- 2076 Asoj · 7 marks
Salient pole generator phasor diagram in per unit
Short answer
At full load 0.8 lagging, using two-reaction theory: ψ = arctan((V sinφ+IXq)/(V cosφ+IRa)) = 52.18°, load angle δ = ψ−φ = 15.31°. Id=0.79 pu, Iq=0.613 pu. Excitation emf E = V cosδ + Iq Ra + Id Xd = 1.448 pu, voltage regulation=44.8%.
3 phase star connected, 50 Hz synchronous generator has direct axis and quadrature axis reactance of 0.6 pu and 0.45 pu. Draw the phasor diagram at full load 0.8 lagging and hence calculate (i) load angle (ii) Id and Iq (iii) open circuit voltage (iv) voltage regulation. Resistance drop at full load is 0.015 pu.
Using the two-reaction (Blondel) theory: = 0.6 pu, = 0.45 pu, = 0.015 pu, = 1 pu, = 1 pu, pf = 0.8 lagging ().
E (on q-axis)
/:
/ : j Id (Xd - Xq)
/ :
/ .-+ E' = V + I(Ra + jXq)
/.' delta
O-------------- V
\ phi
\ I (psi = phi + delta from q-axis)
(i) Load angle
(ii) and
(iii) Open-circuit voltage (excitation emf)
(iv) Voltage regulation
Answer: δ = 15.31°, I_d = 0.790 pu, I_q = 0.613 pu, E = 1.448 pu, regulation = 44.8%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- 25 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- 30 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- 20 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- Excitation emf of salient pole generator · Electric Machines II, chapter 1
- Internal emf and load angle of salient pole motor · Electric Machines II, chapter 2
- Salient pole motor excitation and reluctance power · Electric Machines II, chapter 2
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Star-delta starting torque ratio and full-load slip · Electrical Machines, chapter 5