Chapter 3 · 8 hours
Computational Technique
IOE past exam questions
Past questions and answers
46 questions set from this chapter, 5 of them more than once. Most asked first.
- Asked 4 times
- 2080 Chaitra · 4 marks
- 2079 Chaitra · 4 marks
- 2075 Bhadra · 4 marks
- 2070 Magh · 6 marks
What will be the consequences if AC complex power is calculated as S = V*I? Explain with necessary phasor diagrams.
Answer
The standard definition of complex power is . With this convention, a lagging (inductive) load absorbs positive . Using gives the same but reverses the sign of .
Derivation
Let and , with (positive for a lagging current).
So .
Phasor diagrams (inductive load, current lags)
S = V I* S = V* I
Q>0 S V
^ / /
| / phi / phi (V ref)
| / /------> P
| / \
|/-------> P \ S
v Q<0
Inductive load: Inductive load:
Q positive (absorbs) Q appears negative
Consequences of using
- The real power is unchanged, since is even.
- The sign of is reversed: an inductor (lagging current) would appear to supply reactive power, and a capacitor to absorb it.
- This contradicts the standard convention (IEEE/IEC) that inductive loads absorb VAr. Generator, motor and load data would be read wrongly.
- The power factor angle and the power triangle are flipped, so lagging and leading would be confused.
- In load flow and compensation studies, capacitor banks would be sized in the wrong direction.
Example: Take V and A (inductive load).
- : the load absorbs 500 var, which is correct.
- : this wrongly shows the inductive load as a source of 500 var.
is used so that inductive Q is positive.
- Asked 4 times
- 2080 Chaitra · 4 marks
- 2079 Chaitra · 4 marks
- 2075 Bhadra · 6 marks
- 2074 Bhadra · 2+4 marks
Verify mathematically the following statement: "The per unit impedance of a transformer remains the same when referred to the high voltage side or low voltage side of the transformer."
Answer
The statement is true. The per-unit impedance of a transformer is the same on both sides, provided the base voltages on the two sides are in the ratio of the transformer turns (with the same VA base).
Proof
Consider a transformer of rating (VA), with voltages (LV) and (HV) and turns ratio . Choose:
- the same base VA, , on both sides
- base voltages and , so that
Base impedances:
Let be the equivalent impedance referred to the LV side. Referred to the HV side, it becomes:
Per-unit values:
So is the same whichever side it is referred to.
Numerical check
Take a 10 kVA, 200/400 V transformer with referred to the LV side.
- LV side: , so .
- HV side: and , so .
Significance
The ideal transformer disappears from the per-unit equivalent circuit, leaving only a series impedance. Manufacturers can therefore quote a single % or p.u. impedance without naming a side. The result holds only when the bases follow the turns ratio. If they do not, an off-nominal tap must be included.
- Asked 3 times
- 2077 Chaitra · 4 marks
- 2076 Bhadra · 4 marks
- 2075 Baisakh · 4 marks
What is per unit system? What are the advantages of per unit representation?
Answer
In the per-unit system, every quantity (voltage, current, power, impedance) is expressed as a fraction of a chosen base value of the same unit:
Usually the base MVA () and the base kV () are chosen. The other bases follow from them:
For example, at 100 MVA and 132 kV, , so a 50 Ω line has p.u.
Advantages
- Transformers disappear: The p.u. impedance of a transformer is the same on both sides, so the ideal transformers drop out of the equivalent circuit.
- Compact ranges: The p.u. impedances of machines and transformers of similar type lie in a narrow range whatever their size. This makes it easy to check data and to estimate missing values.
- Manufacturers' data: Impedances are given in % or p.u. on the equipment's own rating, so they can be used directly after a simple change of base.
- Three-phase and single-phase are the same: In p.u. the line and phase values are equal and the factor disappears from the calculations.
- Easier hand and computer calculation: The numbers are of order 1, so errors are easy to spot. Load flow and fault programs use p.u. throughout.
- Meaningful comparison: A voltage of 0.95 p.u. immediately shows a 5 % drop at any voltage level.
- Asked 3 times
- 2072 Asoj · 3+3 marks
- 2071 Bhadra · 5 marks
- 2069 Bhadra · 6 marks
List out the advantages of the per unit system. How are the base voltages and base power chosen?
Answer
Advantages of the per-unit system
- The p.u. impedance of a transformer is the same on the HV and LV sides, so ideal transformers vanish from the equivalent circuit.
- The p.u. impedances of similar equipment lie in a narrow band, whatever the rating. This makes it easy to check data and to assume typical values.
- Manufacturers give impedances in % or p.u. on the rating of the equipment, and these can be used directly.
- Line and phase quantities have the same p.u. value, and factors disappear. Single-phase and three-phase calculations look alike.
- The numbers are near 1, which reduces arithmetic errors. It is easy to see abnormal conditions, for example p.u.
- It is ideal for computer studies (load flow, fault and stability analysis).
Choosing base power and base voltages
- Base power (, MVA): Choose one value for the whole system. It is usually the rating of the largest machine or a round figure such as 100 MVA.
- Base voltage (, kV): Choose it in one section, usually the generator or line section, often equal to that section's rated voltage.
- Other sections: Carry the base voltage through each transformer by its line-to-line voltage ratio:
For single-phase units in a Y–Δ bank, use the line voltage ratio ( on the Y side).
- Derived bases:
- Change of base: Convert each equipment value to the common base:
Example: Take MVA and 11 kV in the generator circuit, with an 11/132 kV transformer. The line base is 132 kV and .
- Asked 2 times
- 2070 Magh · 4 marks
- 2069 Bhadra · 4 marks
Discuss complex power and its significance in circuit analysis.
Answer
Complex power is the product of the voltage phasor and the conjugate of the current phasor. Its real part is the active power and its imaginary part is the reactive power:
where:
- (W)
- (var)
- (VA) is the apparent power
For a three-phase system, .
Power triangle
S (VA)
/|
/ | Q (var)
/phi|
/____|
P (W)
Significance in circuit and power system analysis
- One complex number gives both and , together with their signs, so power flow is described completely.
- Sign convention: With , an inductive load absorbs and a capacitor absorbs (that is, it supplies Q). A source delivers power when , computed with current leaving its + terminal, is positive.
- Conservation: The sum of complex power over all elements is zero (Tellegen's theorem), so and each balance. This is the basis of load flow equations.
- It gives the power factor directly, , and so the size of the compensation needed.
- Equipment such as generators, transformers and cables is rated in VA (that is, ), because heating depends on .
- With it gives the losses and the reactive drop in lines directly.
Example: If V and A, then VA. The load absorbs 1840 W and 1380 var at a power factor of 0.8 lagging.
- 2082 Kartik (new course) · 4 marks
A voltage source Ean = -120∠210° V and the current through the source Ina = 10∠60° A. Find the values of real power (P) and reactive power (Q) and state whether the source is delivering or receiving each.
Answer
Use . The current flows from n to a inside the source, so it leaves the positive terminal a. A positive or therefore means the source is delivering that power.
Simplify the voltage
Complex power
Interpretation
| Quantity | Value | Meaning |
|---|---|---|
| 1039.2 W | Positive, so the source delivers real power | |
| −600 var | Negative, so the source receives (absorbs) 600 var |
The current leads the voltage by 30°, so the source sees a leading (capacitive) load. That load returns reactive power to the source.
Answer: W, delivered by the source. var, absorbed by the source (delivered var).
- 2082 Kartik (new course) · 2+6 marks
Figure below shows a single line diagram of a power system. Draw its impedance diagram without showing their values. Also, redraw the circuit with per unit values in the reactance diagram. Take 5,000 VA base and common system base voltage of 250 V. [Figure: generators G1 (2000 VA, 250 V, Z = j0.2 p.u.) and G2 (2000 VA, 250 V, Z = j0.3 p.u.) in parallel on a common bus, feeding transformer T1 (4000 VA, 250/800 V, Z = j0.2 p.u.), then a line Z = 40 + j150 Ω, then transformer T2 (8000 VA, 1000/500 V, Z = j0.06 p.u.) supplying a load.]
Answer
(a) Impedance diagram (no values)
Each generator is shown as an EMF behind its internal impedance. Each transformer is shown as series leakage impedance with a shunt magnetising branch. The line is a series (short line), and the load is an impedance.
G1 T1 T2
(~)-Zg1-+-Zt1-+--R+jX line--+-Zt2-+-- Load
| | | | Z_L
(~)-Zg2-+ Ym Ym |
G2 | | | |
ref ----+-----+-------------+-----+---
(b) Selecting the bases
- VA for the whole system.
- Generator section: V.
- Line section: through T1 (250/800 V), V.
- Load section: through T2 (rated 1000 V on the line side), V.
Per-unit values
Use .
Line: the base impedance is
T2 (rated 1000 V, while the base on its side is 800 V):
Reactance (per-unit) diagram
j0.5 j0.25 0.3125+j1.172 j0.0586
(G1)--+------/\/\---------/\/\--------/\/\----Load
| |
(G2)--+ j0.75 |
| |
------+------------ reference ----------------+
| Element | p.u. value |
|---|---|
| G1 | j0.50 |
| G2 | j0.75 |
| T1 | j0.25 |
| Line | 0.3125 + j1.1719 |
| T2 | j0.0586 |
The magnetising branches are neglected in the reactance diagram. The load impedance is not given, so it is shown as a block. Its p.u. value would be with .
- 2081 Chaitra (new course) · 8 marks
A 90 MVA, 11 kV 3-phase generator has a reactance of 15%. The generator supplies two motors through transformers and transmission line shown in figure below. The transformer T1 is a 3-phase transformer, 100 MVA, 10/132 kV, 6% reactance. The transformer T2 is composed of 3 single phase units each rated at 30 MVA, 66/10 kV with 5% reactance. The connection of T1 and T2 are as shown. The motors rated at 50 MVA and 40 MVA, both 10 kV and 20% reactance. Taking the generator rating as base, draw the reactance diagram and indicate the reactance in per unit. The reactance of the line is 100 Ω. [Figure: G (Y, grounded) → T1 (Δ–Y, Y grounded) → Line → T2 (Y grounded–Δ) → bus feeding motor M1 (Y, grounded) and motor M2 (Δ).]
Answer
Choice of bases
- MVA and kV in the generator circuit.
- Line: through T1 (10/132 kV), kV.
- T2 is a Y–Δ bank of three single-phase 66/10 kV units. Its line-voltage ratio is kV / 10 kV, and its three-phase rating is MVA.
- Motor circuit: kV.
Per-unit reactances
Use .
(T2 gives the same value on its HV side: .)
| Element | p.u. reactance (90 MVA base) |
|---|---|
| Generator | j0.150 |
| T1 | j0.0446 |
| Line | j0.4269 |
| T2 | j0.0310 |
| Motor M1 | j0.2231 |
| Motor M2 | j0.2789 |
Reactance diagram
j0.15 j0.0446 j0.4269 j0.031
+-/\/\-----/\/\------/\/\-----/\/\---+-----+
| | |
(Eg) j0.2231 j0.2789
| | |
| (Em1) (Em2)
+------------- reference --------------+-----+
The transformer winding connections (Y, Δ, earthing) do not change the positive-sequence p.u. reactances. They only introduce a phase shift, which is ignored in the reactance diagram.
- 2080 Chaitra · 8 marks
What is the significance of reactance diagram? The single line diagram of a three phase power system is shown in the figure. Draw a reactance diagram considering a base of 100 MVA and 13.8 kV on generator side. G: 90 MVA, 13.8 kV, Xg = 18%; T1 = 50 MVA, 13.8/220 kV, XT1 = 10%; T2 = 50 MVA, 220/11 kV, XT2 = 10%; T3 = 50 MVA, 13.8/132 kV, XT3 = 10%; T4 = 50 MVA, 132/11 kV, XT4 = 10%; M: 80 MVA, 10.45 kV, Xm = 20%; Load: 57 MVA, 0.8 pf lagging at 10.45 kV; Xline1 = 50 Ω, Xline2 = 70 Ω. [Figure: generator G at bus 1 feeds two parallel paths to bus 4: T1 (bus 1–2) → Line-1 at 220 kV (bus 2–3) → T2 (bus 3–4); and T3 (bus 1–5) → Line-2 at 132 kV (bus 5–6) → T4 (bus 6–4). Motor M and the load are connected at bus 4.]
Answer
Significance of the reactance diagram
A reactance diagram is the per-phase equivalent circuit of the system, drawn from the single line diagram, in which:
- resistances, magnetising branches and line charging are neglected
- all values are in p.u. on a common base
It is used for short-circuit (fault) calculations and stability studies, where the reactances dominate. It gives a simple network that can be reduced quickly.
Base values
- MVA, and kV at the generator (bus 1).
| Section | Base kV | (Ω) |
|---|---|---|
| Bus 1 (generator) | 13.8 | – |
| Line 1 (via T1 13.8/220) | 220 | |
| Line 2 (via T3 13.8/132) | 132 | |
| Bus 4 (via T2 220/11 or T4 132/11) | 11 | – |
Both paths give 11 kV at bus 4, so the bases are consistent.
Per-unit values
Load: p.u. at a power factor of 0.8 lagging, and p.u. As a series impedance:
Reactance diagram
T1 L1 T2
+--j0.2--j0.1033--j0.2--+
j0.2 | |
+-/\/\---+ bus1 bus4 +---+------+
| | | | |
(Eg) +--j0.2--j0.4017--j0.2--+ j0.2256 1.2667
| T3 L2 T4 | +j0.95
| (Em) |
+------------- reference -----------+----+
| Element | p.u. |
|---|---|
| G | j0.2 |
| T1, T2, T3, T4 | j0.2 each |
| Line 1 | j0.1033 |
| Line 2 | j0.4017 |
| Motor | j0.2256 |
| Load | 1.2667 + j0.95 |
- 2079 Chaitra · 8 marks
Prepare an impedance diagram of the system shown in the figure below and show all impedances in per unit on a 100 MVA, 132 kV base in the transmission line circuit. [Figure: G1 (50 MVA, 13.8 kV, X = 0.15 p.u.) → T1 (80 MVA, Y-Y, 12.2/161 kV, Xt = 0.1 p.u.) → HV bus; from this bus a line of 40 + j160 Ω goes to the HV side of T2, and a parallel path of two sections 20 + j80 Ω and 20 + j80 Ω also joins the two buses, with a load of 50 MVA, cos φ = 0.8 lag, V = 154 kV tapped at the junction of the two sections; T2 (40 MVA, Y-Y, 161/13.8 kV, Xt2 = 0.1 p.u.) → G2 (20 MVA, 13.8 kV, X = 0.15 p.u.).]
Answer
Base values
- MVA, and kV in the transmission circuit, so .
- G1 side, through T1 (12.2/161 kV): kV.
- G2 side, through T2 (161/13.8 kV): kV.
Per-unit impedances
Use .
Lines:
Load (50 MVA, 0.8 lagging, 154 kV): p.u. and p.u.
Impedance diagram
j0.571 j0.186 0.2296+j0.9183 j0.3719 j1.1157
+-/\/\----/\/\--+-------/\/\/\/\-------+--/\/\----/\/\--+
| | | |
(E1) +-0.1148+j0.4591-+-0.1148+j0.4591-+ (E2)
| | |
| 2.1778+j1.6333 (load) |
| | |
+---------------- reference -----+---------------------+
| Element | p.u. (100 MVA, 132 kV line base) |
|---|---|
| G1 | j0.5710 |
| T1 | j0.1860 |
| Line (40 + j160 Ω) | 0.2296 + j0.9183 |
| Each section (20 + j80 Ω) | 0.1148 + j0.4591 |
| Load | 2.1778 + j1.6333 |
| T2 | j0.3719 |
| G2 | j1.1157 |
- 2078 Chaitra · 6 marks
Two three-phase machines have generated EMF of 11∠0° kV and 11∠40° kV. They are connected through a 3-phase line having an impedance of 0 + j15 Ω per phase. Find: (i) whether each machine is acting as generator or motor and the real power generated or consumed by them; (ii) whether each machine is delivering or consuming reactive power and the amount of reactive power.
Answer
Assumption: 11 kV is the line-to-line EMF. The per-phase EMFs are therefore kV and kV. The current is taken as flowing from machine 1 to machine 2 through .
Current
Complex power (three-phase)
Machine 1, with power taken out of its terminal:
Machine 2, with power taken into it (since enters it):
Check with the standard formulas:
(i) Real power
- Machine 1: MW out of it, so it consumes 5.185 MW and acts as a motor.
- Machine 2: MW, so it generates 5.185 MW and acts as a generator.
Machine 2's EMF leads by 40°, so real power flows from 2 to 1. The line is lossless (), so the two powers are equal.
(ii) Reactive power
- Machine 1: Mvar out of it, so it delivers 1.887 Mvar.
- Machine 2: Mvar, so it also delivers 1.887 Mvar.
Both machines supply reactive power to the line, which absorbs:
Answer: Machine 1 is a motor consuming 5.185 MW, and machine 2 is a generator producing 5.185 MW. Each machine supplies 1.887 Mvar, a total of 3.774 Mvar absorbed by the line reactance.
- 2078 Chaitra · 10 marks
A 20 MVA, 11 kV three-phase synchronous generator has a sub-transient reactance of 10%. It is connected through three identical single-phase Δ-Y connected transformers of 5000 kVA, 11/127.02 kV with a reactance of 15% to a high voltage transmission line having a total series reactance of j180 Ω. At the end of the HT transmission line, three identical single-phase star/star connected transformers of 5000 kVA, 127.02/12.702 kV with a reactance of 20%. The load is drawing 15 MVA at 20 kV at 0.9 pf lagging. Draw a single line diagram of the network and determine the reactance diagram. Choose a common base of 15 kV and 25 MVA.
Answer
Single line diagram
G T1 (3 x 1-ph) line T2 (3 x 1-ph)
(~)--||--[ D | Y ]----------j180----[ Y | Y ]----> Load
20 MVA 5 MVA each 5 MVA each 15 MVA
11 kV 11/127.02 kV 127.02/ 20 kV
X"=10% X=15% 12.702 kV 0.9 lag
X=20%
Transformer bank ratings
- T1 (Δ–Y): MVA. Line voltages: 11 kV / kV.
- T2 (Y–Y): 15 MVA, 220 kV / kV.
Base values
Assumption: the 15 kV base is taken in the generator circuit, with MVA.
| Section | Base kV | (Ω) |
|---|---|---|
| Generator | 15 | 9 |
| Line | ||
| Load | 36 |
Per-unit reactances
Load
15 MVA at 20 kV and 0.9 lagging: p.u., p.u.
As a series impedance:
Reactance diagram
j0.0672 j0.1344 j0.05 j0.1793
+-/\/\------/\/\------/\/\------/\/\----+
| |
(Eg) 0.6667 + j0.3229
| (load)
+----------------- reference -----------+
| Element | p.u. (25 MVA, 15 kV gen base) |
|---|---|
| Generator | j0.0672 |
| T1 | j0.1344 |
| Line | j0.0500 |
| T2 | j0.1793 |
| Load | 0.6667 + j0.3229 (0.54 + j0.2615 p.u. power) |
- 2077 Chaitra · 4 marks
What do you mean by single line diagram? Write its significance in power system analysis.
Answer
A single line diagram (SLD), or one-line diagram, shows a balanced three-phase power system using one line to represent all three phases. Standard symbols show the generators, transformers, lines, breakers, buses and loads, together with their ratings and connections.
Typical SLD
G1 M
(~)--[x]--8|8--+===== line =====+--8|8--[x]--(M)
CB T1 | | T2
Bus 1 Bus 2
| |
Load Load
(~) generator 8|8 transformer [x] breaker
Information shown
- Ratings: MVA, kV and % reactance of machines and transformers
- Transformer winding connections (Y, Δ) and neutral earthing
- Line impedances, buses, and the location of breakers, CTs and PTs
- The points where loads and generators connect
Significance in power system analysis
- Simplicity: A balanced three-phase system is solved on a per-phase basis, so one line gives all the needed information without clutter.
- Starting point for analysis: The impedance and reactance diagrams, the bus admittance matrix, load flow, fault studies and stability studies are all built from the SLD.
- Planning and operation: It shows the system layout clearly to planners, operators and protection engineers.
- Protection coordination: It shows the locations of breakers and relays and the fault paths.
- Data in one place: All the ratings needed for p.u. calculation are on one drawing.
A simple example is a generator, a step-up transformer, a transmission line, a step-down transformer and a load in series, each shown by its symbol and rating.
- 2077 Chaitra · 8 marks
Draw the reactance diagram with all values in p.u. on a base of 30 MVA, 6.6 kV in the circuit of generator G1. Required data are as follows: G1: 25 MVA, 6.6 kV, j0.2 p.u.; G2: 15 MVA, 6.6 kV, j0.15 p.u.; G3: 30 MVA, 13.2 kV, j0.15 p.u.; T1: 30 MVA, 6.6 (delta) kV/115 (star) kV, j0.1 p.u.; T2: 15 MVA, 6.6 (delta) kV/115 (star) kV, j0.1 p.u.; T3: single phase units each rated 10 MVA, 69/6.9 kV, j0.1 p.u. [Figure: G1 (Y, grounded) → T1 (Δ–Y grounded) → line j120 Ω → junction bus; from the junction, T2 (Y grounded on HV side, Δ on LV side) up to G2 (Y, grounded); and a line j90 Ω → T3 (Y–Y, grounded) → G3 (Y, grounded).]
Answer
Base values
- MVA, and kV in the G1 circuit.
- Line section (through T1, 6.6/115 kV): kV, so .
- G2 circuit (through T2, 115/6.6 kV): kV.
- T3 is a Y–Y bank of single-phase 69/6.9 kV units. Its line ratio is kV / kV, and its rating is MVA.
- G3 circuit: kV.
Per-unit reactances
| Element | p.u. (30 MVA base) |
|---|---|
| G1 | j0.24 |
| T1 | j0.10 |
| Line (j120 Ω) | j0.2722 |
| T2 | j0.20 |
| G2 | j0.30 |
| Line (j90 Ω) | j0.2042 |
| T3 | j0.108 |
| G3 | j0.1976 |
Reactance diagram
j0.24 j0.10 j0.2722 j0.2042 j0.108 j0.1976
+-/\/\--/\/\----/\/\----+(J)+---/\/\----/\/\----/\/\--+
| | |
(E1) j0.20 (T2) (E3)
| | |
| j0.30 (G2) |
| | |
| (E2) |
+------------------- reference -----------------------+
Here J is the junction bus. Winding connections and earthing do not affect these positive-sequence reactances.
- 2076 Baisakh · 10 marks
Draw the reactance diagram of the following figure with its equivalent per unit system. Take base MVA = 100 MVA and base voltage = 11 kV for generator. Compute the reactance diagram. [Figure: G1 → T1 and G2 → T2 feed a common 220 kV bus at the sending side; Line-1 and Line-2 run in parallel from there to a receiving bus, which feeds G3 through T3. Data: G1 100 MVA, 11 kV, X = 25%; G2 100 MVA, 11 kV, X = 20%; G3 100 MVA, 11 kV, X = 20%; T1 100 MVA, 11/220 kV, X = 6%; T2 100 MVA, 11/220 kV, X = 7%; T3 100 MVA, 220/11 kV, X = 7%; Line-1 100 MVA, 220 kV, X = 10%; Line-2 100 MVA, 220 kV, X = 10%.]
Answer
Base values
- MVA, and kV in the generator circuits.
- Line section (through 11/220 kV transformers): kV, so .
- G3 circuit (through T3, 220/11 kV): kV.
Conversion to the common base
Every component is rated at 100 MVA, and its rated voltage equals the base voltage of its section. Both correction factors are therefore 1, and each p.u. value equals its percentage reactance divided by 100.
| Element | Rating | Calculation | p.u. reactance |
|---|---|---|---|
| G1 | 100 MVA, 11 kV, 25 % | j0.25 | |
| G2 | 100 MVA, 11 kV, 20 % | j0.20 | |
| G3 | 100 MVA, 11 kV, 20 % | j0.20 | |
| T1 | 100 MVA, 11/220 kV, 6 % | j0.06 | |
| T2 | 100 MVA, 11/220 kV, 7 % | j0.07 | |
| T3 | 100 MVA, 220/11 kV, 7 % | j0.07 | |
| Line 1 | 100 MVA, 220 kV, 10 % | j0.10 | |
| Line 2 | 100 MVA, 220 kV, 10 % | j0.10 |
In ohms, each line is .
Reactance diagram
j0.25 j0.06 j0.10 (L1)
+-/\/\--/\/\--+------+--/\/\--+------+ j0.07 j0.20
| | | | +--/\/\--/\/\--+
(E1) | +--/\/\--+ |
| | j0.10 (L2) (E3)
| j0.20 j0.07| |
+-/\/\--/\/\--+ |
| |
(E2) |
+----------------------- reference -----------------+
Simplified values (useful for fault studies)
- The two lines in parallel: .
- G1–T1 branch: . G2–T2 branch: .
- These two branches in parallel: .
- G3–T3 branch: .
- 2076 Bhadra · 10 marks
A 300 MVA, 20 kV three-phase generator has a sub-transient reactance of 20%. The generator supplies two synchronous motors over a 65 kilometre line having transformers at both ends, as shown on the single line diagram. The neutral of one of the motors M1 is grounded while M2 is ungrounded. Rated inputs to the motors are 200 MVA at 13.2 kV and 100 MVA at 13.2 kV for M1 and M2 respectively. For both motors X"d = 20%. The three phase transformer T1 is rated 350 MVA, 230/20 kV with leakage reactance of 10%. Transformer T2 is composed of three single phase transformers, each rated 127/13.2 kV, 100 MVA with leakage reactance of 10%. Series reactance of the transmission line is 0.8 ohm/km. Draw the reactance diagram with all the reactances marked in p.u. Select the generator rating as base in the generator circuit. [Figure: G (Y, neutral grounded through an impedance) → T1 (Δ on generator side, Y grounded on line side) → transmission line TL → T2 (Y grounded on line side, Δ on motor side) → motors M1 (Y, grounded) and M2 (Y, ungrounded).]
Answer
In a per-unit reactance diagram every element is expressed on one common MVA base, and the base voltage changes from zone to zone in the ratio of the transformer line-to-line voltages. Resistances, magnetising branches and the grounding impedances are neglected (they carry no current under balanced conditions).
Step 1: Base values in each zone
- Base MVA (all zones): MVA
- Generator zone: kV (given)
- Line zone (T1 is 20/230 kV): kV
- T2 is a Y–Δ bank of single-phase units 127/13.2 kV, so its line-to-line ratio is kV. Motor zone:
Step 2: Change of base
Step 3: Per-unit reactances
(The three-phase rating of T2 is MVA.)
| Element | Rating used | X (pu on 300 MVA) |
|---|---|---|
| Generator G | 300 MVA, 20 kV | 0.2000 |
| T1 | 350 MVA, 20/230 kV | 0.0857 |
| Line | 52 Ω, base 176.33 Ω | 0.2949 |
| T2 | 300 MVA, 220/13.2 kV | 0.0915 |
| Motor M1 | 200 MVA, 13.2 kV | 0.2744 |
| Motor M2 | 100 MVA, 13.2 kV | 0.5488 |
Step 4: Reactance diagram
j0.0857 j0.2949 j0.0915
+---/\/\/-----/\/\/-----/\/\/---+--------+
| T1 line T2 | |
j0.2 j0.2744 j0.5488
| | |
(Eg) (Em1) (Em2)
| | |
+-------------------------------+--------+
reference (neutral) bus
Answer: On 300 MVA base, , , , , and pu, with base voltages 20 kV, 230 kV and 13.8 kV in the three zones.
- 2075 Baisakh · 6 marks
Draw the reactance diagram using a base of 50 MVA and 13.8 kV on generator G1 of a given single line diagram of a power system. The ratings of the generators and transformers are given below: G1: 20 MVA, 13.8 kV, X" = 20%; G2: 30 MVA, 18 kV, X" = 20%; G3: 30 MVA, 20 kV, X" = 20%; T1: 25 MVA, 220/13.8 kV, X = 10%; T2: 3 single phase units each rated 10 MVA, 127/18 kV, X = 10%; T3: 35 MVA, 220/22 kV, X = 10%. [Figure: G1 (Y, grounded) → T1 (Δ on generator side, Y grounded on HV side) → line Section 1, j80 Ω [?] → central bus; from the central bus T2 (Y on HV side, Δ on LV side) → G2; and line Section 2, j100 Ω → T3 (Y grounded on HV side, Δ on LV side) → G3.]
Answer
All reactances are converted to a common base of 50 MVA; base voltages follow the transformer line-to-line ratios starting from 13.8 kV at G1.
Base values
- G1 zone: kV
- Line zone (T1 13.8/220 kV): kV,
- G2 zone: T2 is a Y–Δ bank of 127/18 kV units, line-to-line ratio kV, so kV
- G3 zone (T3 220/22 kV): kV
Formula:
Per-unit values
| Element | X (pu, 50 MVA base) |
|---|---|
| G1 | 0.5000 |
| G2 | 0.3333 |
| G3 | 0.2755 |
| T1 | 0.2000 |
| T2 | 0.1667 |
| T3 | 0.1429 |
| Line section 1 (j80 Ω) | 0.0826 |
| Line section 2 (j100 Ω) | 0.1033 |
Reactance diagram
j0.2 j0.0826 j0.1033 j0.1429
+-/\/\/--/\/\/---+------/\/\/------/\/\/--+
| T1 L1 | L2 T3 |
j0.5 j0.1667 (T2) j0.2755
| | |
(E1) j0.3333 (E3)
| | |
| (E2) |
| | |
+----------------+------------------------+
reference (neutral) bus
Answer: , , , , , , and pu on 50 MVA, with base voltages 13.8, 220, 18 and 22 kV.
- 2075 Baisakh · 4 marks
A single phase voltage source with V = 100∠0° volts delivers a current I = 10∠10° A, which leaves the positive terminal of the source. Calculate the source real and reactive power and state whether the source delivers or absorbs each of these.
Answer
Complex power delivered by a source whose current leaves its positive terminal is (generator convention). A positive P or Q then means the source delivers it; a negative value means it absorbs it.
- W: positive, so the source delivers real power.
- var: negative, so the source absorbs 173.65 var (equivalently it delivers var).
The current leads the voltage by 10°, so the load connected to the source is capacitive; a capacitive load supplies reactive power, which flows back into the source.
Answer: P = 984.8 W delivered; Q = 173.6 var absorbed by the source.
- 2075 Bhadra · 8 marks
A 90 MVA, 11 kV 3-phase generator has a reactance of 25%. The generator supplies two motors through transformers and transmission line shown in figure below. The transformer T1 is a 3-phase, 100 MVA, 10/132 kV, 6% reactance. The transformer T2 is composed of three single phase units each rated at 30 MVA, 66/10 kV with 5% reactance. The connection of T1 and T2 are shown in figure. The motors are rated at 50 MVA and 40 MVA, both 10 kV and 20% reactance. Taking the generator rating as base, draw the per unit reactance diagram. The reactance of the line is 100 Ω. [Figure: G1 → T1 (Δ on generator side, Y grounded on line side) → Line → T2 (Y grounded on line side, Δ on motor side) → bus feeding M1 (Y, grounded) and M2 (Δ).]
Answer
Base: 90 MVA and 11 kV in the generator circuit (generator rating). Base voltages in other zones follow the line-to-line turns ratios.
Base voltages
- Generator zone: kV
- Line zone (T1 is 10/132 kV): kV
- T2: three single-phase 66/10 kV units connected Y (line side) – Δ (motor side), so line-to-line ratio is kV. Motor zone:
Per-unit reactances (on 90 MVA)
| Element | X (pu, 90 MVA base) |
|---|---|
| Generator | 0.2500 |
| T1 | 0.0446 |
| Line (100 Ω) | 0.4269 |
| T2 | 0.0310 |
| Motor M1 | 0.2231 |
| Motor M2 | 0.2789 |
Reactance diagram
j0.0446 j0.4269 j0.0310
+---/\/\/-----/\/\/-----/\/\/---+--------+
| T1 line T2 | |
j0.25 j0.2231 j0.2789
| | |
(Eg) (Em1) (Em2)
| | |
+-------------------------------+--------+
reference bus
Answer: On 90 MVA base: , , , , , pu; base voltages 11 kV, 145.2 kV and 12.70 kV.
- 2074 Bhadra · 6 marks
Two ideal voltage sources designated as machine 1 and 2 are connected as shown in figure below. If E1 = 100∠0° V and E2 = ∠30° V and Z = 0.5 + j5 Ω, determine (i) whether each machine is generating or consuming real power and the amount, (ii) whether each machine is receiving or supplying reactive power and the amount, and (iii) the P and Q absorbed by the impedance. [Figure: source E1 on the left and source E2 on the right, connected through series impedance Z = 0.5 + j5 Ω; current I flows from E1 towards E2.]
Answer
The magnitude of is not printed; it is taken as 100 V, i.e. V (the usual textbook data).
Current I flows from machine 1 to machine 2. With this direction:
- is the power supplied by machine 1 (current leaves its + terminal).
- is the power absorbed by machine 2 (current enters its + terminal).
Current
(i) and (ii) Machine powers
| Machine | P | Q |
|---|---|---|
| 1 ( = supplied) | W, so it consumes 963.57 W (motor) | var, so it supplies 364.31 var |
| 2 ( = absorbed) | W absorbed, so it generates 1016.63 W | var absorbed, so it supplies 166.29 var |
(iii) Power absorbed by the impedance
Check: P: W. Q: var. Both balance.
Real power flows from machine 2 to machine 1 because leads . Both machines supply reactive power, and all of it is used up in the line reactance.
Answer: Machine 1 consumes 963.6 W and supplies 364.3 var. Machine 2 generates 1016.6 W and supplies 166.3 var. The impedance absorbs 53.1 W and 530.6 var.
- 2074 Bhadra · 8 marks
A one-line diagram of a three-phase power system is shown in figure below. Compute the per unit values taking generator rating as the base in the generator circuit and draw the impedance diagram of the power system shown in figure below. The system has the following data: G1: 25 MVA, 13.8 kV, X = 0.15 p.u.; T1: 30 MVA, 13.2/115 kV, X = 0.11 p.u.; T2: Three single units each rated 10 MVA, 69Y/13.2Δ kV, X = 0.11 p.u.; M1: 15 MVA, 13 kV, X = 0.15 p.u.; M2: 10 MVA, 13 kV, X = 0.15 p.u.; Series impedance of transmission line: Z = 20 + j65 Ω. [Figure: G1 → T1 (Δ on generator side, Y grounded on line side) → transmission line → T2 (Y grounded on line side, Δ on motor side) → bus feeding motors M1 (Y, grounded) and M2 (Y, grounded).]
Answer
Base: 25 MVA and 13.8 kV in the generator circuit. T2 is read as three single-phase units of 69/13.2 kV connected Y (line side) – Δ (motor side).
Base voltages
- Generator zone: kV
- Line zone (T1 13.2/115 kV): kV
- T2 line-to-line ratio: kV. Motor zone: kV
Per-unit values (25 MVA base)
| Element | Base kV | pu value |
|---|---|---|
| G1 | 13.8 | j0.15 |
| T1 | 13.8 | j0.0839 |
| Line | 120.23 | 0.0346 + j0.1124 |
| T2 (30 MVA bank) | 13.28 | j0.0906 |
| M1 | 13.28 | j0.2396 |
| M2 | 13.28 | j0.3594 |
Impedance diagram
j0.0839 0.0346+j0.1124 j0.0906
+--/\/\/-------/\/\/--------/\/\/--+-------+
| T1 line T2 | |
j0.15 j0.2396 j0.3594
| | |
(Eg) (Em1) (Em2)
| | |
+----------------------------------+-------+
reference bus
Answer: , , , , , pu (25 MVA; 13.8 / 120.23 / 13.28 kV).
- 2073 Bhadra · 4 marks
Define the meaning of complex power in power system. Explain the sign conventions of power for sources and loads.
Answer
Complex power is the phasor product of voltage and the conjugate of current. Its real part is the active power and its imaginary part is the reactive power:
- (W), the average power converted to work or heat.
- (var), the power that oscillates between source and the fields of L and C.
- (VA), the apparent power. Equipment is rated in VA.
- is the power-factor angle. Q is positive for a lagging (inductive) current.
Sign conventions
Load (motor) convention: the current enters the positive terminal. is then the power absorbed.
- P > 0: the element absorbs real power (resistor, motor).
- Q > 0: it absorbs reactive power (inductor, lagging load).
- Q < 0: it supplies reactive power (capacitor).
Source (generator) convention: the current leaves the positive terminal. is then the power delivered.
- P > 0: the source delivers real power (generator action). P < 0 means it absorbs P (motor action).
- Q > 0: it delivers reactive power (over-excited machine). Q < 0 means it absorbs Q.
Load convention Source convention
I --> + + --> I
+------o o------+
| Load | S absorbed | Src | S delivered
+------o o------+
- -
| Element | P | Q (load convention) |
|---|---|---|
| Resistor | + | 0 |
| Inductor | 0 | + (absorbs) |
| Capacitor | 0 | − (supplies) |
| Induction motor | + | + |
Example: V and the current leaving the + terminal is A. Then VA, so the source delivers 433 W and 250 var.
- 2073 Bhadra · 10 marks
Develop the reactance diagram of the following network and express all the parameters in p.u. values based on power 1000 kVA and base voltage of 11 kV at low voltage side: G1: 1000 kVA, 11 kV, X = 2.5%; G2: 500 kVA, 11 kV, X = 0.1%; Tr-1: 1000 kVA, 11 kV/66 kV, X = 2%; Tr-2: 500 kVA, 12.5 kV/75 kV, X = 2%; Tr-3: 1500 kVA, 66 kV/400 kV, X = 2%; TL: 10 Ω/phase. If the load draws a current of 1200 A, calculate the current supplied by G1 and G2.
Answer
No figure is printed, so the usual arrangement is assumed: G1–Tr1 and G2–Tr2 feed a common 66 kV bus; from it the line TL and Tr3 (66/400 kV) supply the load. The two generator emfs are taken as equal, so the load current divides between the two generator branches in inverse ratio of their impedances. The 1200 A load current is taken as referred to the 11 kV level, since its voltage level is not stated.
G1--Tr1(11/66)--+
|66 kV bus
G2--Tr2(12.5/75)+--TL(10 ohm)--Tr3(66/400)--Load
Base values ( = 1000 kVA)
- G1 side: 11 kV (given). 66 kV bus: kV.
- G2 side through Tr2: kV.
- Load side: kV.
- at 66 kV . at 11 kV A.
Per-unit reactances
| Element | X (pu, 1000 kVA) |
|---|---|
| G1 | 0.0250 |
| G2 | 0.0020 |
| Tr-1 | 0.0200 |
| Tr-2 | 0.0517 |
| TL | 0.0023 |
| Tr-3 | 0.0133 |
Reactance diagram
j0.025 j0.02
+-/\/\/--/\/\/--+
| G1 Tr1 | j0.0023 j0.0133
(E1) +---/\/\/----/\/\/---> Load
| G2 Tr2 | TL Tr3
+-/\/\/--/\/\/--+
j0.002 j0.0517
(E1, E2 return to the common reference bus)
Current shared by G1 and G2
Branch impedances: pu and pu.
(In per unit the load current is pu. G1 carries 12.43 pu and G2 carries 10.43 pu.)
Answer: G1 supplies about 652.6 A and G2 about 547.4 A (54.4 % and 45.6 % of the load current).
Note: if the G2 reactance of 0.1 % is a misprint for 10 %, then pu, pu, and the shares become 1018.0 A (G1) and 182.0 A (G2).
- 2073 Magh · 10 marks
Compute the per unit values taking power base of 30 MVA and 6.6 kV in the circuit of generator G1 and draw the reactance diagram of a power system shown in figure below. The system has the following data: G1: 25 MVA, 6.6 kV, X = 0.2 p.u.; G2: 15 MVA, 6.6 kV, X = 0.15 p.u.; M: 30 MVA, 13.2 kV, X = 0.15 p.u.; T1: 30 MVA, 6.6/115 kV, X = 0.1 p.u.; T2: 15 MVA, 6.6/115 kV, X = 0.1 p.u. [Figure: G1 (Y, grounded) → T1 (Y grounded–Y grounded) → bus; Line-1 from this bus to a junction; Line-3 from the junction to a bus feeding T3 (Y grounded on line side, Δ on motor side) → motor M; Line-2 from the junction down to a bus feeding T2 (grounded windings) → G2 (Y, grounded). No line impedances or T3 rating are printed.]
Answer
Base: 30 MVA and 6.6 kV in the G1 circuit. The line impedances and the T3 rating are not printed, so T3 is assumed to be 30 MVA, 115/13.2 kV, X = 0.1 pu, and the line reactances are kept as symbols (Ω).
Base voltages
- G1 zone: 6.6 kV
- Line zone (T1 6.6/115 kV): 115 kV,
- G2 zone (T2 115/6.6 kV): 6.6 kV
- Motor zone (T3 115/13.2 kV): 13.2 kV
Per-unit values (30 MVA base)
For example, a line reactance of 100 Ω would be pu.
| Element | X (pu, 30 MVA) |
|---|---|
| G1 | 0.24 |
| G2 | 0.30 |
| Motor M | 0.15 |
| T1 | 0.10 |
| T2 | 0.20 |
| T3 (assumed) | 0.10 |
| Lines 1, 2, 3 |
Reactance diagram
j0.10 jXL1 jXL3 j0.10
+---/\/\/---/\/\/--+--/\/\/---/\/\/---+
| T1 Line1 | Line3 T3 |
j0.24 | j0.15
| jXL2 (Line2) |
(E1) | (Em)
| j0.20 (T2) |
| | |
| j0.30 (G2) |
| | |
| (E2) |
+------------------+------------------+
reference (neutral) bus
Answer: , , , , , pu, and each line pu on the 30 MVA, 115 kV base.
- 2072 Asoj · 6 marks
Two ideal voltage sources designated as machine 1 and 2 are connected as shown in figure. If E1 = 120∠10° V, E2 = 120∠30° V and Z = 1 + j5 Ω, determine: (i) whether each machine is consuming P and Q or generating P and Q (ii) P and Q absorbed by the impedance (iii) direction of power flow. [Figure: source E1 on the left and source E2 on the right, both with + terminal at top, connected through series impedance Z; current I flows from E1 towards E2.]
Answer
Take I flowing from machine 1 to machine 2 through Z. Then is the power supplied by machine 1 and is the power absorbed by machine 2.
Current
(i) Machine powers
| Machine | Real power | Reactive power |
|---|---|---|
| 1 | supplies −913.73 W, so it consumes 913.73 W (motor) | generates 356.43 var |
| 2 | absorbs −980.53 W, so it generates 980.53 W (generator) | consumes 22.42 var |
(ii) Power absorbed by Z
Check: W and var.
(iii) Direction of power flow
- Real power flows from machine 2 to machine 1, because leads by 20°. Real power flows from the leading-angle end to the lagging end.
- Reactive power flows from machine 1 towards machine 2. Machine 1 supplies 356.43 var: 334.01 var is used in the line reactance and 22.42 var reaches machine 2. The magnitudes are equal here, so Q is decided by the angle and the R/X of the line.
Answer: Machine 1 is a motor drawing 913.7 W and supplying 356.4 var. Machine 2 generates 980.5 W and draws 22.4 var. Z absorbs 66.8 W and 334.0 var. P flows 2 → 1.
- 2072 Asoj · 4 marks
Draw the p.u. impedance diagram for the system shown below. [Figure: G (6.6 kV, 20 MVA, X = 0.15 p.u.) → T1 (11/132 kV, 25 MVA, X = 0.1 p.u.) → line 10 + j60 Ω → T2 (132/11 kV, 20 MVA, X = 0.1) → motor M (11 kV, 15 MVA, X = 0.15 p.u.).]
Answer
Choose the generator rating as base: 20 MVA, 6.6 kV in the generator circuit. (The 6.6 kV generator feeds the 11 kV winding of T1, so the transformer and motor values need voltage correction.)
Base voltages
- Generator zone: kV
- Line zone (T1 11/132 kV): kV
- Motor zone (T2 132/11 kV): kV
Per-unit values
Impedance diagram
j0.2222 0.0319+j0.1913 j0.2778
+---/\/\/-------/\/\/--------/\/\/---+
| T1 line T2 |
j0.15 j0.5556
| |
(Eg) (Em)
| |
+------------------------------------+
reference bus
Answer: On 20 MVA (base 6.6 / 79.2 / 6.6 kV): , , , , pu.
- 2072 Magh · 6 marks
Figure below shows a single line diagram of a power system. The ratings of the generators and transformers are given below: G1: 25 MVA, 6.6 kV, XG1 = 0.20 pu; G2: 15 MVA, 6.6 kV, XG2 = 0.15 pu; G3: 30 MVA, 13.2 kV, XG3 = 0.15 pu; T1: 30 MVA, 6.6Δ–115Y kV, XT1 = 0.10 pu; T2: 15 MVA, 6.6Δ–115Y kV, XT2 = 0.10 pu; T3: single phase units each rated 10 MVA, 6.9/69 kV, XT3 = 0.10 pu. Draw the per unit circuit diagram using base values of 30 MVA and 6.6 kV in the circuit of generator 1. [Figure: G1 (25 MVA, 6.6 kV, Y grounded) → T1 (Δ–Y grounded, 6.6/115 kV) → Line-1 j120 Ω → junction bus; from the junction T2 (Δ–Y grounded, 6.6/115 kV) up to G2 (15 MVA, 6.6 kV, Y grounded); and Line-2 j90 Ω → T3 (Y–Y grounded, √3×69/√3×6.9 kV) → G3 (30 MVA, 13.2 kV, Y grounded).]
Answer
Base: 30 MVA, 6.6 kV in the G1 circuit. Base voltages change by the line-to-line turns ratio of each transformer.
Base voltages
- G1 zone: 6.6 kV
- Line zone (T1 6.6/115 kV): 115 kV,
- G2 zone (T2 115/6.6 kV): 6.6 kV
- G3 zone: T3 is a Y–Y bank of 6.9/69 kV single-phase units, so its line-to-line ratio is kV, i.e. 10 : 1:
Per-unit values (30 MVA base)
| Element | Base kV | X (pu) |
|---|---|---|
| G1 | 6.6 | 0.2400 |
| G2 | 6.6 | 0.3000 |
| G3 | 11.5 | 0.1976 |
| T1 | 6.6/115 | 0.1000 |
| T2 | 6.6/115 | 0.2000 |
| T3 | 115/11.5 | 0.1080 |
| Line-1 | 115 | 0.2722 |
| Line-2 | 115 | 0.2042 |
Per-unit circuit
j0.10 j0.2722 j0.2042 j0.108
+--/\/\/---/\/\/----+----/\/\/-----/\/\/---+
| T1 Line-1 | Line-2 T3 |
j0.24 j0.20 (T2) j0.1976
| | |
(E1) j0.30 (G2) (E3)
| | |
| (E2) |
+-------------------+----------------------+
reference (neutral) bus
Answer: , , , , , , , pu.
- 2072 Magh · 4 marks
What is complex power? Why is complex power taken as VI* rather than V*I in power systems? Explain.
Answer
Complex power is , the phasor quantity whose real part is the active power (W), whose imaginary part is the reactive power (var) and whose magnitude is the apparent power (VA). It is defined as .
Why
Let and . The power-factor angle is .
- Both give the same P. Only the sign of Q differs.
- Sign agreement with the accepted convention. With , a lagging (inductive) load (, ) gives . Inductive loads "absorb" vars and capacitors "supply" vars. This is the convention adopted by IEEE/IEC and used in load-flow studies, generator capability charts and var meters. With , an inductive load would show negative Q, which conflicts with the convention.
- Consistency with impedance. With , inductive reactance (+X) gives +Q. The power triangle is then the impedance triangle scaled by . With the triangle would be the mirror image of the impedance triangle.
- Independence from reference. Taking the conjugate removes the absolute phase angles and keeps only the difference . So S does not depend on which phasor is chosen as reference. ( without a conjugate would give the angle , which changes with the reference and has no meaning.)
Im(Q)
^ S = VI*
| /
| / Q = |V||I| sin(phi) > 0
| / phi (lagging load)
+----------> Re (P)
Example: V and A (lagging). Then VA, which is correct: the load absorbs 500 var. But VA would wrongly suggest that the inductive load supplies vars.
- 2072 Magh · 6 marks
Two 3-phase synchronous generators connected in star with neutral grounded are connected to each other through a line with series impedance per phase of 2 + j8 Ω. The terminal voltages of generators 1 and 2 are 200∠30° V and 210∠50° V respectively. Determine the active and reactive power generated/consumed by each generator.
Answer
The given terminal voltages are taken as per-phase (line-to-neutral) values, since the generators are star connected with neutral grounded and the impedance is per phase. Three-phase power is 3 times the per-phase power.
Let I flow from G1 to G2 through . Then is the power delivered by G1 and is the power received by G2.
Current
Powers per phase
Interpretation
| Quantity | Per phase | Three-phase |
|---|---|---|
| G1 real power | consumes 1674.31 W (motoring) | consumes 5022.92 W |
| G1 reactive power | generates 485.19 var | generates 1455.57 var |
| G2 real power | generates 1826.24 W | generates 5478.73 W |
| G2 reactive power | generates 122.55 var | generates 367.66 var |
| Line loss | 151.94 W, 607.74 var | 455.81 W, 1823.23 var |
Check: W and var.
Real power flows from G2 to G1 because leads by 20°. G1 behaves as a synchronous motor. Both machines supply reactive power, which is consumed by the line reactance.
Answer: G2 generates 5.48 kW and 0.37 kvar. G1 absorbs 5.02 kW (motor) and generates 1.46 kvar. The line absorbs 0.46 kW and 1.82 kvar (three-phase totals).
- 2071 Bhadra · 6 marks
Determine the amount of power generated by each of the generators in the power system network below. Also specify the direction of power flow in the network. [Figure: E1 = 1.05∠5° pu behind reactance j0.08 pu, connected through a line of resistance 0.025 pu and reactance j0.1 pu to E2 = 1.05∠20° pu behind reactance j0.08 pu.]
Answer
The two internal reactances and the line form one series path between the two emfs:
Let I flow from to . Then is the power generated by G1 and is the power absorbed by G2.
j0.08 0.025+j0.1 j0.08
+-/\/\/-----/\/\/-------/\/\/-+
| I --> |
(E1) 1.05/5 deg 1.05/20 deg (E2)
| |
+-----------------------------+
Current
Powers
| Generator | Real power | Reactive power |
|---|---|---|
| G1 | absorbs 1.0737 pu (acts as motor) | generates 0.2477 pu |
| G2 | generates 1.1012 pu | generates 0.0386 pu |
Check: pu (I²R loss) and pu (I²X).
Direction of power flow
- Real power flows from G2 to G1, since leads by 15°.
- Both generators supply reactive power to the network, and it is consumed in the series reactances. With equal emf magnitudes, each machine supplies part of the .
Answer: G2 generates 1.101 pu real power and G1 receives 1.074 pu. The loss is 0.0275 pu. G1 and G2 supply 0.248 pu and 0.039 pu reactive power. P flows G2 → G1.
- 2071 Bhadra · 6 marks
Draw the per-unit reactance diagram for the power system shown below, choosing suitable base values. G1: 25 kV, 20 MVA, 20%; G2: 25 kV, 30 MVA, 30%; T1: 50 MVA, 33/220 kV, 15%; T2: 50 MVA, 220/11 kV; M1: 20 MVA, 11 kV, 30%; M1: 30 MVA, 11 kV, 20% (second motor, printed as M1). [Figure: G1 and G2 in parallel on a bus → T1 → line j50 Ω/phase → T2 → bus feeding motors M1 and M2.]
Answer
Choice of base: 50 MVA (transformer rating) and 220 kV on the line. Then the generator side base is 33 kV (T1 33/220 kV) and the motor side base is 11 kV (T2 220/11 kV). The reactance of T2 is not printed; it is assumed to be 15 % on its own rating (same as T1).
Per-unit reactances (50 MVA base)
| Element | Base kV | X (pu) |
|---|---|---|
| G1 (20 MVA, 25 kV) | 33 | 0.2870 |
| G2 (30 MVA, 25 kV) | 33 | 0.2870 |
| T1 | 33/220 | 0.1500 |
| Line (j50 Ω) | 220 | 0.0517 |
| T2 (assumed 15 %) | 220/11 | 0.1500 |
| M1 (20 MVA) | 11 | 0.7500 |
| M2 (30 MVA) | 11 | 0.3333 |
Reactance diagram
j0.15 j0.0517 j0.15
+--+---/\/\/---/\/\/-----/\/\/---+------+
| | T1 line T2 | |
j0.287 j0.287 j0.75 j0.3333
| | | |
(E1)(E2) (Em1) (Em2)
| | | |
+--+-----------------------------+------+
reference bus
Answer: On 50 MVA with 33 / 220 / 11 kV bases: , , , (assumed), , pu.
- 2071 Magh · 5 marks
Two ideal 3-phase synchronous machines A and B are connected by a series impedance of 0 + j5 Ω per phase. The voltages at the two machines are 100∠0° and 120∠30° V respectively. Calculate and analyze the direction of power flow in the system.
Answer
Take the voltages as per-phase values. Let I flow from A to B. Then is the power supplied by A and is the power received by B.
Current
Powers per phase
Check with the lossless-line formula: W.
Analysis
| Machine | Real power | Reactive power |
|---|---|---|
| A | supplies −1200 W, so it receives 1200 W (motor) | supplies −78.46 var, so it receives 78.46 var |
| B | receives −1200 W, so it generates 1200 W | receives −801.54 var, so it supplies 801.54 var |
| Link (j5 Ω) | 0 W (no resistance) | absorbs 723.08 var |
- Real power flows from B to A because leads by 30°. There is no resistance, so A receives exactly what B sends.
- Reactive power flows from B (higher voltage, 120 V) to A (lower voltage, 100 V). B supplies 801.54 var: 723.08 var is used in the link and 78.46 var reaches A.
- Three-phase totals (×3): 3600 W from B to A; B supplies 2404.6 var; the link absorbs 2169.2 var; A receives 235.4 var.
Answer: B is the generator and sends 1200 W per phase (3.6 kW total) to A, which acts as a motor. Q flows from B to A: B supplies 801.5 var, the link uses 723.1 var, and A receives 78.5 var (per phase).
- 2071 Magh · 6 marks
Starting from voltage and current phasors, derive the expression for complex power. Construct the phasor diagram of complex power and explain the significance of the components.
Answer
Complex power S is the phasor product of the voltage and the conjugate of the current. Its real part is the average (active) power and its imaginary part is the reactive power.
Derivation
Let the instantaneous voltage and current be
The instantaneous power is
Here , and .
- The first term has average . This is the active power.
- The second term has zero average and peak . This is the reactive power.
In phasor form, and . Then
For a load : .
Phasor diagram and power triangle
V reference (lagging load) Power triangle
---------------> V /|
\ phi S / | Q = |V||I|sin(phi)
\ / |
\ I (lags V) / phi |
v +-------+
P = |V||I|cos(phi)
Multiplying V by the conjugate of I turns the V–I phasor diagram into a right-angled triangle. The hypotenuse is , the base is P, the height is Q, and the angle is .
Significance of the components
| Component | Unit | Meaning |
|---|---|---|
| P (real part) | W | Average power converted to useful work and losses. It is what energy meters record. |
| Q (imaginary part) | var | Power exchanged back and forth with magnetic and electric fields. It is needed for magnetising and sets the voltage levels, but does no net work. |
| VA | Sets the current and the rating of generators, transformers and cables | |
| , | — | Power factor: the share of S that is useful power |
- Q > 0 means a lagging (inductive) load and Q < 0 a leading (capacitive) load.
- A low power factor means more current for the same P. This causes more loss, more voltage drop and larger equipment. So utilities add capacitors to reduce Q.
Example: V and A give VA, with pf 0.8 lagging.
- 2070 Bhadra · 6 marks
Determine the amount of power generated by each of the generators in the power system network below. Also specify the direction of power flow in the network. [Figure: E1 = 1.1∠15° pu behind reactance j0.1 pu, connected through a line of resistance 0.03 pu and reactance j0.1 pu to E2 = 1.1∠0° pu behind reactance j0.1 pu.]
Answer
Total series impedance between the two emfs:
Let I flow from to . Then is the power generated by G1 and is the power received by G2.
j0.1 0.03+j0.1 j0.1
+-/\/\/-----/\/\/-------/\/\/-+
| I --> |
(E1) 1.1/15 deg 1.1/0 deg (E2)
| |
+-----------------------------+
Current
Powers
| Generator | Real power | Reactive power |
|---|---|---|
| G1 | generates 1.0472 pu | generates 0.0327 pu |
| G2 | receives 1.0200 pu (acts as motor) | received = −0.2394, so it generates 0.2394 pu |
Check: pu and pu.
Direction of power flow
- Real power flows from G1 to G2, because leads by 15°. G1 is generating and G2 is motoring.
- Both machines supply reactive power to the network, and it is all consumed in the series reactances ( pu).
Answer: G1 generates 1.047 pu of real power. G2 receives 1.020 pu. The line and reactances absorb 0.027 pu. Reactive power supplied is 0.033 pu by G1 and 0.239 pu by G2. P flows G1 → G2.
- 2070 Magh · 6 marks
Two ideal voltage sources designated as machines 1 and 2 are connected to each other via a line with impedance of 0 - j5 Ω. If E1 = 100∠0° V and E2 = 100∠30° V, determine the magnitude and the direction of power flow.
Answer
The line impedance is a pure capacitive reactance. Let I flow from machine 1 to machine 2. Then is the power supplied by machine 1 and is the power received by machine 2.
Current
Powers
Check with using : W, from 1 to 2.
Magnitude and direction
| Quantity | Result |
|---|---|
| Real power | 1000 W flows from machine 1 to machine 2 (1 generates, 2 consumes) |
| Machine 1 reactive | var, so it absorbs 267.95 var |
| Machine 2 reactive | receives +267.95 var, so it absorbs 267.95 var |
| Capacitive line | generates 535.90 var (= 267.95 + 267.95) |
Note: with an inductive link, real power flows from the leading machine (2) to the lagging one. A capacitive link reverses this, so power flows from machine 1 to machine 2 even though leads. The line capacitance supplies reactive power equally to both ends, because the voltage magnitudes are equal.
Answer: P = 1000 W flows from machine 1 to machine 2. Each machine absorbs 267.95 var, all supplied by the capacitive line (535.9 var).
- 2070 Magh · 8 marks
Compute the per unit values taking a common base and draw the impedance diagram of a power system shown in figure below. The system has the following data: Generators: G1: 25 MVA, 6.6 kV, X = 0.2 p.u.; G2: 15 MVA, 6.6 kV, X = 0.15 p.u.; G3: 30 MVA, 13.2 kV, X = 0.15 p.u. Transformers: T1: 30 MVA, 6.6/115 kV, X = 0.1 p.u.; T2: 15 MVA, 6.6/115 kV, X = 0.1 p.u.; T3: three 1-ph units of 10 MVA, 69/6.9 kV, X = 0.4 p.u. [Figure: G1 (Y, grounded) → T1 (Δ–Y grounded) → line j100 Ω → junction bus; from the junction T2 (Y grounded on bus side, Δ on generator side) up to G2; and line j130 Ω → T3 (Y–Y, grounded) → G3 (Y, grounded).]
Answer
Common base: 30 MVA, 6.6 kV in the G1 circuit. Base voltages in other zones follow the line-to-line ratios.
Base voltages
- G1 zone: 6.6 kV
- Line zone (T1 6.6/115 kV): 115 kV,
- G2 zone (T2 115/6.6 kV): 6.6 kV
- G3 zone: T3 is a Y–Y bank of 69/6.9 kV units, so the line-to-line ratio is 119.5/11.95 kV (10 : 1). Then kV
Per-unit values (30 MVA)
| Element | X (pu, 30 MVA) |
|---|---|
| G1 | 0.2400 |
| G2 | 0.3000 |
| G3 | 0.1976 |
| T1 | 0.1000 |
| T2 | 0.2000 |
| T3 | 0.4320 |
| Line j100 Ω | 0.2268 |
| Line j130 Ω | 0.2949 |
Impedance diagram
j0.10 j0.2268 j0.2949 j0.432
+--/\/\/---/\/\/----+----/\/\/-----/\/\/---+
| T1 line 1 | line 2 T3 |
j0.24 j0.20 (T2) j0.1976
| | |
(E1) j0.30 (G2) (E3)
| | |
| (E2) |
+-------------------+----------------------+
reference (neutral) bus
Answer: , , , , , , , pu (base 30 MVA; 6.6 / 115 / 6.6 / 11.5 kV).
- 2069 Bhadra · 6 marks
Construct a reactance diagram for the system given below and express all the reactances in per unit system. G1, G2: 10 MVA, 11.5 kV, 10%; G3: 15 MVA, 11.5 kV, 12%; T1, T2: 10 MVA, 11/66 kV, 10%; T3: 15 MVA, 11/66, 15%; T4: 35 MVA, 66/11 kV, 18%; L1 = L2 = L3 = L4 = j20 Ω/ph. [Figure: G1 (bus 1) → T1 → bus 2; G2 (bus 3) → T2 → bus 4; line L2 from bus 2 to bus 6, L1 from bus 2 to bus 4, L3 from bus 4 to bus 7, L4 from bus 6 to bus 7; T3 between bus 6 and bus 5 feeding G3; T4 between bus 7 and bus 8 feeding motor M (no motor rating printed).]
Answer
Choice of base: 10 MVA, with 11 kV in the generator circuits (the transformer LV rating) and 66 kV on the lines. The motor rating is not printed, so its reactance is left as (pu on its own rating). Its value on the common base is .
Per-unit reactances (10 MVA base)
| Element | X (pu, 10 MVA) |
|---|---|
| G1, G2 | 0.1093 each |
| G3 | 0.0874 |
| T1, T2 | 0.1000 each |
| T3 | 0.1000 |
| T4 | 0.0514 |
| L1 to L4 | 0.0459 each |
Reactance diagram
(E1)-j0.1093-[1]-j0.10-[2]---j0.0459(L2)---[6]
| |
j0.0459(L1) j0.0459(L4)
| |
(E2)-j0.1093-[3]-j0.10-[4]---j0.0459(L3)---[7]
[6]-j0.10(T3)-[5]-j0.0874-(E3)
[7]-j0.0514(T4)-[8]-jXM-(Em)
All sources (E1, E2, E3, Em) return to the
common reference (neutral) bus.
Answer: On 10 MVA (11 kV / 66 kV bases): , , , , and each line 0.0459 pu.
- 2069 Poush · 6 marks
Two 50 Hz, 3-phase synchronous machines are connected to each other via a line with series impedance of 3 + j10 Ohm/phase. Determine the direction of active and reactive power flow in the line and power generated/consumed by each of these machines. The terminal phase voltages of machines 1 and 2 are 3.81∠0° kV and 3.81∠-18° kV respectively.
Answer
Let I flow from machine 1 to machine 2 through . Then is the power delivered by machine 1 and is the power received by machine 2 (per phase; three-phase = 3 × per phase).
Current
Powers per phase
Check: kW and kvar.
Results
| Quantity | Per phase | Three-phase |
|---|---|---|
| Machine 1, P | generates 431.09 kW | 1293.26 kW |
| Machine 1, Q | , so it absorbs 58.28 kvar | 174.84 kvar |
| Machine 2, P | consumes 391.98 kW (motor) | 1175.94 kW |
| Machine 2, Q | receives −188.64, so it generates 188.64 kvar | 565.92 kvar |
| Line loss | 39.11 kW, 130.36 kvar | 117.33 kW, 391.08 kvar |
Direction of flow
- Active power flows from machine 1 to machine 2, because leads by 18°.
- Reactive power flows from machine 2 towards machine 1. Machine 2 supplies 188.64 kvar: 130.36 kvar is used in the line reactance and 58.28 kvar reaches machine 1. Both voltage magnitudes are equal, so the flow of Q depends on the angle and on the line resistance.
Answer: Machine 1 is the generator (1293.3 kW, three-phase) and machine 2 the motor (1175.9 kW). The line loss is 117.3 kW. Q flows from machine 2 (565.9 kvar) to machine 1 (174.8 kvar received). The line absorbs 391.1 kvar.
- 2069 Poush · 4 marks
What is complex power? Show and explain the symmetry between the impedance triangle and power triangle.
Answer
Complex power is . Its real part P (W) is the active power, its imaginary part Q (var) is the reactive power, and its magnitude (VA) is the apparent power. The angle of S is the power-factor angle .
Symmetry with the impedance triangle
For a load carrying current I, . So
So , and . Every side of the impedance triangle is multiplied by the same real number . The power triangle is therefore similar to the impedance triangle:
Impedance triangle Power triangle
/| /|
|Z| / | X |S| / | Q = |I|^2 X
/ | / |
/phi| /phi|
+----+ +----+
R P = |I|^2 R
| Impedance triangle | Power triangle | Link |
|---|---|---|
| R | P | |
| X | Q | |
| angle | angle | same angle |
| same power factor |
Significance:
- The two triangles have the same angle. The power factor of a load can be found either from its impedance or from its powers.
- Inductive X (+) gives +Q (vars absorbed). Capacitive X (−) gives −Q (vars supplied). Both triangles flip below the axis together.
- This symmetry holds only because S is defined as . With , Q would be and the power triangle would be the mirror image of the impedance triangle.
Example: with A gives VA. Both triangles have angle 53.13° and pf 0.6 lagging.
- 2069 Poush · 8 marks
Compute the per unit values of a power system shown in figure below taking the common base of the generator. [Figure: G (100 MVA, 6 kV, X = 6%, Y grounded) → T1 (Δ–Y grounded, 120 MVA, 6.6/132 kV, X = 4%) → transmission line (10 + j50) Ω → T2 (Y grounded on line side, Δ on motor side, 120 MVA, 6.6/132 kV; no reactance printed) → bus feeding motors M1 (50 MVA, 6 kV, X = 6%) and M2 (40 MVA, 6 kV, X = 6%).]
Answer
Common base: 100 MVA, 6 kV in the generator circuit. The reactance of T2 is not printed; it is taken equal to T1, X = 4 % on 120 MVA, 6.6/132 kV (an identical transformer).
Base voltages
- Generator zone: kV
- Line zone (T1 6.6/132 kV): kV,
- Motor zone (T2 132/6.6 kV): kV
Per-unit values (100 MVA)
| Element | Base kV | pu value |
|---|---|---|
| G | 6 | j0.06 |
| T1 | 6 / 120 | j0.0403 |
| Line | 120 | 0.0694 + j0.3472 |
| T2 (assumed 4 %) | 120 / 6 | j0.0403 |
| M1 | 6 | j0.12 |
| M2 | 6 | j0.15 |
Impedance diagram
j0.0403 0.0694+j0.3472 j0.0403
+--/\/\/-------/\/\/--------/\/\/--+-------+
| T1 line T2 | |
j0.06 j0.12 j0.15
| | |
(Eg) (Em1) (Em2)
| | |
+----------------------------------+-------+
reference bus
Answer: , , , , pu on 100 MVA (6 / 120 / 6 kV).
- 2068 Bhadra · 3 marks
Mention the conditions and advantages of representing a 3-phase system by a single phase system.
Answer
A balanced three-phase system can be solved as a single-phase (per-phase) equivalent: one phase plus a neutral, using line-to-neutral voltages. The other two phases have the same results shifted by ±120°.
Conditions
- The sources are balanced: equal magnitudes and 120° apart, with positive sequence.
- The loads and network are balanced: equal impedance in each phase, and lines are fully transposed so that mutual effects are equal.
- The system operates in steady state under balanced (normal or three-phase symmetrical fault) conditions. Unbalanced faults need symmetrical components.
- Δ-connected elements are replaced by their equivalent Y (). Transformer phase shifts are ignored or added back later.
Under these conditions the neutral current is zero. So the neutral impedance carries no current and is left out of the per-phase circuit.
Advantages
- Calculation is reduced to one circuit instead of three coupled circuits. This saves time and effort.
- One-line (single-line) diagrams and per-phase impedance/reactance diagrams can be used.
- Per-unit quantities are the same for the per-phase and three-phase circuits, which makes the work simpler.
- Three-phase power is simply per-phase power: .
- It is used directly in load-flow, short-circuit (symmetrical fault) and stability studies.
- 2068 Bhadra · 5 marks
Draw a reactance diagram of the electric power system given below and express all reactances in per unit system by choosing appropriate base values. G1: 14 kV, 30 MVA, 10%; M: 11 kV, 25 MVA, 13%; T1: 66/11 kV, 25 MVA, 12%; T1: 13.8/66 kV, 25 MVA, 12% (as printed; one of these is T2). [Figure: G → T1 → line j18 Ohms/phase → T2 → motor M.]
Answer
The two transformers are read as T1: 13.8/66 kV (at the generator) and T2: 66/11 kV (at the motor), both 25 MVA, 12 %.
Choice of base: 25 MVA (transformer rating), 66 kV on the line. Then the base is 13.8 kV in the generator zone and 11 kV in the motor zone.
Per-unit reactances
| Element | Base kV | X (pu, 25 MVA) |
|---|---|---|
| G (30 MVA, 14 kV) | 13.8 | 0.0858 |
| T1 | 13.8/66 | 0.1200 |
| Line j18 Ω | 66 | 0.1033 |
| T2 | 66/11 | 0.1200 |
| Motor M | 11 | 0.1300 |
Reactance diagram
j0.12 j0.1033 j0.12
+----/\/\/----/\/\/------/\/\/----+
| T1 line T2 |
j0.0858 j0.13
| |
(Eg) (Em)
| |
+---------------------------------+
reference bus
Answer: On 25 MVA (13.8 / 66 / 11 kV): , , , , pu.
- 2068 Bhadra · 2+3 marks
How are generator and load complex powers expressed? What will happen if the convention of taking the conjugate of current is not followed? Explain with necessary derivation.
Answer
Generator and load complex power
Complex power is always written as . What it means depends on the assumed current direction.
- Generator (source) convention: the current leaves the + terminal. is the power delivered. For an over-excited generator supplying a lagging load, and .
- Load convention: the current enters the + terminal. is the power absorbed. For an inductive load : with .
At any bus, the net injected power is . This is the form used in load-flow studies.
If the conjugate is not taken
Let , and .
Case 1:
P is correct, but the sign of Q is reversed. An inductive (lagging) load would show negative Q, as if it were supplying vars like a capacitor. Generators and loads would then disagree with the standard convention used in meters, capability charts and load-flow programs. The power triangle would also become the mirror image of the impedance triangle ().
Case 2: (no conjugate at all)
The angle now depends on the sum of the phase angles. If the reference is changed by , then becomes . So P and Q would change just because a different phasor was chosen as reference, which is physically meaningless. Taking the conjugate makes S depend only on the difference , which is independent of the reference.
Example: V and A (lagging by 30°).
- VA. Correct: an inductive load absorbs 500 var.
- VA. Wrong sign of Q.
- here, but with V as reference (, ) it becomes . The result changes with the reference.
So the conjugate of current must be taken to get a unique, reference-independent S with the standard sign of Q.
- 2068 Bhadra · 6 marks
Two 3-phase synchronous machines are connected by an inductive link of j10 Ohms/phase. If the emfs of machine A and machine B are VA = 200∠10° V, VB = 200∠30° V, determine the direction of the reactive power flow and reactive power loss in the link. Neglect the voltage drops at both the machines.
Answer
Per phase, with I flowing from A to B through . Then is the power supplied by A and is the power received by B.
Current
Powers
Check: var.
Direction of reactive power
- Machine A supplies +241.23 var into the link.
- Machine B receives −241.23 var, so it also supplies 241.23 var into the link.
- So reactive power flows from both ends into the link. There is no net transfer of vars from one machine to the other, because the voltage magnitudes are equal (200 V each). Each machine supplies half of the link's .
- Real power: 1368.08 W per phase flows from B (leading, 30°) to A (lagging, 10°).
| Quantity | Per phase | Three-phase |
|---|---|---|
| Q supplied by A | 241.23 var | 723.69 var |
| Q supplied by B | 241.23 var | 723.69 var |
| Reactive loss in link | 482.46 var | 1447.38 var |
| Real power B → A | 1368.08 W | 4104.24 W |
Answer: Reactive power flows from both machines into the link, 241.2 var each per phase. The reactive loss in the link is 482.5 var per phase (1447.4 var for three phases).
- 2068 Magh · 6 marks
Two 3-phase synchronous machines A and B are connected by a link having series impedance of 0 + j10 Ohms/phase. The terminal voltages at machines A and B are 200∠0° V and 200∠15° V respectively. Compute the magnitude and direction of active power flow through the link.
Answer
For a purely reactive link the real power transfer is
and it flows from the machine with the leading angle to the one with the lagging angle.
Calculation (per phase)
The negative sign means the power actually flows from B to A.
Check with phasors:
So A receives 1035.28 W and B delivers 1035.28 W. The link has no resistance, so there is no real-power loss. Each machine supplies 136.30 var to the link ( var).
| Quantity | Per phase | Three-phase |
|---|---|---|
| Real power B → A | 1035.28 W | 3105.83 W |
| Reactive loss in link | 272.59 var | 817.78 var |
Answer: About 1.035 kW per phase (3.106 kW three-phase) flows from machine B to machine A. B acts as the generator and A as the motor, because leads by 15°.
- 2068 Magh · 6 marks
What are the major advantages of adopting the per unit system in electric power systems? Explain.
Answer
In the per-unit system every quantity is expressed as a fraction of a chosen base value: . One base MVA is used for the whole system, with a base kV in each voltage zone. Base current and base impedance follow from these: and .
Major advantages
- Transformers disappear from the circuit. With base voltages in the ratio of the transformer turns, a transformer's per-unit impedance is the same whether referred to the HV or LV side. The ideal transformer is removed, and the whole network becomes one simple per-unit circuit.
- Values lie in a narrow, familiar range. Machine reactances fall in known bands (for example transformer X ≈ 0.05–0.15 pu, synchronous ≈ 1–2 pu, ≈ 0.1–0.3 pu), whatever the size of the machine. Wrong data is easy to spot.
- Manufacturers give impedances in pu or % on the rating. Only a change of base is needed:
- No factors and no Y/Δ confusion. Per-unit values are the same for per-phase and three-phase quantities (for example ). So three-phase calculations become single-phase ones.
- Easy comparison. Voltage profiles are seen directly (for example 0.95–1.05 pu). Machines of different ratings can be compared, and losses and drops judged at a glance.
- Better computation. Numbers are of order 1, which avoids very large or very small values and reduces numerical error. Load-flow, fault and stability programs all work in pu.
- Simple equations. Many relations keep their form, for example and .
Example: a 50 MVA, 11/132 kV transformer with X = 10 % has pu. Referred to the HV side this is ; referred to the LV side it is . Both are the same 0.1 pu.
Questions from Old Question Collection (EE 555) (IOE EE 555 exam papers from 2068 Bhadra to 2080 Chaitra) and 2080 course papers (ENEE 205) (IOE ENEE 205 (2080 course) papers, 2081 Chaitra and 2082 Kartik). Answers are written for this site; check them against your class notes.
Chapter titles and hours from the IOE syllabus ↗