20 MVA salient pole motor maximum power

Short answer

By two-reaction theory, excitation voltage Ef = 29007 V per phase (50.24 kV line), load angle δ = 26.38°. Maximum power occurs at δm = 50.36°, with Pmax = 27.14 MW.

A 20 MVA, 3 phase star connected 11 kV, 12 pole 50 Hz salient pole synchronous motor has a direct axis reactance of 50 ohm and quadrature axis reactance of 3 ohm per phase. The armature resistance being negligible. At rated load, unity power factor and rated voltage determine (i) excitation voltage (ii) The maximum value of power angle and corresponding power.

Given: 20 MVA, 11 kV, star, Xd=50 ΩX_d = 50\ \Omega, Xq=3 ΩX_q = 3\ \Omega, Ra=0R_a = 0, rated load at unity pf and rated voltage.

V=110003=6350.85 V per phaseIa=20×1063×11000=1049.73 A (in phase with V)\begin{aligned} V &= \frac{11000}{\sqrt3} = 6350.85\ \text{V per phase} \\ I_a &= \frac{20\times10^6}{\sqrt3 \times 11000} = 1049.73\ \text{A}\ (\text{in phase with } V) \end{aligned}

Method (two-reaction theory, motor, Ra=0R_a = 0): V⃗=E⃗f+jXdI⃗d+jXqI⃗q\vec V = \vec E_f + jX_d\vec I_d + jX_q\vec I_q.

  1. E⃗′=V⃗−jXqI⃗a\vec E' = \vec V - jX_q\vec I_a gives the direction of EfE_f (the q-axis), so its angle is −δ-\delta.
  2. Angle between IaI_a and the q-axis: ψ=δ−ϕ\psi = \delta - \phi (ϕ\phi positive for lagging, negative for leading); Id=Iasin⁡ψI_d = I_a\sin\psi, Iq=Iacos⁡ψI_q = I_a\cos\psi.
  3. Ef=E′+(Xd−Xq)IdE_f = E' + (X_d - X_q)I_d.

(i) Excitation voltage

E⃗′=V−jXqIa=6350.85−j(3×1049.73)=6350.85−j3149.18=7088.8∠−26.38∘ V⇒ δ=26.38∘ψ=δ−0=26.38∘ (upf)Id=1049.73sin⁡26.38∘=466.34 A,Iq=940.45 AEf=E′+(Xd−Xq)Id=7088.8+47×466.34=29007 V per phase=50.24 kV line\begin{aligned} \vec E' &= V - jX_qI_a = 6350.85 - j(3 \times 1049.73) = 6350.85 - j3149.18 \\ &= 7088.8\angle -26.38^\circ\ \text{V} \quad \Rightarrow\ \delta = 26.38^\circ \\ \psi &= \delta - 0 = 26.38^\circ \ (\text{upf}) \\ I_d &= 1049.73\sin26.38^\circ = 466.34\ \text{A},\quad I_q = 940.45\ \text{A} \\ E_f &= E' + (X_d - X_q)I_d = 7088.8 + 47 \times 466.34 \\ &= 29007\ \text{V per phase} = 50.24\ \text{kV line} \end{aligned}

Check: PP at δ=26.38∘\delta = 26.38^\circ from the power-angle equation =20.00= 20.00 MW == rated input.

(ii) Maximum power and its power angle

P=3[EfVXdsin⁡δ+V22(1Xq−1Xd)sin⁡2δ]P = 3\left[\frac{E_fV}{X_d}\sin\delta + \frac{V^2}{2}\left(\frac{1}{X_q}-\frac{1}{X_d}\right)\sin2\delta\right]

Let a=EfVXd=3.6844×106a = \dfrac{E_fV}{X_d} = 3.6844\times10^6 and b=V2(1Xq−1Xd)=12.6378×106b = V^2\left(\dfrac{1}{X_q} - \dfrac{1}{X_d}\right) = 12.6378\times10^6 (per phase).

dPdδ=0⇒2bcos⁡2δ+acos⁡δ−b=0\dfrac{dP}{d\delta} = 0 \Rightarrow 2b\cos^2\delta + a\cos\delta - b = 0:

cos⁡δm=−a+a2+8b24b=0.6380δm=50.36∘Pmax=3asin⁡δm+3b2sin⁡2δm=8.51+18.63=27.14 MW\begin{aligned} \cos\delta_m &= \frac{-a + \sqrt{a^2 + 8b^2}}{4b} = 0.6380 \\ \delta_m &= 50.36^\circ \\ P_{max} &= 3a\sin\delta_m + \tfrac{3b}{2}\sin2\delta_m \\ &= 8.51 + 18.63 = 27.14\ \text{MW} \end{aligned}

The maximum occurs below 90∘90^\circ because of the reluctance term.

Answer: (i) Ef=29007E_f = 29007 V per phase (50.24 kV line), load angle 26.38∘26.38^\circ; (ii) maximum power angle δm=50.36∘\delta_m = 50.36^\circ, Pmax=27.14P_{max} = 27.14 MW.