Per unit resistance drop of core type transformer

Short answer

ε_r = (ρ (δ_p L_mtp + δ_s L_mts)) / E_t; if equal current density δ and mean turn L_mt, ε_r = 2 ρ δ L_mt / E_t. This equals full‑load copper loss per phase divided by the phase VA rating.

Derive the expressions for per unit resistance drop of a core type transformer.

Per-unit resistance drop is the full-load resistive voltage drop expressed as a fraction of rated voltage, εr=IpRp/Vp\varepsilon_r = I_pR_p/V_p. It can be found from winding dimensions as below.

Notation

  • TpT_p, TsT_s = primary and secondary turns; IpI_p, IsI_s = currents
  • LmtpL_{mtp}, LmtsL_{mts} = mean lengths of turn
  • apa_p, asa_s = conductor areas; δp\delta_p, δs\delta_s = current densities
  • ρ\rho = resistivity of copper; EtE_t = volts per turn

Derivation

Resistance of each winding:

rp=ρTpLmtpap,rs=ρTsLmtsasr_p = \frac{\rho T_pL_{mtp}}{a_p},\qquad r_s = \frac{\rho T_sL_{mts}}{a_s}

Total resistance referred to primary:

Rp=rp+rs(TpTs)2R_p = r_p + r_s\left(\frac{T_p}{T_s}\right)^2

Per-unit resistance:

εr=IpRpVp=IprpVp+Iprs(Tp/Ts)2Vp\varepsilon_r = \frac{I_pR_p}{V_p} = \frac{I_pr_p}{V_p} + \frac{I_pr_s(T_p/T_s)^2}{V_p}

Since IpTp=IsTsI_pT_p = I_sT_s and Vp/Tp=Vs/Ts=EtV_p/T_p = V_s/T_s = E_t, the second term equals Isrs/VsI_sr_s/V_s. So

εr=IprpVp+IsrsVs\varepsilon_r = \frac{I_pr_p}{V_p} + \frac{I_sr_s}{V_s}

Now Iprp=IpρTpLmtpap=ρ δp TpLmtpI_pr_p = I_p\dfrac{\rho T_pL_{mtp}}{a_p} = \rho\,\delta_p\,T_pL_{mtp} (as Ip/ap=δpI_p/a_p = \delta_p), and Vp=EtTpV_p = E_tT_p:

IprpVp=ρ δpLmtpEt,IsrsVs=ρ δsLmtsEt\frac{I_pr_p}{V_p} = \frac{\rho\,\delta_pL_{mtp}}{E_t},\qquad \frac{I_sr_s}{V_s} = \frac{\rho\,\delta_sL_{mts}}{E_t}

Therefore

εr=ρ(δpLmtp+δsLmts)Et\varepsilon_r = \frac{\rho\left(\delta_pL_{mtp} + \delta_sL_{mts}\right)}{E_t}

If both windings have the same current density δ\delta and a common mean turn LmtL_{mt}:

εr=2ρ δ LmtEt\varepsilon_r = \frac{2\rho\,\delta\,L_{mt}}{E_t}

Other forms

Multiplying the numerator and denominator by IpI_p:

εr=Ip2RpVpIp=full-load copper loss (per phase)VA rating (per phase)\varepsilon_r = \frac{I_p^2R_p}{V_pI_p} = \frac{\text{full-load copper loss (per phase)}}{\text{VA rating (per phase)}}

Example

With ρ\rho = 0.021 Ω-mm²/m, δ\delta = 2.5 A/mm², LmtL_{mt} = 0.9 m and EtE_t = 7.5 V:

εr=2×0.021×2.5×0.97.5=0.0126 p.u.=1.26%\varepsilon_r = \frac{2\times0.021\times2.5\times0.9}{7.5} = 0.0126\ \text{p.u.} = 1.26\%

Conclusions

  • εr\varepsilon_r falls if EtE_t is high (fewer turns) or δ\delta is low.
  • A short mean turn (stepped core, compact windings) reduces both copper loss and εr\varepsilon_r.

✓ Answer checked by Claude Sonnet 5.5