Per unit system and its advantages

Short answer

The per-unit system expresses quantities as fractions of chosen base values. Advantages: transformer impedances become identical on both sides, equipment impedances fall in narrow ranges, three-phase and single-phase calculations unify, and values near unity simplify analysis and error detection.

What is per unit system? What are the advantages of per unit representation?

In the per-unit system, every quantity (voltage, current, power, impedance) is expressed as a fraction of a chosen base value of the same unit:

per-unit value=actual valuebase value\text{per-unit value} = \frac{\text{actual value}}{\text{base value}}

Usually the base MVA (SbS_b) and the base kV (VbV_b) are chosen. The other bases follow from them:

Ib=Sb3Vb,Zb=Vb2SbI_b = \frac{S_b}{\sqrt3 V_b},\qquad Z_b = \frac{V_b^2}{S_b}

For example, at 100 MVA and 132 kV, Zb=174.24 ΩZ_b = 174.24\ \Omega, so a 50 Ω line has Z=0.287Z = 0.287 p.u.

Advantages

  1. Transformers disappear: The p.u. impedance of a transformer is the same on both sides, so the ideal transformers drop out of the equivalent circuit.
  2. Compact ranges: The p.u. impedances of machines and transformers of similar type lie in a narrow range whatever their size. This makes it easy to check data and to estimate missing values.
  3. Manufacturers' data: Impedances are given in % or p.u. on the equipment's own rating, so they can be used directly after a simple change of base.
  4. Three-phase and single-phase are the same: In p.u. the line and phase values are equal and the factor 3\sqrt3 disappears from the calculations.
  5. Easier hand and computer calculation: The numbers are of order 1, so errors are easy to spot. Load flow and fault programs use p.u. throughout.
  6. Meaningful comparison: A voltage of 0.95 p.u. immediately shows a 5 % drop at any voltage level.