Chapter 2 · 7 hours
Three Phase Synchronous Motor
IOE past exam questions
Past questions and answers
34 questions set from this chapter, 5 of them more than once. Most asked first.
- Asked 4 times
- 2078 Bhadra · 7 marks
- 2075 Asoj · 7 marks
- 2072 Chaitra · 6 marks
- 2069 Chaitra · 8 marks
A synchronous motor can operate as both inductive and capacitive characteristics. Justify this statement with relevant phasor diagrams. (Explain how a three-phase synchronous motor can be operated to draw lagging as well as leading current from the source.)
Answer
A synchronous motor runs at constant speed whatever its excitation. For a constant load (constant input power ), changing the field current changes the back emf , and hence the magnitude and power factor of the armature current. So the same motor can behave as an inductive (lagging) or a capacitive (leading) load.
Motor equation (per phase, neglected):
The resultant voltage drives the current, which lags by 90°.
1. Under-excitation (): lagging pf (inductive)
V
O-------------->
\`-. /
\ `-. / Er = jIXs
\ `/
I \ Eb (short)
(lags V)
- ; the motor draws a lagging current.
- The armature current supplies the missing magnetisation (demagnetising requirement), like an induction motor or inductor.
2. Normal excitation (): unity pf
- Field current is just enough for the required flux; current is in phase with and is minimum for that load.
O--------------> V
O--------> I (in phase)
\ /
Eb / Er
3. Over-excitation (): leading pf (capacitive)
I (leads V)
^ V
| O---------->
| \ .
| \ . Er
| Eb (long)
- ; the resultant makes the current lead .
- The motor supplies reactive power to the system and acts as a capacitor. Running at no load like this, it is called a synchronous condenser, used for power-factor improvement and voltage control.
Summary
| Excitation | vs | Current | pf | Acts as |
|---|---|---|---|---|
| Under | Large | Lagging | Inductor | |
| Normal | Minimum | Unity | Resistor | |
| Over | Large | Leading | Capacitor |
These variations are shown by the V-curves (armature current vs field current at constant load), whose lowest point is at unity pf.
- Asked 3 times
- 2079 Bhadra · 6 marks
- 2072 Kartik · 8 marks
- 2070 Asar · 8 marks
Explain the variation of armature current and power factor for different values of excitation current (normal excitation, under-excitation and over-excitation) in a synchronous motor with suitable figures and phasor diagrams.
Answer
In a synchronous motor with constant load (constant power ), varying the DC field current changes the back emf . Since and are fixed, stays constant, so the tip of the current phasor moves along a line perpendicular to , while also stays constant.
(a) Normal excitation
- Field current gives such that the current is in phase with : unity pf.
- Armature current is minimum for that load.
(b) Under-excitation
- is smaller; the resultant voltage swings so that the current lags .
- Armature current is larger than at normal excitation; the motor draws lagging reactive power (magnetising current) from the supply.
(c) Over-excitation
- is larger; the current leads .
- Armature current again increases; the motor supplies reactive power to the supply (synchronous condenser action).
Phasors at constant load (V reference, Rs = 0)
I3 (lead, over-excited)
\
\ I1 (upf, normal)
O----+------> V I tip moves on the
/ vertical line I cos(phi)
/ = constant
I2 (lag, under-excited)
V-curves and inverted V-curves
Ia pf
| \ / full load | _
| \ / | / \ (inverted V)
| \ \ / / | / \
| \_\_/_/ no load | / \
+------------> If +--------------> If
lag | upf | lead lag upf lead
- V-curves: vs at constant load, shaped like a "V". The minimum point of each curve is at unity pf. The left side (under-excited) is lagging, the right side (over-excited) is leading. Higher load gives a higher curve.
- Inverted V-curves: pf vs ; the peak is unity pf. The locus of minimum points (unity pf) shifts to the right as load increases, since more excitation is needed at higher load.
| Excitation | pf | Armature current |
|---|---|---|
| Under | Lagging | High |
| Normal | Unity | Minimum |
| Over | Leading | High |
This property lets an over-excited synchronous motor drive its load and also correct the plant power factor.
- Asked 2 times
- 2071 Chaitra · 6 marks
- 2071 Shrawan · 6 marks
Explain why the synchronous motor is not self starting and explain damper winding method of starting of synchronous motor.
Answer
Why a synchronous motor is not self-starting
- When balanced 3-phase supply is given to the stator, a magnetic field rotating at synchronous speed is set up.
- The rotor poles are excited by DC and are stationary at start.
- At one instant, a stator N pole is in front of a rotor S pole: attraction tends to turn the rotor in the direction of the field (say clockwise).
- Half a cycle later (1/100 s at 50 Hz), the stator poles have moved by one pole pitch; now a stator N is in front of the rotor N: repulsion tends to turn the rotor anticlockwise.
- Because of its inertia, the rotor cannot move in such a short time; the torque reverses every half cycle, so the average starting torque is zero. The rotor only vibrates.
t = 0: stator N -> attracts rotor S -> torque CW
t = T/2: stator S -> repels rotor S -> torque CCW
average torque = 0 (rotor stays at rest)
Hence the rotor must first be brought close to synchronous speed by some other means.
Damper winding method (starting as induction motor)
Construction: copper or brass bars are placed in slots in the rotor pole faces and short-circuited at both ends by end rings, forming a squirrel-cage (damper / amortisseur) winding.
Procedure
- Keep the DC field winding open or short-circuited through a discharge resistance (to avoid very high induced voltage in the many-turn field winding).
- Switch on the 3-phase supply (often at reduced voltage through an auto-transformer or star–delta starter to limit current).
- The rotating field induces currents in the damper bars, and the motor starts as an induction motor, accelerating to about 95–98% of synchronous speed.
- Now apply DC excitation to the field. The rotor poles lock with the stator field and are pulled into synchronism.
- At synchronous speed there is no relative motion, so no current flows in the damper bars; they carry current only during speed changes, when they also damp hunting.
Advantages: simple, no separate starting motor, also prevents hunting. Limitation: low starting torque, so it suits motors that start at light load.
- Asked 2 times
- 2083 Baisakh (new course) · 3 marks
- 2081 Bhadra · 8 marks
What is meant by hunting in a synchronous motor? Explain in details and what is done to minimize it.
Answer
Hunting is the periodic oscillation (swinging) of the rotor of a synchronous machine about its steady equilibrium position (load angle ) when the load or supply changes suddenly. The rotor speed swings above and below synchronous speed while the average speed stays synchronous. It is also called phase swinging.
How it occurs
- Suppose the motor runs at load angle with load torque .
- The load is suddenly increased to . The rotor slows down momentarily, and increases to give more torque.
- Due to its inertia, the rotor does not stop at the new angle ; it overshoots to , where the developed torque is more than the load torque.
- The excess torque accelerates the rotor; it swings back past towards a smaller angle; then it is retarded again.
- The rotor thus oscillates about at the natural frequency of the machine–system. Small oscillations die out if there is enough damping.
delta
| .-.
d3 | / \ .-.
d2 |---/-----\---/---\---.-------- new steady value
| / \_/ '-'
d1 |_/
+--------------------------------> time
load step
Causes
- Sudden change in load (especially periodic loads such as compressors and pumps).
- Sudden change in supply voltage or frequency, or faults in the system.
- Sudden change in field current.
- Pulsating torque of the prime mover (generators driven by diesel engines).
- Resonance between the natural frequency of the rotor and the frequency of load pulsations.
Effects
- Large mechanical stresses and fatigue in the shaft.
- Large current and power swings, voltage fluctuations and increased losses.
- If the swing exceeds the stability limit, the machine falls out of step (loses synchronism).
- Can cause resonance and damage.
Methods to minimise hunting
- Damper (amortisseur) windings: short-circuited copper bars in the pole faces. When the rotor swings, relative motion induces currents in them which produce a torque opposing the swing (like an induction motor), damping the oscillation. This is the main method.
- Flywheel: adds inertia and smooths the torque of reciprocating prime movers or loads; it changes the natural frequency away from the forcing frequency.
- Design the machine with suitable synchronising power (proper and excitation), so the natural frequency is not near the frequency of load pulsations.
- Avoid sudden large changes in load, and use fast-acting excitation systems with power system stabilisers.
- Asked 2 times
- 2080 Bhadra · 8 marks
- 2072 Chaitra · 8 marks
A 3-phase, 5 kVA, 208 V, 4-pole, 50 Hz star connected synchronous motor has negligible armature winding resistance and synchronous reactance of 8 ohm per phase. It is operated from the 3-phase, 208 V, 50 Hz power supply and field excitation is adjusted so that the power factor is unity and the motor draws a power of 3 kW from the supply.
(i) Find the back emf (or excitation) voltage and power angle.
(ii) Keeping the excitation voltage constant, the power angle is increased by 20% due to increase in load on the shaft. Calculate the new armature current and power factor.
Answer
Given: star, 5 kVA, 208 V, 50 Hz, , ; unity pf, input 3 kW.
(i) Back emf and power angle
Line value of back emf V.
O-------------------> V = 120.09
O--------> I (upf) |
`-. | jIXs = 66.62
`-. |
`-. Eb = 137.33, delta = 29.02 deg
(ii) Power angle increased by 20%, excitation constant
New input power W.
Answer: (i) E_b = 137.33 V/phase (237.9 V line), δ = 29.02°; (ii) I = 9.85 A, pf = 0.996 lagging (input ≈ 3.53 kW).
- 2082 Baisakh · 6 marks
Explain how synchronous motor adjust itself for the change in load. Elaborate the effects of change in excitation of synchronous motor on armature current and power factor with proper diagram.
Answer
A synchronous motor always runs at synchronous speed . When the shaft load changes it cannot slow down (as an induction motor does); instead the rotor shifts backwards in space by a larger load angle , and the armature current changes to supply the new power.
Adjustment to change in load
- At no load the rotor poles are almost in line with the stator field (), and the motor draws only enough current to meet losses.
- When load torque increases, the rotor momentarily slows down. The rotor poles fall back with respect to the rotating stator field, so increases.
- Back emf stays the same in magnitude (excitation unchanged) but moves further behind . The resultant voltage grows, so armature current increases.
- Power drawn rises until it equals the new load plus losses. The rotor then runs again at with a larger fixed .
- If load exceeds (at for a cylindrical rotor), the motor pulls out of step and stops.
V (fixed)
------------------>
\ delta1
\--------> Ef (light load)
\
\ delta2 > delta1
\------> Ef (heavy load, same length)
Effect of change in excitation (constant load)
With load (and hence ) constant, is constant, so the tip of moves on a line perpendicular to , and is also constant.
| Excitation | vs | Armature current | Power factor |
|---|---|---|---|
| Under-excited | Large | Lagging | |
| Normal | Minimum | Unity | |
| Over-excited | Large | Leading |
I(lead) I(unity)
\ |
\ |
------------ +-------+--------> V
\ |
I(lag) locus of I tip
(I cos(phi) const)
- Raising the field current from a low value first reduces (lagging pf improves) until is minimum at unity pf.
- Further increase makes rise again with a leading pf.
- Plotting against field current gives the V-curves; the pf vs field current curve is an inverted V.
This is why an over-excited synchronous motor can act as a synchronous condenser to improve plant power factor.
- 2082 Baisakh · 8 marks
A 75 kW, 400 V, 4-pole, 3-phase star connected synchronous motor has a resistance and synchronous reactance per phase of 0.04 Ω and 0.4 Ω respectively. Compute for full load 0.8 pf lead the open circuit emf per phase and mechanical power developed. Assume an efficiency of 92.5%.
Answer
Given: kW, V (star), , , pf = 0.8 leading, .
Input power and current
Open-circuit (excitation) emf
For a motor , so . Take as reference; leading current is at .
Line value: V. As expected for leading pf, (over-excited), and the load angle is .
Mechanical power developed
Check: kW, the same value.
(The difference between 78.51 kW and the 75 kW output is the friction, windage, core and stray loss.)
Answer: V per phase (461.0 V line), load angle ; mechanical power developed kW.
- 2081 Bhadra · 8 marks
A synchronous motor absorbing 60 kW is connected in parallel with a factory load of 240 kW having a lagging p.f. of 0.8. If the connected combined load has a p.f. of 0.9, what is the value of the leading kVAR supplied by the motor and at what p.f. is it working?
Answer
The synchronous motor is over-excited so it supplies leading kVAR, which cancels part of the lagging kVAR of the factory load.
Factory load
Combined load
kVAR from the motor
kVAR (lag +)
|
180 + factory load
|
145.3 + combined (pf 0.9)
| motor gives -34.7 kVAR
+--------------------------- kW
60 240 300
Answer: The motor supplies 34.70 kVAR leading and works at a power factor of 0.866 leading (input 69.31 kVA).
- 2080 Bhadra · 5+2 marks
Derive the power angle characteristics of salient pole synchronous machine and also derive condition for maximum power.
Answer
The power angle characteristic gives the power of a salient pole machine as a function of the load angle . Because the air gap is not uniform, the armature current is split into a direct-axis part (sees ) and a quadrature-axis part (sees ), with (two-reaction theory).
Derivation (generator, neglected)
E (q-axis)
/|
jXq Iq / |
/ | jXd Id
/ |
V /delta|
-----+------+------> d-axis
I lags V by phi; psi = delta + phi
Take along the q-axis and lagging by . From the phasor diagram, resolving along the two axes:
Power per phase is . Projecting and on (the angle between and the q-axis is ):
Using :
For three phases multiply by 3. The same expression holds for a motor (with the angle by which lags ).
- First term: excitation power, depends on field current.
- Second term: reluctance power, due to saliency; it exists even when and vanishes for a cylindrical rotor ().
P | .--. resultant
| .' '.
| .' exc. '.
| / .-.reluct.\
|/.-' '-. \
+-----------+----+---- delta
0 ~60-75 90 180 deg
Condition for maximum power
Let and . With :
So maximum power occurs at (unlike the cylindrical machine, where is at ). The salient pole machine is therefore "stiffer": it gives more synchronising power for a given .
- 2079 Bhadra · 6 marks
A 3-phase 9 kVA, 320 V, 4-pole, 50 Hz synchronous motor has negligible armature winding resistance and synchronous reactance of 7.2 ohm per phase is operated from a 3-phase 320 V, 50 Hz power supply and field supply is adjusted so that power factor is unity and motor draws power of 4.6 kW from the supply.
(i) Find back emf and power angle.
(ii) Keeping excitation voltage constant, load on the shaft of motor increased so that load angle increases by 25%. Calculate new value of current drawn by the motor and power factor.
Answer
Assumption: star connection (not stated); neglected.
Given: V, , kW at unity pf.
(i) Back emf and power angle
Motor: , with in phase with :
Line value of V.
V = 184.75 -------------->
\ delta = 17.92 deg |
\ | jXs Ia = 59.76
\--------------------->|
Ef = 194.18
Ia in phase with V
(ii) Load angle increased by 25 %
Power factor lagging.
Check: new input kW, equal to .
Answer: (i) V/phase (336.3 V line), . (ii) A at 0.9975 lagging pf.
- 2078 Bhadra · 7 marks
Salient pole synchronous motor has reactance Xd = 0.8 pu, Xq = 0.4 pu. It is a 3-phase, 50 MVA, 11 kV, 50 Hz. Motor draws rated current at a supply power factor of 0.8 lagging. Rotational losses are 0.15 pu and armature resistance losses are neglected.
a) Calculate the excitation voltage.
b) Find the power due to field excitation and that due to the salience of the machine.
c) If the field current is zero, will the machine stay in synchronism, explain why?
Answer
Work in per unit: pu, rated current pu at 0.8 lagging, so pu.
Method (two-reaction theory, motor, ): .
- gives the direction of (the q-axis), so its angle is .
- Angle between and the q-axis: ( positive for lagging, negative for leading); , .
- .
a) Excitation voltage
kV (line), i.e. 4.62 kV per phase. , as expected for an under-excited (lagging) motor.
b) Excitation power and reluctance power
Check: input pu. Shaft output pu MW.
c) Field current reduced to zero
With only reluctance power remains:
The motor must take pu (0.65 pu load + 0.15 pu rotational loss). Since , the reluctance torque cannot carry the load, so the machine falls out of synchronism. It would stay in step as a reluctance motor only if the shaft load were reduced so that total input is below 0.625 pu (load below 0.475 pu).
Answer: (a) pu (8.0 kV line), ; (b) excitation power 0.353 pu (17.65 MW), saliency power 0.447 pu (22.35 MW); (c) No, it loses synchronism.
- 2078 Kartik · 7 marks
Explain why synchronous motor does not have self-starting torque? Write starting methods and explain the damper winding starting method.
Answer
A synchronous motor has no net starting torque when its field is excited and the stator is switched on, so it must be brought near synchronous speed by some other means.
Why it is not self-starting
- The stator 3-phase supply produces a field rotating at (1500 rpm for 4-pole, 50 Hz) instantly.
- The rotor poles are fixed by DC excitation, and the heavy rotor is at rest.
- Suppose a stator N pole is just ahead of a rotor S pole: attraction pulls the rotor one way. Half a cycle (0.01 s) later a stator S pole sits there and pushes the rotor the opposite way.
- Due to rotor inertia it cannot follow these rapid reversals, so the average torque is zero; the rotor only vibrates.
t = 0 : stator N over rotor S -> torque CW
t = T/2 : stator S over rotor S -> torque CCW
average over one cycle -> 0
Starting methods
- Damper (amortisseur) winding / induction motor starting - most common.
- Pony (auxiliary) motor - a small induction motor or DC machine on the same shaft brings the rotor near , then the field is excited and the machine is synchronised.
- Slip-ring induction motor method - rotor has a 3-phase winding connected through slip rings and resistances; starts as a slip-ring induction motor, then DC is fed to the rotor.
- Variable frequency supply (inverter) - frequency is raised slowly from zero so the rotor follows the field from rest.
- DC exciter on shaft used as a DC motor to run the machine up.
Damper winding starting method
- Copper or brass bars are placed in slots in the pole faces and shorted at both ends by end rings, forming a partial squirrel cage.
- Step 1: Field winding is not connected to DC; it is shorted through a discharge resistance (to avoid very high induced voltage in it). Reduced voltage (autotransformer or star-delta) is applied to the stator.
- Step 2: The rotating field induces currents in the damper bars, producing induction-motor torque. The rotor accelerates to about 95-97 % of .
- Step 3: DC excitation is switched on. The rotor poles lock with the stator poles (synchronising or "pull-in" torque) and the rotor runs at .
- Step 4: At synchronous speed there is no relative motion, so no current flows in the damper bars; they carry current only when speed changes, which also damps hunting.
3-ph AC --> [Autotransformer] --> Stator
|
Rotor: pole faces with damper bars |
Field --[discharge R]-- (start) |
Field --[DC exciter ]-- (near Ns) |
The motor starts with low torque because the cage is small; hence this method suits pumps, fans and compressors started at light load.
- 2078 Kartik · 7 marks
A 3-phase, 11 kV, 50 Hz, 10 pole, 200 kW star connected salient pole synchronous motor has Xd = 1.2 p.u. and Xq = 0.8 p.u. It operates at 0.98 power factor leading. Determine the internal emf and load angle.
Answer
Assumptions: the motor operates at rated voltage and rated current ( pu, pu) with losses and neglected; bases are the machine ratings (11 kV line, 6.351 kV phase).
leading , pu.
Method (two-reaction theory, motor, ): .
- gives the direction of (the q-axis), so its angle is .
- Angle between and the q-axis: ( positive for lagging, negative for leading); , .
- .
Load angle
So the load angle is .
Internal emf
In volts: kV per phase kV line.
V = 1.0 ---------------------->
\ Ia (leads V by 11.5 deg)
\ delta = 34.07
\
'--> Ef = 1.685 pu (Ef > V: over-excited)
Check: pu .
Answer: Internal emf pu (10.70 kV/phase, 18.53 kV line); load angle .
- 2076 Chaitra · 8 marks
State the characteristic features and application of synchronous motor. Explain the effect of excitation on armature current and power factor on synchronous motor with diagram.
Answer
A synchronous motor is an AC motor whose rotor, excited by DC, locks with the stator rotating field and runs at exactly synchronous speed .
Characteristic features
- Runs only at synchronous speed; speed does not change with load (zero speed regulation) as long as supply frequency is constant.
- Not self-starting; needs damper winding, pony motor or variable frequency supply to start.
- Power factor can be controlled by field current: lagging, unity or leading.
- When over-excited it supplies reactive power, so it can work as a synchronous condenser.
- If load torque exceeds the pull-out torque, it falls out of step and stops.
- Needs a DC source for excitation, so it is costlier and more complex than an induction motor.
- Efficiency is high, especially in large and low-speed ratings.
- May hunt (oscillate about ) under sudden load changes; damper windings reduce this.
Applications
- Power factor correction in industries and substations (synchronous condenser).
- Constant speed drives: compressors, large fans, blowers, centrifugal pumps, rolling mills, cement mills.
- Low-speed high-power drives: reciprocating compressors, ball mills.
- Motor-generator sets, frequency changers; small versions (reluctance, hysteresis) in clocks and recorders.
- Voltage regulation at the end of long transmission lines.
Effect of excitation on armature current and pf
At constant load the input is fixed, so the active component is constant. Changing the field current changes and only the reactive component of .
Ia (A)
|\ /
| \ lagging / leading
| \ /
| \___________/ <- min Ia, upf
+----------------------- If
under normal over-excited
- Under-excitation (): resultant makes lag ; large current, lagging pf.
- Normal excitation ( roughly equal to ): in phase with ; current minimum, unity pf.
- Over-excitation (): leads ; current rises again, leading pf.
Ia(lead)
\ Ia(upf)
\ |
-----------\------+------> V
\ |
Ia(lag) |
tip of Ia moves on vertical line
The plot of against is the V-curve; joining the minimum points gives the unity pf compounding curve. Curves for higher load lie above, and the pf curve has an inverted-V shape.
- 2076 Chaitra · 6 marks
A 4 kVA, 110 V, 50 Hz, 3 phase star connected synchronous motor has Xd = 3 ohm/phase and Xq = 2 ohm/phase, when the motor is delivering full load at 0.8 pf lagging at rated voltage. Calculate the excitation emf, load angle and maximum power that motor can develop.
Answer
Given: 4 kVA, 110 V, star, , , full load at 0.8 lagging, neglected.
Method (two-reaction theory, motor, ): .
- gives the direction of (the q-axis), so its angle is .
- Angle between and the q-axis: ( positive for lagging, negative for leading); , .
- .
Load angle
Load angle .
Excitation emf
Line value V.
Maximum power for this excitation
Check at : W . Correct.
Setting with , :
Answer: V per phase (91.0 V line), load angle , maximum power kW at .
- 2076 Asoj · 6 marks
Explain how the damper winding on the rotor pole of a 3-phase synchronous motor can be used to make the motor self starting.
Answer
A damper (amortisseur) winding is a set of copper or brass bars embedded in slots on the rotor pole faces and short-circuited at both ends by end rings. It forms a partial squirrel cage, so the synchronous motor can start as an induction motor and then pull into synchronism.
Construction
end ring end ring
||==========bar============||
||==========bar============|| pole face
||==========bar============||
(bars of all poles joined -> squirrel cage)
- Bars are placed in semi-closed slots on each pole shoe.
- End rings (or segments) join the bars of all poles, giving a closed cage.
- Bar resistance is chosen to give reasonable starting torque.
Starting procedure
- Field kept unexcited: the DC field winding is disconnected from the exciter and shorted through a discharge resistance. This avoids a dangerously high voltage being induced in the many-turn field winding at standstill, and the induced field current adds some starting torque.
- Supply applied: 3-phase supply is given to the stator, usually at reduced voltage (autotransformer or star-delta) to limit starting current.
- Induction motor action: the rotating field cuts the damper bars, induces emf and current in them, and produces torque exactly as in a squirrel-cage induction motor. The rotor accelerates.
- Near synchronous speed: the rotor reaches about 95-98 % of (slip of 2-5 %). It cannot reach by induction action alone.
- Field excited: the discharge resistor is removed and DC is applied. The rotor poles are now magnetised; because slip is small, the stator poles drag the rotor poles into step (pull-in torque), and the motor runs at .
- Full voltage is then applied to the stator.
Behaviour after synchronising
- At there is no relative motion between the stator field and the damper bars, so no emf, no current and no torque in them; they do not affect normal running.
- If the rotor speed swings above or below (hunting), currents are induced that oppose the swing, so the same winding damps hunting.
Limitations
- Starting torque is low (cage is small and fits only on pole faces), so the motor must be started at light load.
- Pull-in is possible only if load and inertia are not too large.
- 2075 Chaitra · 7 marks
State the characteristic features of synchronous motor and explain how a synchronous motor can be operated to draw lagging current as well as leading current.
Answer
A synchronous motor runs at constant synchronous speed and, unlike an induction motor, its power factor can be set by the DC field current.
Characteristic features
- Speed is constant at from no load to full load; it depends only on supply frequency and number of poles.
- Not self-starting; started by damper winding, pony motor or variable frequency.
- Operates at lagging, unity or leading pf depending on excitation.
- Over-excited motor on no load acts as a synchronous condenser.
- Breaks down (pulls out of step) if load exceeds the maximum (pull-out) torque.
- Requires a separate DC excitation source.
- Prone to hunting on sudden load changes.
- High efficiency, especially for large, low-speed drives.
How it draws lagging or leading current
For a motor (with neglected): , so
The current lags the resultant voltage by . Keeping the load (and so and ) constant, only is changed by the field current.
1. Under-excitation, - lagging current
V ---------------------->
\ Er (from Ef tip to V tip)
\ delta
'-----> Ef (short)
Ia = Er/jXs lags V -> lagging pf
The resultant is nearly in phase with , so (90° behind ) lags . The motor takes magnetising (lagging) reactive power from the supply to make up for its weak field.
2. Normal excitation - unity pf
is such that is ahead of ; then is in phase with , and current is minimum.
3. Over-excitation, - leading current
V ---------------------->
\ Er points above V
\ delta
'-----------------> Ef (long)
Ia = Er/jXs leads V -> leading pf
swings ahead of by more than , so leads . The excess field means the motor supplies lagging reactive power to the network, behaving like a capacitor.
| Excitation | Current | pf | |
|---|---|---|---|
| Under | large | lagging | |
| Normal | about | minimum | unity |
| Over | large | leading |
This control is the basis of the V-curves and of using synchronous motors for power factor correction.
- 2075 Chaitra · 7 marks
A 6600 V, 2 MW, 3 phase star connected synchronous motor has Xd = 5 ohm/phase and Xq = 3.1 ohm/phase. Neglecting all losses, calculate the excitation e.m.f. when the motor supplies rated load at 0.8 p.f.
Answer
Assumption: the power factor is not stated as lagging or leading; the usual textbook version of this problem takes 0.8 leading (over-excited motor). The lagging result is given at the end. Star connection, all losses neglected, so input = 2 MW.
Method (two-reaction theory, motor, ): .
- gives the direction of (the q-axis), so its angle is .
- Angle between and the q-axis: ( positive for lagging, negative for leading); , .
- .
Load angle
So .
Excitation emf
Line value V.
Check: MW. Correct.
Ia (leads V by 36.87 deg)
/
/
-----+-------------------> V = 3811 V
\ delta = 7.33 deg
'----------> Ef = 4542 V
If the pf is 0.8 lagging: , , A, V per phase (5634 V line).
Answer (0.8 leading): V per phase kV line, load angle .
- 2075 Asoj · 7 marks
A 25 MVA, 3-phase star connected 11 kV, 12 poles, 50 Hz salient pole synchronous motor has direct axis reactance of 48 ohm and quadrature axis reactance of 3.5 ohm per phase. The armature resistance being negligible. At rated load, unity power factor and rated voltage, Determine: (i) Excitation Voltage (ii) Maximum value of power angle and corresponding power
Answer
Given: 25 MVA, 11 kV, star, , , , rated load at unity pf and rated voltage.
Method (two-reaction theory, motor, ): .
- gives the direction of (the q-axis), so its angle is .
- Angle between and the q-axis: ( positive for lagging, negative for leading); , .
- .
(i) Excitation voltage
Check: at from the power-angle equation MW rated input.
(ii) Maximum power and its power angle
Let and (per phase).
:
The maximum occurs below because of the reluctance term.
Answer: (i) V per phase (72.84 kV line), load angle ; (ii) maximum power angle , MW.
- 2074 Chaitra · 6 marks
In what manner does a synchronous motor adjust itself to an increasing shaft load?
Answer
A synchronous motor meets an increasing shaft load without changing speed. It does so by increasing its load (torque) angle , the angle by which the rotor poles (and ) fall behind the stator field (and ).
Step-by-step action
- At no load, the rotor poles are almost exactly under the stator poles; is very small and the motor draws only a small current for losses.
- Load is increased. Load torque becomes greater than the developed torque, so the rotor decelerates momentarily.
- Rotor falls back. Because the stator field keeps rotating at , the rotor poles slip back by a larger angle . The magnetic "spring" linking the poles is stretched more.
- More current. keeps the same magnitude (field current unchanged) but swings further behind . The resultant voltage increases, so increases.
- More power. Developed power rises:
- New balance. When the developed torque equals load torque plus losses, the rotor again runs at exactly , but with a larger fixed .
V ------------------------------>
\ \
\ \ delta2 (more load)
\ \
\ '----> Ef2 (same length)
delta1
'---------> Ef1 (light load)
Er2 > Er1 -> Ia2 > Ia1
Limit of loading
- Power rises with only up to (cylindrical rotor), where .
- If load is increased beyond this pull-out torque, the rotor cannot stay locked; it falls out of step, and the motor stalls with heavy current (the protection then trips).
- The pull-out limit can be raised by increasing excitation ().
Other effects
- With fixed excitation, the power factor changes with load; for a given the pf moves towards lagging as load increases.
- A sudden load change makes the rotor overshoot and oscillate about the new (hunting); damper windings reduce this.
- 2074 Chaitra · 8 marks
A 3.3 kV, 50 Hz star connected synchronous motor has a synchronous impedance of (0.8 + j55) Ω. It is synchronized to 3.3 kV main from which it is drawing 750 kW at an excitation emf of 4.27 kV (line). Determine the armature current, power factor and power angle. Also find the mechanical power developed. If the stray load loss is 30 kW, find the efficiency.
Answer
Assumption: the printed cannot be right: with 55 Ω the largest power the motor could take is about MW, less than 750 kW. The standard version of this problem has per phase, which is used here.
Given: V, V per phase, input kW, i.e. kW per phase.
Power angle
Power input per phase of a motor:
Armature current and power factor
Power factor leading (over-excited, ).
Check: kW.
Mechanical power and efficiency
Answer: A, pf leading, power angle , mechanical power developed kW, efficiency .
- 2074 Asoj · 6 marks
"Synchronous motor is not self starting". Explain it with proper justification.
Answer
A 3-phase synchronous motor with its field excited cannot start by itself because the average torque on the stationary rotor is zero.
Justification
- When 3-phase supply is switched on, the stator produces a magnetic field that immediately rotates at synchronous speed, (e.g. 1500 rpm for a 4-pole, 50 Hz machine).
- The rotor is excited by DC, so it has fixed N and S poles, and it is at rest with large inertia.
- Instant 1: suppose stator poles are placed so that stator N is just ahead of rotor S. Unlike poles attract, so the rotor gets a torque in, say, the clockwise direction.
- Half a cycle later (0.01 s at 50 Hz): the stator field has moved by one pole pitch; now a stator S pole faces the rotor S pole. Like poles repel and the torque is anticlockwise.
- The torque thus reverses every half cycle. The heavy rotor cannot pick up speed in 0.01 s to follow the field, so it only vibrates.
- The average torque over one cycle is zero, and the motor does not start.
Instant 1 Instant 2 (T/2 later)
stator: N S stator: S N
| | | |
rotor : S N rotor : S N
attract -> clockwise repel -> anticlockwise
average torque = 0
Condition for running
Continuous torque in one direction is possible only when the rotor poles move at the same speed as the stator field, so that they stay locked to opposite stator poles. Therefore the rotor must first be brought close to by another means.
How it is started
- Damper winding (induction motor starting), then DC field is switched on.
- Pony motor on the same shaft.
- Slip-ring induction motor method.
- Variable frequency supply (VFD) raising frequency from zero.
- 2073 Chaitra · 6 marks
Explain the functions of damper winding provided on pole face of rotor of a synchronous motor.
Answer
A damper winding consists of heavy copper or brass bars set in slots on the rotor pole faces and short-circuited at both ends by end rings, like a partial squirrel cage.
pole face (one pole)
_______________________
| o o o o | o = damper bars
|______________________|
\ field coil /
bars of all poles joined by end rings
At synchronous speed there is no relative motion between the stator field and the rotor, so the damper bars carry no current. They work only when the rotor speed differs from .
Functions
-
Starting the motor (self-starting). At start, the rotating stator field induces currents in the bars and produces induction-motor torque. The motor runs up to about 95-98 % of ; then DC excitation is applied and the rotor pulls into step. Without dampers a synchronous motor has zero starting torque.
-
Damping hunting. When load changes suddenly the rotor swings about its new load angle. Any speed above or below causes slip, induces current in the bars and produces a torque opposing the swing (induction motor and generator action). The oscillation dies out quickly.
-
Suppressing negative-sequence fields. Under unbalanced loads or faults, the backward-rotating field induces currents in the bars which oppose it, reducing rotor heating and voltage distortion.
-
Reducing harmonics and voltage distortion by opposing harmonic flux in the air gap, giving a better waveform.
-
Improving stability. By damping oscillations after faults or switching, they help the machine stay in synchronism.
-
Protecting the field winding at start. Because the damper carries the induced currents, the induced voltage stress on the field winding is reduced (the field is also shorted through a discharge resistor).
Limitation
The cage is small (only on pole faces), so starting torque is low; motors started this way are started at light load.
- 2073 Chaitra · 6 marks
A 30 MVA, 3 phase star connected 11 kV, 12 pole 50 Hz salient pole synchronous motor has a direct axis reactance of 55 ohm and quadrature axis reactance of 4 ohm per phase. The armature resistance being negligible. At rated load, unity power factor and rated voltage. Determine (i) Excitation voltage (ii) The maximum value of power angle and corresponding power.
Answer
Given: 30 MVA, 11 kV, star, , , , rated load at unity pf and rated voltage.
Method (two-reaction theory, motor, ): .
- gives the direction of (the q-axis), so its angle is .
- Angle between and the q-axis: ( positive for lagging, negative for leading); , .
- .
(i) Excitation voltage
Check: at from the power-angle equation MW rated input.
(ii) Maximum power and its power angle
Let and (per phase).
:
The maximum occurs below because of the reluctance term.
Answer: (i) V per phase (113.44 kV line), load angle ; (ii) maximum power angle , MW.
- 2073 Shrawan · 7 marks
Explain the effect of varying excitation on armature current and power factor in a synchronous motor. Draw V curves and state their significance.
Answer
At constant load and supply voltage, the field current of a synchronous motor controls the back emf ; this changes the armature current and the power factor, but not the speed or the active power.
Effect of varying excitation
Input power per phase is constant, so the active component is constant; the tip of the phasor moves along a line perpendicular to . Also is constant, so the tip of moves on a line parallel to .
Ia3 (lead) Ia2 (upf)
\ |
\ |
------------+-------------+--------> V
\ | locus of Ia tip
Ia1 (lag) | (Ia cos(phi) const)
- Under-excitation (): lags ; it has a large lagging reactive component. Current is high, pf lagging.
- Increasing : the lagging component falls, so decreases and pf improves.
- Normal excitation: is in phase with ; current is minimum, pf = unity.
- Over-excitation (): leads and grows again; pf leading. The motor now supplies reactive power to the system.
V-curves
Plotting against for constant power output gives V-shaped curves.
Ia
|F F F = full load
| F F H = half load
|H F F H N = no load
| H F F F H
|N H H N
| N H H N
| N N N
+------------------- If
lagging | leading
upf (minima)
- One V-curve for each load (no load, half load, full load); higher load curves lie higher and to the right.
- The minimum point of each curve corresponds to unity pf. The line joining them is the unity pf compounding curve; points left of it are lagging, right are leading.
- Plotting pf against gives inverted V-curves, with peak (pf = 1) at normal excitation.
Significance of V-curves
- Show the field current needed for unity pf (minimum current, least copper loss) at any load.
- Show how much leading kVAR an over-excited motor can supply, so it can be used as a synchronous condenser for power factor correction.
- Show the limits of operation: the left end of each curve (very low ) approaches the stability limit, where the motor would pull out of step.
- Help the operator choose excitation to keep armature current within rating.
- Used to determine the excitation required for voltage control at substations.
- 2073 Shrawan · 7 marks
A 660 V, 3-phase, star-connected synchronous motor draws 50 kW at power factor of 0.8 lagging. Find the new current and power factor when the back e.m.f increases by 25%. The machine has synchronous reactance of 3 Ω and effective resistance is negligible.
Answer
Assumptions: star connection; the shaft load (input power 50 kW) stays the same when the excitation is raised; .
Original operating point
New back emf (+25 %)
Power is unchanged, so :
New current and power factor
Power factor lagging.
Check: kW.
Raising the excitation reduced the reactive (lagging) part of the current, so the current fell and the pf moved close to unity.
Answer: New current A at a power factor of 0.994 lagging (originally 54.67 A at 0.8 lagging).
- 2071 Chaitra · 6 marks
A 20 MVA, 3 phase star connected 11 kV, 12 pole 50 Hz salient pole synchronous motor has a direct axis reactance of 50 ohm and quadrature axis reactance of 3 ohm per phase. The armature resistance being negligible. At rated load, unity power factor and rated voltage determine (i) excitation voltage (ii) The maximum value of power angle and corresponding power.
Answer
Given: 20 MVA, 11 kV, star, , , , rated load at unity pf and rated voltage.
Method (two-reaction theory, motor, ): .
- gives the direction of (the q-axis), so its angle is .
- Angle between and the q-axis: ( positive for lagging, negative for leading); , .
- .
(i) Excitation voltage
Check: at from the power-angle equation MW rated input.
(ii) Maximum power and its power angle
Let and (per phase).
:
The maximum occurs below because of the reluctance term.
Answer: (i) V per phase (50.24 kV line), load angle ; (ii) maximum power angle , MW.
- 2071 Shrawan · 6 marks
A 3 phase, 10 MVA, 2300 V, 60 Hz synchronous motor has Xs = 0.9 pu and negligible stator resistance. The motor is connected to infinite bus. If terminal voltage, Vt = 2300∠0 V and excitation emf Ef = 3450∠120 V [printed "3450V<120"]. Determine power transfer and power factor of machine. Also draw phasor diagram.
Answer
Reading of data: V and V are taken as line values (the rating is 2300 V line), with at as printed. Work in per unit on 10 MVA, 2300 V.
Power transfer
Current and power factor
Using the motor equation :
The real part is negative: since leads , the machine is not taking power; it is delivering 14.43 MW to the bus, i.e. acting as a generator. Taking the generated current pu, it leads by :
Ef (1.5 pu)
\
\ at 120 deg from Vt
\
O-----------> Vt (1.0 pu)
\
\ Ia (motor convention)
v at -126.6 deg
jXs.Ia = Vt - Ef joins tip of Ef to tip of Vt
Ia(gen) = -Ia leads Vt by 53.4 deg
Note: with the machine is beyond the steady-state limit () and the current (2.42 pu) is far above rating, so this point is not a stable working point. If the angle was meant as (motor action, lagging), the same magnitudes result: the motor absorbs 14.43 MW at a pf of 0.596 lagging.
Answer: Power transferred pu MW; power factor (leading as printed, i.e. generating; lagging if is at ).
- 2070 Chaitra · 2+4 marks
Justify, synchronous motor is not self starting. Explain any two starting methods of synchronous motor.
Answer
A synchronous motor with excited field has zero average starting torque, so it is not self-starting.
Justification
- On switching on, the stator field rotates at immediately, while the excited rotor poles are stationary and the rotor has high inertia.
- At one instant a stator N pole faces a rotor S pole and the rotor is pulled, say, clockwise. Half a cycle later (0.01 s at 50 Hz) a stator S pole faces the same rotor pole and pushes it anticlockwise.
- The torque reverses every half cycle; the rotor cannot follow, so the average torque is zero and it only vibrates.
t = 0 : N over S -> attract -> CW
t = T/2 : S over S -> repel -> CCW
average torque = 0
Method 1: Damper winding (induction motor starting)
- Bars in pole-face slots, shorted by end rings, form a squirrel cage.
- Field winding is shorted through a discharge resistor; reduced voltage is applied to the stator.
- The motor starts as an induction motor and reaches about 95-98 % of .
- DC excitation is then switched on; rotor poles lock with stator poles and the motor runs at . The damper then carries no current, except during hunting, which it damps.
Method 2: Pony (auxiliary) motor
[Pony motor] ==shaft== [Sync motor] ---> load
(small IM or DC motor) |
synchroscope/lamps
- A small induction motor (with fewer poles) or DC motor coupled to the shaft runs the unloaded synchronous motor up to about synchronous speed.
- DC field is excited, and the stator is connected to supply when voltage, frequency and phase sequence match (checked with synchroscope or lamps), as in synchronising an alternator.
- The pony motor is then disconnected (or acts as a load-free shaft).
- Suitable only for starting without load.
Other methods: slip-ring induction motor starting, variable frequency (inverter) starting, and using the DC exciter as a motor.
- 2070 Asar · 4 marks
A 400 V, 10 HP, 3-phase synchronous motor has negligible armature resistance and synchronous reactance of 10 Ω/phase. Determine the minimum current and the corresponding induced emf for full load conditions. Assume an efficiency of 85%.
Answer
For a given load, armature current is minimum at unity power factor, because then the whole current is active current. Assumptions: star connection, 1 hp = 746 W.
Minimum current
Induced emf
At unity pf, with in phase with :
V = 230.94 ------------------>|
\ | IXs = 126.68
\ delta |
'------------------------>'
Ef = 263.40 (Ia along V)
Line value V.
Answer: Minimum current A (at unity pf); induced emf V per phase V line.
- 2069 Chaitra · 4 marks
The full load current of 3.3 kVA, star-connected synchronous motor is 160 A at 0.8 pf lagging. The resistance and synchronous reactance of the motor are 0.8 Ω and 5.5 Ω per phase respectively. Calculate the excitation emf. Assume mechanical stray load loss to be 30 kW.
Answer
Reading of data: "3.3 kVA" is a misprint for 3.3 kV (a 3.3 kVA motor cannot take 160 A). Star connection. The stray loss does not affect the excitation emf, since depends only on , and .
Motor equation: , with as reference.
Line value V.
Since the motor is under-excited, which agrees with its lagging power factor.
(For reference: input kW, copper loss kW; the 30 kW stray loss would be used only for output or efficiency.)
Answer: Excitation emf V per phase (2.46 kV line), lagging by .
- 2083 Baisakh (new course) · 3 marks
A 300 V, 1.5 MW, 3 phase synchronous motor has Xd = 4 Ω/phase and Xq = 3 Ω/phase, neglecting all losses, calculate the excitation emf when motor supplies rated load at unity power factor. Calculate the maximum mechanical power which the motor would develop for this field excitation.
Answer
Reading of data: at 300 V a 1.5 MW motor would take about 2900 A, and would be many times the supply voltage, so "300 V" is a misprint for 3300 V (the standard version of this problem). Star connection, losses neglected.
Excitation emf (two-reaction method)
Line value V.
Maximum mechanical power
With W and W:
Answer: V per phase (3744 V line); maximum power MW at .
- 2082 Bhadra (new course) · 3 marks
Define excitation system in synchronous motor. Explain briefly with neat phasor diagram about the effect of changing excitation with constant load in synchronous motor.
Answer
The excitation system of a synchronous motor is the DC source and its control (DC exciter, static rectifier or brushless exciter, with field regulator) that supplies the field current to the rotor poles; it decides the back emf and hence the motor's power factor.
Effect of changing excitation at constant load
With constant load, and are constant. Only the reactive part of changes.
Ia3 (over: lead)
\ Ia2 (normal: upf)
\ |
-----------\------+--------> V
\ |
Ia1 (under: lag)
tip of Ia moves on a line normal to V
| Excitation | pf | ||
|---|---|---|---|
| Under | large | lagging | |
| Normal | minimum | unity | |
| Over | large | leading |
As field current rises, first falls to a minimum (unity pf) and then rises with leading pf, giving the V-curve.
- 2082 Bhadra (new course) · 3 marks
A 3 phase, 100 hp, 440 V, star connected synchronous motor has a synchronous impedance per phase of 0.1+j1 Ω. The excitation and torque losses are 4 kW and may be assumed constant. Calculate the current, power factor and efficiency when operating at full load with an excitation equivalent to 400 line volts.
Answer
Assumptions: 1 hp = 746 W; "full load" means 100 hp shaft output; the 4 kW excitation and friction losses are supplied by the developed power.
Load angle
Mechanical power developed per phase:
Current and power factor
Power factor lagging (under-excited, 400 V < 440 V).
Efficiency
Answer: A, pf lagging, efficiency .
Questions from Old Question Collection (EE 601) (IOE EE 601 exam papers from 2069 Chaitra to 2082 Baisakh), Question bank (ioesolutions) (IOE EE 601 papers 2069 to 2073 (only 2070 Asar not in the collection)) and 2080 course papers (ENEE 253) (ENEE 253 papers, 2082 Bhadra and 2083 Baisakh). Answers are written for this site; check them against your class notes.
Chapter titles and hours from the IOE syllabus ↗