- 2076 Bhadra · 10 marks
Reactance diagram: 300 MVA, 20 kV generator, two motors
Short answer
Using base 300 MVA, Vb=20 kV (gen), 230 kV (line), 13.8 kV (motors). Per-unit reactances: generator j0.2, T1 j0.0857, line (52 Ω) j0.2949, T2 j0.0915, M1 j0.2745, M2 j0.5490.
A 300 MVA, 20 kV three-phase generator has a sub-transient reactance of 20%. The generator supplies two synchronous motors over a 65 kilometre line having transformers at both ends, as shown on the single line diagram. The neutral of one of the motors M1 is grounded while M2 is ungrounded. Rated inputs to the motors are 200 MVA at 13.2 kV and 100 MVA at 13.2 kV for M1 and M2 respectively. For both motors X"d = 20%. The three phase transformer T1 is rated 350 MVA, 230/20 kV with leakage reactance of 10%. Transformer T2 is composed of three single phase transformers, each rated 127/13.2 kV, 100 MVA with leakage reactance of 10%. Series reactance of the transmission line is 0.8 ohm/km. Draw the reactance diagram with all the reactances marked in p.u. Select the generator rating as base in the generator circuit. [Figure: G (Y, neutral grounded through an impedance) → T1 (Δ on generator side, Y grounded on line side) → transmission line TL → T2 (Y grounded on line side, Δ on motor side) → motors M1 (Y, grounded) and M2 (Y, ungrounded).]
In a per-unit reactance diagram every element is expressed on one common MVA base, and the base voltage changes from zone to zone in the ratio of the transformer line-to-line voltages. Resistances, magnetising branches and the grounding impedances are neglected (they carry no current under balanced conditions).
Step 1: Base values in each zone
- Base MVA (all zones): MVA
- Generator zone: kV (given)
- Line zone (T1 is 20/230 kV): kV
- T2 is a Y–Δ bank of single-phase units 127/13.2 kV, so its line-to-line ratio is kV. Motor zone:
Step 2: Change of base
Step 3: Per-unit reactances
(The three-phase rating of T2 is MVA.)
| Element | Rating used | X (pu on 300 MVA) |
|---|---|---|
| Generator G | 300 MVA, 20 kV | 0.2000 |
| T1 | 350 MVA, 20/230 kV | 0.0857 |
| Line | 52 Ω, base 176.33 Ω | 0.2949 |
| T2 | 300 MVA, 220/13.2 kV | 0.0915 |
| Motor M1 | 200 MVA, 13.2 kV | 0.2745 |
| Motor M2 | 100 MVA, 13.2 kV | 0.5490 |
Step 4: Reactance diagram
j0.0857 j0.2949 j0.0915
+---/\/\/-----/\/\/-----/\/\/---+--------+
| T1 line T2 | |
j0.2 j0.2745 j0.5490
| | |
(Eg) (Em1) (Em2)
| | |
+-------------------------------+--------+
reference (neutral) bus
Answer: On 300 MVA base, , , , , and pu, with base voltages 20 kV, 230 kV and 13.8 kV in the three zones.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Impedance diagram: 25 MVA generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: two generators, two motors, j50 Ω line · Power System Analysis I, chapter 3
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- Fault at both ends of a 50 Ω line · Power System Analysis II, chapter 3
- SLG fault on 20 MVA generator · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5