG>0Q_G > 0.
  • Load convention: the current enters the + terminal. SL=VI∗S_L = VI^* is the power absorbed. For an inductive load Z=R+jXZ = R + jX: SL=∣I∣2Z=PL+jQLS_L = |I|^2Z = P_L + jQ_L with QL>0Q_L > 0.

At any bus, the net injected power is Si=SGi−SLi=ViIi∗S_i = S_{Gi} - S_{Li} = V_iI_i^*. This is the form used in load-flow studies.

If the conjugate is not taken

Let V=∣V∣∠θvV = |V|\angle\theta_v, I=∣I∣∠θiI = |I|\angle\theta_i and ϕ=θv−θi\phi = \theta_v - \theta_i.

Case 1: S=V∗IS = V^*I

V∗I=∣V∣∣I∣∠(θi−θv)=∣V∣∣I∣cos⁡ϕ−j∣V∣∣I∣sin⁡ϕ=P−jQV^*I = |V||I|\angle(\theta_i - \theta_v) = |V||I|\cos\phi - j|V||I|\sin\phi = P - jQ

P is correct, but the sign of Q is reversed. An inductive (lagging) load would show negative Q, as if it were supplying vars like a capacitor. Generators and loads would then disagree with the standard convention used in meters, capability charts and load-flow programs. The power triangle would also become the mirror image of the impedance triangle (S=∣I∣2(R−jX)S = |I|^2(R - jX)).

Case 2: S=VIS = VI (no conjugate at all)

VI=∣V∣∣I∣∠(θv+θi)VI = |V||I|\angle(\theta_v + \theta_i)

The angle now depends on the sum of the phase angles. If the reference is changed by α\alpha, then VIVI becomes ∣V∣∣I∣∠(θv+θi+2α)|V||I|\angle(\theta_v + \theta_i + 2\alpha). So P and Q would change just because a different phasor was chosen as reference, which is physically meaningless. Taking the conjugate makes S depend only on the difference θv−θi\theta_v - \theta_i, which is independent of the reference.

Example: V=100∠30∘V = 100\angle30^\circ V and I=10∠0∘I = 10\angle0^\circ A (lagging by 30°).

  • VI∗=1000∠30∘=866+j500VI^* = 1000\angle30^\circ = 866 + j500 VA. Correct: an inductive load absorbs 500 var.
  • V∗I=866−j500V^*I = 866 - j500 VA. Wrong sign of Q.
  • VI=1000∠30∘VI = 1000\angle30^\circ here, but with V as reference (V=100∠0∘V = 100\angle0^\circ, I=10∠−30∘I = 10\angle-30^\circ) it becomes 1000∠−30∘1000\angle-30^\circ. The result changes with the reference.

So the conjugate of current must be taken to get a unique, reference-independent S with the standard sign of Q.

  • 2068 Bhadra · 6 marks

Two 3-phase synchronous machines are connected by an inductive link of j10 Ohms/phase. If the emfs of machine A and machine B are VA = 200∠10° V, VB = 200∠30° V, determine the direction of the reactive power flow and reactive power loss in the link. Neglect the voltage drops at both the machines.

Answer

Per phase, with I flowing from A to B through Z=j10 ΩZ = j10\ \Omega. Then SA=VAI∗S_A = V_AI^* is the power supplied by A and SB=VBI∗S_B = V_BI^* is the power received by B.

Current

VA=200∠10∘=196.96+j34.73 VVB=200∠30∘=173.21+j100.00 VI=VA−VBj10=23.76−j65.27j10=−6.527−j2.376=6.946∠−160∘ A\begin{aligned} V_A &= 200\angle10^\circ = 196.96 + j34.73\ \text{V}\\ V_B &= 200\angle30^\circ = 173.21 + j100.00\ \text{V}\\ I &= \frac{V_A - V_B}{j10} = \frac{23.76 - j65.27}{j10} = -6.527 - j2.376\\ &= 6.946\angle-160^\circ\ \text{A} \end{aligned}

Powers

SA=VAI∗=(200∠10∘)(6.946∠160∘)=−1368.08+j241.23 VASB=VBI∗=(200∠30∘)(6.946∠160∘)=−1368.08−j241.23 VAQloss=∣I∣2X=48.246×10=482.46 var\begin{aligned} S_A &= V_AI^* = (200\angle10^\circ)(6.946\angle160^\circ) = -1368.08 + j241.23\ \text{VA}\\ S_B &= V_BI^* = (200\angle30^\circ)(6.946\angle160^\circ) = -1368.08 - j241.23\ \text{VA}\\ Q_{loss} &= |I|^2X = 48.246\times10 = 482.46\ \text{var} \end{aligned}

Check: Qloss=∣VA−VB∣2X=(2×200sin⁡10∘)210=69.46210=482.46Q_{loss} = \frac{|V_A - V_B|^2}{X} = \frac{(2\times200\sin10^\circ)^2}{10} = \frac{69.46^2}{10} = 482.46 var.

Direction of reactive power

  • Machine A supplies +241.23 var into the link.
  • Machine B receives −241.23 var, so it also supplies 241.23 var into the link.
  • So reactive power flows from both ends into the link. There is no net transfer of vars from one machine to the other, because the voltage magnitudes are equal (200 V each). Each machine supplies half of the link's I2XI^2X.
  • Real power: 1368.08 W per phase flows from B (leading, 30°) to A (lagging, 10°).
QuantityPer phaseThree-phase
Q supplied by A241.23 var723.69 var
Q supplied by B241.23 var723.69 var
Reactive loss in link482.46 var1447.38 var
Real power B → A1368.08 W4104.24 W

Answer: Reactive power flows from both machines into the link, 241.2 var each per phase. The reactive loss in the link is 482.5 var per phase (1447.4 var for three phases).

  • 2068 Magh · 6 marks

Two 3-phase synchronous machines A and B are connected by a link having series impedance of 0 + j10 Ohms/phase. The terminal voltages at machines A and B are 200∠0° V and 200∠15° V respectively. Compute the magnitude and direction of active power flow through the link.

Answer

For a purely reactive link the real power transfer is

P=∣VA∣∣VB∣Xsin⁡(δA−δB)P = \frac{|V_A||V_B|}{X}\sin(\delta_A - \delta_B)

and it flows from the machine with the leading angle to the one with the lagging angle.

Calculation (per phase)

PA→B=200×20010sin⁡(0∘−15∘)=4000×(−0.2588)=−1035.28 W\begin{aligned} P_{A\to B} &= \frac{200\times200}{10}\sin(0^\circ - 15^\circ)\\ &= 4000\times(-0.2588) = -1035.28\ \text{W} \end{aligned}

The negative sign means the power actually flows from B to A.

Check with phasors:

IA→B=200∠0∘−200∠15∘j10=5.221∠−172.5∘ ASA=VAI∗=200×5.221∠172.5∘=−1035.28+j136.30 VASB=VBI∗=−1035.28−j136.30 VA\begin{aligned} I_{A\to B} &= \frac{200\angle0^\circ - 200\angle15^\circ}{j10} = 5.221\angle-172.5^\circ\ \text{A}\\ S_A &= V_AI^* = 200\times5.221\angle172.5^\circ = -1035.28 + j136.30\ \text{VA}\\ S_B &= V_BI^* = -1035.28 - j136.30\ \text{VA} \end{aligned}

So A receives 1035.28 W and B delivers 1035.28 W. The link has no resistance, so there is no real-power loss. Each machine supplies 136.30 var to the link (I2X=27.26×10=272.59I^2X = 27.26\times10 = 272.59 var).

QuantityPer phaseThree-phase
Real power B → A1035.28 W3105.83 W
Reactive loss in link272.59 var817.78 var

Answer: About 1.035 kW per phase (3.106 kW three-phase) flows from machine B to machine A. B acts as the generator and A as the motor, because VBV_B leads VAV_A by 15°.

  • 2068 Magh · 6 marks

What are the major advantages of adopting the per unit system in electric power systems? Explain.

Answer

In the per-unit system every quantity is expressed as a fraction of a chosen base value: pu value=actual valuebase value\text{pu value} = \frac{\text{actual value}}{\text{base value}}. One base MVA is used for the whole system, with a base kV in each voltage zone. Base current and base impedance follow from these: Ib=Sb3VbI_b = \frac{S_b}{\sqrt3V_b} and Zb=Vb2SbZ_b = \frac{V_b^2}{S_b}.

Major advantages

  1. Transformers disappear from the circuit. With base voltages in the ratio of the transformer turns, a transformer's per-unit impedance is the same whether referred to the HV or LV side. The ideal transformer is removed, and the whole network becomes one simple per-unit circuit.
  2. Values lie in a narrow, familiar range. Machine reactances fall in known bands (for example transformer X ≈ 0.05–0.15 pu, synchronous XdX_d ≈ 1–2 pu, Xd′′X''_d ≈ 0.1–0.3 pu), whatever the size of the machine. Wrong data is easy to spot.
  3. Manufacturers give impedances in pu or % on the rating. Only a change of base is needed: Zpu,new=Zpu,oldSb,newSb,old(Vb,oldVb,new)2Z_{pu,new} = Z_{pu,old}\frac{S_{b,new}}{S_{b,old}}\left(\frac{V_{b,old}}{V_{b,new}}\right)^2
  4. No 3\sqrt3 factors and no Y/Δ confusion. Per-unit values are the same for per-phase and three-phase quantities (for example S3ϕ,pu=VpuIpuS_{3\phi,pu} = V_{pu}I_{pu}). So three-phase calculations become single-phase ones.
  5. Easy comparison. Voltage profiles are seen directly (for example 0.95–1.05 pu). Machines of different ratings can be compared, and losses and drops judged at a glance.
  6. Better computation. Numbers are of order 1, which avoids very large or very small values and reduces numerical error. Load-flow, fault and stability programs all work in pu.
  7. Simple equations. Many relations keep their form, for example Vpu=IpuZpuV_{pu} = I_{pu}Z_{pu} and Spu=VpuIpu∗S_{pu} = V_{pu}I_{pu}^*.

Example: a 50 MVA, 11/132 kV transformer with X = 10 % has X=0.1X = 0.1 pu. Referred to the HV side this is 0.1×132250=34.85 Ω0.1\times\frac{132^2}{50} = 34.85\ \Omega; referred to the LV side it is 0.1×11250=0.242 Ω0.1\times\frac{11^2}{50} = 0.242\ \Omega. Both are the same 0.1 pu.

Questions from Old Question Collection (EE 555) (IOE EE 555 exam papers from 2068 Bhadra to 2080 Chaitra) and 2080 course papers (ENEE 205) (IOE ENEE 205 (2080 course) papers, 2081 Chaitra and 2082 Kartik). Answers are written for this site; check them against your class notes.

Chapter titles and hours from the IOE syllabus ↗