25 MVA salient pole motor maximum power
Short answer
With V=6350.85 V/phase, Ia=1312.16 A at unity pf, two-reaction theory gives excitation voltage Ef = 42.05 kV/phase (72.84 kV line) at load angle 35.87°. Maximum power occurs at δm=53.93°, Pmax=28.75 MW.
A 25 MVA, 3-phase star connected 11 kV, 12 poles, 50 Hz salient pole synchronous motor has direct axis reactance of 48 ohm and quadrature axis reactance of 3.5 ohm per phase. The armature resistance being negligible. At rated load, unity power factor and rated voltage, Determine: (i) Excitation Voltage (ii) Maximum value of power angle and corresponding power
Given: 25 MVA, 11 kV, star, , , , rated load at unity pf and rated voltage.
Method (two-reaction theory, motor, ): .
- gives the direction of (the q-axis), so its angle is .
- Angle between and the q-axis: ( positive for lagging, negative for leading); , .
- .
(i) Excitation voltage
Check: at from the power-angle equation MW rated input.
(ii) Maximum power and its power angle
Let and (per phase).
:
The maximum occurs below because of the reluctance term.
Answer: (i) V per phase (72.84 kV line), load angle ; (ii) maximum power angle , MW.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- 30 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- 20 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- Salient pole motor excitation and reluctance power · Electric Machines II, chapter 2
- Internal emf and load angle of salient pole motor · Electric Machines II, chapter 2
- Salient pole generator phasor diagram in per unit · Electric Machines II, chapter 1
- Excitation emf of salient pole generator · Electric Machines II, chapter 1
- Excitation emf and maximum power of 4 kVA motor · Electric Machines II, chapter 2
- Excitation emf of 6600 V salient pole motor · Electric Machines II, chapter 2
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3