Neutral reactance and L-G fault severity

Short answer

For a solid L-G fault, the fault current is I_f = 3E_a / [j(X1 + X2 + X0 + 3X_n)]. With solid grounding (X_n=0) and X0 << X1, I_LG = 3E_a/(2X1+X0) exceeds the three-phase current E_a/X1, so L-G faults are more severe. The limiting neutral reactance to equalize L-G and three-phase fault currents is X_n = (X1 - X0)/3.

A three phase synchronous generator whose neutral is grounded through a reactance Xn has balanced emfs and sequence reactance as X1, X2 and X0 such that X1 = X2 >> X0. i) Derive the expression for fault current for solid line to ground fault on phase a. ii) Draw the sequence networks and their interconnection for above fault. iii) Show that if neutral is solidly grounded, L-G fault is more severe than 3-phase fault at the terminal of generator. iv) Find the limiting value of neutral grounding reactance so that fault current in L-G and 3 phase faults are equal.

For an L-G fault on a generator grounded through XnX_n, If=3Ea/[j(X1+X2+X0+3Xn)]I_f = 3E_a/[j(X_1 + X_2 + X_0 + 3X_n)]; with solid grounding and X0<X1X_0 < X_1 this exceeds the 3-phase current Ea/X1E_a/X_1, and the two are equal when Xn=(X1−X0)/3X_n = (X_1 - X_0)/3.

i) Fault current for solid L-G fault on phase a

Generator sequence equations (neutral reactance appears as 3Xn3X_n in the zero sequence network):

Va1=Ea−jX1Ia1,Va2=−jX2Ia2,Va0=−j(X0+3Xn)Ia0V_{a1} = E_a - jX_1I_{a1}, \quad V_{a2} = -jX_2I_{a2}, \quad V_{a0} = -j(X_0 + 3X_n)I_{a0}

Boundary conditions: Ib=Ic=0I_b = I_c = 0, Va=0V_a = 0.

From Is=A−1IpI_s = A^{-1}I_p: Ia0=Ia1=Ia2=Ia/3I_{a0} = I_{a1} = I_{a2} = I_a/3.

From Va=Va0+Va1+Va2=0V_a = V_{a0} + V_{a1} + V_{a2} = 0:

Ea−jIa1(X1+X2+X0+3Xn)=0  ⇒  Ia1=Eaj(X1+X2+X0+3Xn)E_a - jI_{a1}(X_1 + X_2 + X_0 + 3X_n) = 0 \;\Rightarrow\; I_{a1} = \frac{E_a}{j(X_1 + X_2 + X_0 + 3X_n)} If=Ia=3Ia1=3Eaj(X1+X2+X0+3Xn)I_f = I_a = 3I_{a1} = \frac{3E_a}{j(X_1 + X_2 + X_0 + 3X_n)}

ii) Sequence networks and interconnection

 Positive      Negative      Zero
 F1 o          F2 o          F0 o
    |jX1          |jX2          |jX0
  (Ea)            |             |j3Xn
    |             |             |
 N1 o          N2 o          N0 o

 L-G fault: networks in series
     Ia1-->
 +-(Ea)-jX1--F1--N2--jX2--F2--N0--j3Xn--jX0--F0-+
 |                                              |
 N1 --------------------------------------------+

(F1 joined to N2, F2 to N0, F0 back to N1: a single series loop carrying Ia1I_{a1}.)

iii) Solidly grounded: L-G more severe than 3-phase fault

With Xn=0X_n = 0 and X1=X2X_1 = X_2:

∣ILG∣=3Ea2X1+X0,∣I3ϕ∣=EaX1=3Ea3X1|I_{LG}| = \frac{3E_a}{2X_1 + X_0}, \qquad |I_{3\phi}| = \frac{E_a}{X_1} = \frac{3E_a}{3X_1}

Since X0≪X1X_0 \ll X_1, 2X1+X0<3X12X_1 + X_0 < 3X_1, so

∣ILG∣>∣I3ϕ∣|I_{LG}| > |I_{3\phi}|

For example, X1=X2=0.2X_1 = X_2 = 0.2, X0=0.05X_0 = 0.05 pu: ILG=3/0.45=6.67I_{LG} = 3/0.45 = 6.67 pu while I3ϕ=1/0.2=5I_{3\phi} = 1/0.2 = 5 pu. Hence an L-G fault at the terminals of a solidly grounded generator is more severe, and the winding bracing must be designed for it, or the neutral grounded through a reactor.

iv) Limiting neutral reactance

For equal fault currents:

3Ea2X1+X0+3Xn=EaX1  ⇒  3X1=2X1+X0+3Xn\frac{3E_a}{2X_1 + X_0 + 3X_n} = \frac{E_a}{X_1} \;\Rightarrow\; 3X_1 = 2X_1 + X_0 + 3X_n Xn=X1−X03X_n = \frac{X_1 - X_0}{3}

With XnX_n larger than this value, the L-G fault current is less than the three-phase fault current. In the example above, Xn=(0.2−0.05)/3=0.05X_n = (0.2 - 0.05)/3 = 0.05 pu.