Short answer

Rated line current = 1 pu. Without reactance SLG fault current is 4 pu; with Xn, 3/(0.75+3Xn)=1 gives neutral reactance Xn=0.75 pu = 8.71 Ω.

A 3-phase generator rated 15 MVA, 13.2 kV has a solidly grounded neutral. Its positive, negative and zero sequence reactance are 40%, 30% and 5% respectively. Find the value of reactance to be connected in neutral circuit so that fault current for a single line to ground fault (of negligible fault impedance) at No-load does not exceed line current.

Data: 15 MVA, 13.2 kV, solidly grounded; X1=0.40X_1 = 0.40, X2=0.30X_2 = 0.30, X0=0.05X_0 = 0.05 pu. At no load E=1E = 1 pu; rated line current =1= 1 pu.

Fault current without neutral reactance

If=3EX1+X2+X0=30.75=4 puI_f = \frac{3E}{X_1+X_2+X_0} = \frac{3}{0.75} = 4\ \text{pu}

This is four times rated current, so a neutral reactance XnX_n is needed. XnX_n carries 3Ia03I_{a0}, so it appears as 3Xn3X_n in the zero-sequence network.

Required neutral reactance

If=3EX1+X2+X0+3Xn≤10.40+0.30+0.05+3Xn=3Xn=3−0.753=0.75 pu\begin{aligned} I_f &= \frac{3E}{X_1+X_2+X_0+3X_n} \le 1 \\ 0.40 + 0.30 + 0.05 + 3X_n &= 3 \\ X_n &= \frac{3 - 0.75}{3} = 0.75\ \text{pu} \end{aligned}

Ohmic value

Zbase=(13.2)215=11.616 ΩZ_{base} = \frac{(13.2)^2}{15} = 11.616\ \Omega Xn=0.75×11.616=8.712 ΩX_n = 0.75 \times 11.616 = 8.712\ \Omega

Answer: neutral reactance Xn=0.75X_n = 0.75 pu =8.71 Ω= 8.71\ \Omega.

Check: with XnX_n, If=3/(0.75+2.25)=1I_f = 3/(0.75 + 2.25) = 1 pu = rated current (15×1063×13.2×103=656 A)\left(\frac{15\times10^6}{\sqrt3\times13.2\times10^3} = 656\ \text{A}\right).