Short answer

Advantages include eliminating ideal transformers, unifying three-phase and single-phase calculations, and providing compact impedance ranges. Base power is chosen as a common MVA (e.g., 100 MVA); base voltage is set to rated voltage in one zone and propagated through transformers by their line-to-line voltage ratios.

List out the advantages of the per unit system. How are the base voltages and base power chosen?

Advantages of the per-unit system

  1. The p.u. impedance of a transformer is the same on the HV and LV sides, so ideal transformers vanish from the equivalent circuit.
  2. The p.u. impedances of similar equipment lie in a narrow band, whatever the rating. This makes it easy to check data and to assume typical values.
  3. Manufacturers give impedances in % or p.u. on the rating of the equipment, and these can be used directly.
  4. Line and phase quantities have the same p.u. value, and 3\sqrt3 factors disappear. Single-phase and three-phase calculations look alike.
  5. The numbers are near 1, which reduces arithmetic errors. It is easy to see abnormal conditions, for example V=0.9V = 0.9 p.u.
  6. It is ideal for computer studies (load flow, fault and stability analysis).

Choosing base power and base voltages

  1. Base power (SbS_b, MVA): Choose one value for the whole system. It is usually the rating of the largest machine or a round figure such as 100 MVA.
  2. Base voltage (VbV_b, kV): Choose it in one section, usually the generator or line section, often equal to that section's rated voltage.
  3. Other sections: Carry the base voltage through each transformer by its line-to-line voltage ratio:
Vb,new=Vb,old×Vrated, new sideVrated, old sideV_{b,new} = V_{b,old}\times\frac{V_{rated,\ new\ side}}{V_{rated,\ old\ side}}

For single-phase units in a Y–Δ bank, use the line voltage ratio (3V\sqrt3 V on the Y side).

  1. Derived bases:
Ib=Sb3Vb,Zb=Vb2SbI_b = \frac{S_b}{\sqrt3V_b},\qquad Z_b = \frac{V_b^2}{S_b}
  1. Change of base: Convert each equipment value to the common base:
Zpu,new=Zpu,old×Sb,newSb,old×(Vb,oldVb,new)2Z_{pu,new} = Z_{pu,old}\times\frac{S_{b,new}}{S_{b,old}}\times\left(\frac{V_{b,old}}{V_{b,new}}\right)^2

Example: Take Sb=100S_b = 100 MVA and 11 kV in the generator circuit, with an 11/132 kV transformer. The line base is 132 kV and Zb=1322/100=174.24 ΩZ_b = 132^2/100 = 174.24\ \Omega.