- 2073 Shrawan · 6 marks
Neutral reactance for 15 MVA generator
Short answer
Rated line current = 1 pu. Without reactance SLG fault current is 4 pu; with Xn, 3/(0.75+3Xn)=1 gives neutral reactance Xn=0.75 pu = 8.71 Ω.
A 3-phase generator rated 15 MVA, 13.2 kV has a solidly grounded neutral. Its positive, negative and zero sequence reactance are 40%, 30% and 5% respectively. Find the value of reactance to be connected in neutral circuit so that fault current for a single line to ground fault (of negligible fault impedance) at No-load does not exceed line current.
Data: 15 MVA, 13.2 kV, solidly grounded; , , pu. At no load pu; rated line current pu.
Fault current without neutral reactance
This is four times rated current, so a neutral reactance is needed. carries , so it appears as in the zero-sequence network.
Required neutral reactance
Ohmic value
Answer: neutral reactance pu .
Check: with , pu = rated current .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Neutral reactance/resistance to limit L-G current · Power System Analysis II, chapter 5
- Neutral reactance and L-G fault severity · Power System Analysis II, chapter 5 · asked 2×
- L-L fault line voltages, 25 MVA alternator · Power System Analysis II, chapter 5 · asked 2×
- Fault currents of isolated-neutral 380 V generator · Power System Analysis II, chapter 5
- L-L fault currents and voltages, 30 MVA generator · Power System Analysis II, chapter 5
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×